Code | Alarm name | Description | Action | Pumpdown | Reset type | Probable cause |
1 | Evaporator leaving water thermistor fault | Thermistor outside range | Unit shut down | Yes | Auto | Thermistor or wiring fault or |
| | | | | | bad connection |
2 | Evaporator entering water thermistor fault | Ditto | Unit shut down | Yes | Auto | Ditto |
3 | Condenser leaving water thermistor fault | Ditto | Heating mode: Unit shut down, | Yes | Auto | Ditto |
| | | if control on leaving water. | | | |
| | | Cooling mode: no action | | | |
4 | Condenser entering water thermistor fault | Ditto | Heating mode: Unit shut down, | - | Auto | Ditto |
| | | if control on entering water. | | | |
| | | Cooling mode: no action | | | |
5 | Heat reclaim entering water thermistor fault | Ditto | Unit with heat recalaim option: | - | Auto | Ditto |
| | | heat reclaim mode shut down, | | | |
| | | unit changes over to standard | | | |
| | | cooling mode. If not: no action | | | |
6 | Heat reclaim leaving water thermistor fault | Ditto | None | - | Auto | Ditto |
| | | | | | |
7 | Outdoor temperature sensor fault | Ditto | Reset: normal setpoint used. | - | Auto, if temp. mea- | Thermistor faulty |
| | | Limitation or reset deactivated. | | sured by sensor | |
| | | | | returns to normal | |
8 | CHWS (master/slave) fluid thermistor fault | Ditto | Deactivated | - | Ditto | Themistor faulty |
9 | Suction thermistor fault, compressor A1 | Ditto | Circuit A shut down | Yes | Auto | Ditto |
10 | Suction thermistor fault, compressor B1 | Ditto | Circuit B shut down | Yes | Auto | Ditto |
11 | External 0-10 V dc signal fault | Reset signal outside range | Reset: normal setpoint used | No | Auto | Signal incorrect, wiring error |
| | | Limitation or reset deactivated | | | |
12 | Discharge pressure sensor fault, circuit A | Voltage transmitted by incorrect sensor | Circuit A shut down | Yes | Auto | Sensor fault or wiring error |
13 | Discharge pressure sensor fault, circuit B | Ditto | Circuit B shut down | Yes | Auto | Ditto |
14 | Suction pressure sensor fault, circuit A | Ditto | Circuit A shut down | No | Auto | Ditto |
15 | Suction pressure sensor fault, circuit B | Ditto | Circuit B shut down | No | Auto | Ditto |
16 | Oil pressure sensor fault, compressor A1 | Ditto | Circuit A shut down | No | Auto | Ditto |
17 | Oil pressure sensor fault, compressor B1 | Ditto | Circuit B shut down | No | Auto | Ditto |
18 | Oil pressure sensor fault, compressor A2 | Ditto | Compressor A2 shut down | - | Auto | Ditto |
19 | Oil pressure sensor fault, compressor B2 | Ditto | Compressor B2 shut down | - | Auto | Ditto |
20 | Oil pressure sensor fault, compressor A3 | Ditto | Compressor A3 shut down | - | Auto | Ditto |
21 | Oil pressure sensor fault, compressor B3 | Ditto | Compressor B3 shut down | - | Auto | Ditto |
22 | Oil pressure sensor fault, compressor A4 | Ditto | Compressor A4 shut down | - | Auto | Ditto |
23 | Oil pressure sensor fault, compressor B4 | Ditto | Compressor B4 shut down | - | Auto | Ditto |
24 | Pumpdown pressure sensor fault, circuit A | Ditto | If circuit is in heat reclaim | - | Auto, if press. mea- | |
| | | mode, it goes to cooling mode. | | sured by sensor | |
| | | If not, no action | | returns to normal | |
25 | Pumpdown pressure sensor fault, circuit B | Ditto | Ditto | - | Ditto | Ditto |
26 | Loss of communication with compressor board A1 | Communication with the compressor | Circuit A shut down | No | Auto | Wiring fault, faulty module, |
| | board is lost | | | | incorrect module address |
27 | Loss of communication with compressor board A2 | Ditto | Compressor A2 shut down | No | Auto | Ditto |
28 | Loss of communication with compressor board A3 | Ditto | Compressor A3 shut down | No | Auto | Ditto |
29 | Loss of communication with compressor board A4 | Ditto | Compressor A4 shut down | No | Auto | Ditto |
30 | Loss of communication with compressor board B1 | Ditto | Circuit B shut down | No | Auto | Ditto |
31 | Loss of communication with compressor board B2 | Ditto | Compressor B2 shut down | No | Auto | Ditto |
32 | Loss of communication with compressor board B3 | Ditto | Compressor B3 shut down | - | Auto | Ditto |
33 | Loss of communication with compressor board B4 | Ditto | Compressor B4 shut down | - | Auto | Ditto |
34 | Loss of communication with EXV board | Ditto | Unit shut down | No | Auto | Wiring bus faulty, incorrect |
| | | | | | address or board faulty |
35 | Loss of communication with NRCP board | The board does not respond | Unit shut down, if heat reclaim mode | No | Auto, if board is | NRCP board faulty |
| | | is selected | | again detected | |
36 | Loss of communication with fan board 1 | Ditto | Unit shut down, if the number of | No | Auto | Wiring bus faulty, incorrect |
| | | fan stages per circuit is less than 3. | | | address or board faulty |
| | | If not, circuit A shut down | | | |
37 | Loss of communication with fan board 2 | Ditto | Circuit B shut down | No | Auto | Ditto |
38 | Loss of communication with 4xAI - 2xAO board 1 | Ditto | Unit shut down or no action | No | Auto | Ditto, depending on |
| | | | | | configuration |
39 | Loss of communication with 4xAI - 2xAO board 2 | Ditto | Compressors or circuit shut down | No | Auto | Ditto, depending on |
| | | | | | configuration |
40 | Pumpdown fault, circuit A | End of pumpdown conditions not | Circuit A shut down | No | Manual | EXV or sensor faulty |
| | satisfied | | | | |
41 | Pumpdown fault, circuit B | Ditto | Circuit B shut down | No | Manual | Ditto |
42 | Evaporator frost protection | Unit operating: units shut down if | Unit shut down | No | Auto first time, | Low water flow or |
| | temp. < defrost threshold. | | | then manual | thermistor defective |
| | Unit shut down: if temp < threshold | | | | |
| | and evaporator heater on for more | | | | |
| | than 10 mins. | | | | |
43 | Low evaporator water flow rate. | | Unit shut down | No | Manual | Water pump faulty |
44 | Low suction temperature, circuit A | Circuit operating: saturated suction | Circuit A shut down | No | Manual | Low charge, filter dirty |
| | temp. < defrost threshold and < leaving | | | | ot thermistor faulty |
| | water -16°C for more than 10 mins. | | | | |
45 | Low suction temperature, circuit B | Ditto | Circuit B shut down | No | Manual | Ditto |
46 | High suction overheat, circuit A | EXV fully open | Circuit A shut down | Yes | Manual | Ditto |
47 | High suction overheat, circuit B | Ditto | Circuit B shut down | Yes | Manual | Ditto |
48 | Low suction overheat, circuit A | EXV in min. position, and circuit | Circuit A shut down | Yes | Manual | EXV or thermistor or |
| | superheat below superheat setpoint | | | | transducer defective |
| | -5.5 K, saturated suction temp. above | | | | |
| | MOP for 5 mins. | | | | |