4.5.6.3 - Manual tests

This function allows the user to test the outputs individually, if the machine is completely shut down (LOFF). To carry out a manual test use the arrow keys to access the output to be tested and press the Enter key (longer than 2 seconds) to activate the modification mode. The password is automatically requested, if it has not previously been verified. The Outputs/Test LED on the user interface begins to flash. Enter the desired test value and again press Enter to start the test. 'TESt' is displayed on the 4- digit display alternately with the value tested. The Outputs/Test LED stops flashing. Press the Enter key or an arrow key to stop the test.

4.5.7 - Description of the Configuration menu

4.5.7.1- General

This menu can be used to display and modify all configura- tions: Factory, Service and User. Only the User Configuration can be modified by the end-user. The Factory, Service and master/slave configurations are not described in this docu- ment. A configuration can only be modified if the unit is fully stopped (LOFF).

The menus User 1 [USEr 1] and User 2 [USEr 2] are pass- word-protected. The other menus are directly accessible, except if item 12 of the User 1 menu (password for all configurations) has been validated.

4.5.7.2 - Password

A password must be entered in order to access the test function or to modify a configuration. It is automatically requested, if necessary: 'EntEr PASS' is displayed on the 4-digit display and the configuration menu LED flashes, indicating that the modifi- cation mode is active. Press the arrow keys until the value '11' is displayed on the 4-digit display. Press Enter to validate this. The configuration menu LED stops flashing. If the password is correct, 'Good' is displayed. If the password is incorrect, 'PASS incorrEct' is displayed. The User password has a default value of 11.

This value can be modified through the Service configuration. The password can be entered if the unit is fully stopped, other- wise 'ACCES dEniEd' (access denied) will be displayed on the 4-digit display. The controller automatically deactivates the password after 5 minutes without activity (i.e. no buttons pressed) or after powering up.

SUB-MENU USER CONFIGURATION

ITEM

USER 1

USER 2

DATE

SCHEDULE 1

SCHEDULE 2

HOLIDAYS

BROADCAST

 

[USER1]

[USER2]*

[dAtE]*

[ScHEduLE 1MEnu]*

[ScHEduLE 2 MEnu]*

[HOLidAy MEnu]*

[BrodCASt]*

0

Return to previous menu

Return to previous

Return to previous

Return to previous menu

Return to previous

Return to previous menu

Return to previous menu

 

 

menu*

menu

 

menu

 

 

1

Circuit selection

Periodic pump start-

Hour*

SUB-MENU:

SUB-MENU:

SUB-MENU:

Broadcast acknowledger

 

 

up*

 

Period 1 [PErIod 1]

Period 1 [PErIod 1]

Holidays 1 [HOLidAy 1]

selection

2

Circuit capacity increase

Night mode - start

Day of the week*

SUB-MENU:

SUB-MENU:

SUB-MENU:

Broadcast activation

 

sequence

hour*

 

Period 2 [PErIod 2]

Period 2 [PErIod 2]

Holidays 2 [HOLidAy 2]

 

3

Ramp selection*

Night mode - end

Day and month*

SUB-MENU:

SUB-MENU:

SUB-MENU:

Outdoor temperature

 

 

hour*

 

Period 3 [PErIod 3]

Period 3 [PErIod 3]

Holidays 3 [HOLidAy 3]

broadcast bus

4

Start-up delay*

Night mode - demand

Year*

SUB-MENU:

SUB-MENU:

SUB-MENU:

Outdoor temperature

 

 

limit in %

 

Period 4 [PErIod 4]

Period 4 [PErIod 4]

Holidays 4 [HOLidAy 4]

broadcast element

5

Water pump selection

Number clock 1*

-

SUB-MENU:

SUB-MENU:

SUB-MENU:

Start month daylight

 

 

 

 

Period 5 [PErIod 5]

Period 5 [PErIod 5]

Holidays 5 [HOLidAy 5]

saving time

6

Water pump changover

Number clock 2*

-

SUB-MENU:

SUB-MENU:

SUB-MENU:

Start day daylight saving

 

delay*

 

 

Period 6 [PErIod 6]

Period 6 [PErIod 6]

Holidays 6 [HOLidAy 6]

time

7

Automatic reset

CCN address *

-

SUB-MENU:

SUB-MENU:

SUB-MENU:

Start hour daylight saving

 

selection*

 

 

Period 7 [PErIod 7]

Period 7 [PErIod 7]

Holidays 7 [HOLidAy 7]

time

8

Demand limit selection

CCN bus*

-

SUB-MENU:

SUB-MENU:

SUB-MENU:

Minutes to add

 

 

 

 

Period 8 [PErIod 8]

Period 8 [PErIod 8]

Holidays 8 [HOLidAy 8]

 

9

Voltage corresponding to

-

-

-

-

SUB-MENU:

End month daylight saving

 

100% of demand limit

 

 

 

 

Holidays 9 [HOLidAy 9]

time

10

Voltage corresponding to

-

-

-

-

SUB-MENU:

End day daylight saving

 

0% of demand limit

 

 

 

 

Holidays 10 [HOLidAy 10]

time

11

Extended display

-

-

-

-

SUB-MENU:

End hour daylight saving

 

selection

 

 

 

 

Holidays 11 [HOLidAy 11]

time

12

Password for all user

-

-

-

-

SUB-MENU:

Minutes to subtract

 

configurations

 

 

 

 

Holidays 12 [HOLidAy 12]

 

13

Software version number

-

-

-

-

SUB-MENU:

-

 

 

 

 

 

 

Holidays 13 [HOLidAy 13]

 

14

-

-

-

-

-

SUB-MENU:

-

 

 

 

 

 

 

Holidays 14 [HOLidAy 14]

 

15

-

-

-

-

-

SUB-MENU:

-

 

 

 

 

 

 

Holidays 15 [HOLidAy 15]

 

16

-

-

-

-

-

SUB-MENU:

-

 

 

 

 

 

 

Holidays 16 [HOLidAy 16]

 

Legend:

*: only displayed if configuration requires.

20

Image 20
Contents Installation, operation and maintenance instructions 30GK Series PRO-DIALOG ControlTable of Contents Safety Considerations Diagnostics Troubleshooting Avoiding electrocution Safety ConsiderationsGeneral General Description Abbreviations usedHardware Description General Control boardElectronic boards Control boxBoard addresses Red LEDGreen LED Orange LED CCN/clock boardEvaporator entering water temperature sensor Evaporator leaving water temperature sensorCondenser entering and leaving water temperature sensors Heat reclaim condenser entering/leaving water temperaturesDescription Connector Terminal Channel User connectionsAvailable Terminals RemarksSetting UP PRO-DIALOG Plus Control Local interface general featuresMain interface Main Interface Button Name DescriptionStopping the unit in local mode Unit start/stop controlDescription Starting unit and selecting an operating typeModifying the value of a parameter/access to a sub- menu MenusSelecting a menu Selecting a menu itemMenu StructureMenu tree StatusDescription of the Information menu Information Menu Format Units DescriptionDescription of the Temperatures menu Temperatures Menu Format Units CommentsDescription of the Pressures menu Pressures Menu Format Units CommentsDescription of the Setpoints menu Setpoints Menu Format Units Range CommentsDescription of the Inputs menu Description of the Outputs/Tests menu GeneralMenu description Inputs Menu Format Units CommentsFormat Units Description Manual tests Description of the Configuration menu GeneralPassword SUB-MENU Period Configuration SUB-MENU Holiday ConfigurationDescription of the User 1 Configuration sub-menu User 1 Configuration SUB-MENU Format Units Default CommentsDate & Time Configuration SUB-MENU Format Comments Description of the User 2 Configuration sub-menuDescription of Date and Time configuration sub Menu Typical timer program Description of the Holidays sub-menusDescription of the Broadcast sub-menu Item # Format CommentsDescription of the Alarms menu Description of the Alarms History menuBroadcast Configuration SUB-MENU Item # Format Comments Alarms Menu Item # Format DescriptionDescription of the Runtimes 1 menu Maintenance menu descriptionRuntime menu description Description of the Runtimes 2 menu Chilss Contact Type Mode Shutdown PRO-DIALOG Plus Control OperationStart/stop control Heating/cooling selectionEvaporator water pump control Control interlock contact Condenser water pump controlEvaporator heater control Control pointDemand limit by 0-10 V d.c. signal Demand limitCapacity control Determining the lead circuitSlave compressor start-up sequence Controlling the EXVHead pressure control on air-cooled units Head pressure control on water-cooled unitsMaster/slave assembly High pressure load shedding functionPumping down Controlling Pro-Dialog Plus units with a System ManagerDiagnostics Troubleshooting Displaying alarmsResetting alarms Optional heat reclaim moduleAlarm codes Alarm Code DescriptionsCCN Compressor faults 6.4.1.1 General DGT only for units with low-temperature optionCompressor protection devices Starter Guard

30GK specifications

The Carrier 30GK is a prominent chiller model known for its efficiency and reliability in various commercial and industrial applications. Offering a blend of advanced technology and robust design, the 30GK series caters to diverse cooling needs while maintaining energy efficiency and low operational costs.

One of the standout features of the 30GK is its use of the latest scroll compressor technology. This contributes to its efficient performance, enabling the chiller to operate at optimal levels while minimizing energy consumption. The scroll compressor is known for its quiet operation, which reduces noise pollution, making it an ideal choice for buildings located in noise-sensitive environments.

The 30GK chiller series is equipped with microchannel coil technology, which allows for improved heat exchange efficiency. The microchannel design uses a compact coil structure that enhances refrigerant flow and reduces refrigerant volume, leading to a smaller footprint compared to traditional coil designs. This innovative design not only saves space but also improves the chiller's overall performance.

Another notable characteristic of the Carrier 30GK is its environmental consciousness. The chiller operates using environmentally friendly refrigerants, aligning with modern regulations and sustainability goals. Its design incorporates energy-efficient components that contribute to significant reductions in greenhouse gas emissions, making it suitable for environmentally responsible projects.

Moreover, the 30GK is designed for easy serviceability, with accessible components that simplify maintenance. This feature is particularly important for facility managers seeking to minimize downtime and keep maintenance costs low. The chiller also includes advanced monitoring and control systems, which enable real-time performance tracking and diagnostics, enhancing operational efficiency.

In terms of performance, the 30GK chiller is known for its wide capacity range, making it versatile for various applications. Whether for commercial spaces, industrial processes, or large buildings, the 30GK can meet the cooling demands reliably.

Overall, the Carrier 30GK chiller represents a perfect balance of cutting-edge technology, energy efficiency, and sustainability. Its features make it a leading choice in the market, suited for those looking to invest in high-quality and dependable cooling solutions.