Carrier 30GK manual High pressure load shedding function, Pumping down, Master/slave assembly

Page 31

LOCAL OPERATING MODE

PARAMETER STATUS

HEATING/

LOCAL

SCHEDULE 2

ACTIVE SETPOINT

COOLING

SETPOINT

PROGRAM STATUS

 

OPERATING

SELECTION

 

 

MODE

 

 

 

 

 

 

 

cooling

sp 1

-

cooling setpoint 1

cooling

sp2

-

cooling setpoint 2

heating

-

-

heating setpoint

holidays

auto

occupied

cooling setpoint 1

holidays

auto

unoccupied

cooling setpoint 2

 

 

 

REMOTE OPERATING MODE

 

 

PARAMETER STATUS

 

 

HEATING/

CONTROL

SCHEDULE 2

ACTIVE SETPOINT

COOLING

CONTACT

PROGRAM STATUS

 

OPOERATING

 

 

 

MODE

 

 

 

heating

-

-

heating setpoint

cooling

sp 1

-

cooling setpoint 1

cooling

sp2

-

cooling setpoint 2

-

holidays

occupied

cooling setpoint 1

-

holidays

unoccupied

cooling setpoint 2

 

 

 

CCN OPERATING MODE

 

 

PARAMETER STATUS

 

 

 

 

 

HEATING/COOLING

SCHEDULE 2

ACTIVE SETPOINT

OPERATING MODE

PROGRAM STATUS

 

 

 

 

 

cooling

 

occupied

cooling setpoint 1

cooling

 

unoccupied

cooling setpoint 2

heating

 

-

heating setpoint

5.17 - High pressure load shedding function

This function does not require an additional board. It prevents high pressure a break on a circuit by the following means:

Preventing any capacity increase on the circuit once the high pressure value has reached an initial threshold.

Shedding one or more capacity stages once a second protection threshold has been reached.

In the event of capacity stages being shed, no capacity increase will be authorised on the circuit concerned for a period of 5 minutes.

5.18 - Pumping down

When the lead compressor in each circuit is started or stopped, that circuit goes through a pumping down cycle to purge the evaporator and suction line of refrigerant. The maximum duration of this cycle is 3 minutes.

5.19 - Master/slave assembly

Two PRO-DIALOG Plus units can be linked to produce a master/ slave assembly. The two machines are interconnected over the CCN bus. All parameters required for the master/slave function must be configured through the Service configuration menu.

Master/slave operation requires the connection of a temperature probe at the common manifold on each machine, if the heat exchanger leaving water temperature is controlled.

The master/slave assembly can operate with constant or variable flow. In the case of variable flow each machine must control its own water pump and automatically shut down the pump, if the cooling capacity is zero. For constant flow operation the pumps for each unit are continuously operating, if the system is opera- ting. The master unit can control a common pump that will be activated, when the system is started. In this case the slave unit pump is not used.

All control commands to the master/slave assembly (start/stop, setpoint, heating/cooling operation, load shedding, etc.) are handled by the unit which is configured as the master, and must therefore only be applied to the master unit. They will be trans- mitted automatically to the slave unit. The master unit can be controlled locally, remotely or by CCN commands. Therefore to start up the assembly, simply validate the Master operating type (MASt) on the master unit. If the Master has been confi- gured for remote control then use the remote volt-free contacts for unit start/stop. The slave unit must stay in CCN operating type continuously. To stop the master/slave assembly, select Local Off (LOFF) on the master unit or use the remote volt- free contacts if the unit has been configured for remote control.

One of the functions of the master unit (depending on its con- figuration) may be the designation, whether the master or slave is to be the lead machine or the follower. The roles of lead machine and follower will be reversed when the difference in running hours between the two units exceeds a configurable value, ensuring that the running times of the two units are automatically equalised. The changeover between lead machine and follower may take place when the assembly is started up, or even whilst running. The running time balancing function is not active if it has not been configured: in this case the lead machine is always the master unit.

The lead machine will always be started first. When the lead machine is at its full available capacity, start-up delay (confi- gurable) is initialised on the follower. When this delay has expired, and if the error on the control point is greater than 1.7°C, the follower unit is authorised to start and the pump is activated. The follower will automatically use the master unit active set- point. The lead machine will be held at its full available capa- city for as long as the active capacity on the follower is not zero. When the follower unit receives a command to stop, its evaporator water pump is turned off with 20 seconds delay.

In the event of a communication fault between the two units, each shall return to an autonomous operating mode until the fault is cleared. If the master unit is halted due to an alarm, the slave unit is authorised to start without prior conditions.

5.20- Controlling Pro-Dialog Plus units with a System Manager

Up to eight PRO-DIALOG Plus units (or System Manager compatible units) can be controlled by one control module of the FSM or CSM III type which can handle multi-tasking of control functions such as starting units in sequence.

31

Image 31
Contents 30GK Series PRO-DIALOG Control Installation, operation and maintenance instructionsTable of Contents Safety Considerations Diagnostics Troubleshooting General Safety ConsiderationsAvoiding electrocution Abbreviations used General DescriptionControl box Hardware DescriptionGeneral Control board Electronic boardsOrange LED CCN/clock board Board addressesRed LED Green LEDHeat reclaim condenser entering/leaving water temperatures Evaporator entering water temperature sensorEvaporator leaving water temperature sensor Condenser entering and leaving water temperature sensorsRemarks Description Connector Terminal ChannelUser connections Available TerminalsMain Interface Button Name Description Setting UP PRO-DIALOG Plus ControlLocal interface general features Main interfaceStarting unit and selecting an operating type Stopping the unit in local modeUnit start/stop control DescriptionSelecting a menu item Modifying the value of a parameter/access to a sub- menuMenus Selecting a menuStructure MenuStatus Menu treeInformation Menu Format Units Description Description of the Information menuPressures Menu Format Units Comments Description of the Temperatures menuTemperatures Menu Format Units Comments Description of the Pressures menuSetpoints Menu Format Units Range Comments Description of the Setpoints menuInputs Menu Format Units Comments Description of the Inputs menuDescription of the Outputs/Tests menu General Menu descriptionFormat Units Description Password Description of the Configuration menu GeneralManual tests SUB-MENU Holiday Configuration SUB-MENU Period ConfigurationUser 1 Configuration SUB-MENU Format Units Default Comments Description of the User 1 Configuration sub-menuDescription of Date and Time configuration sub Menu Description of the User 2 Configuration sub-menuDate & Time Configuration SUB-MENU Format Comments Item # Format Comments Typical timer programDescription of the Holidays sub-menus Description of the Broadcast sub-menuAlarms Menu Item # Format Description Description of the Alarms menuDescription of the Alarms History menu Broadcast Configuration SUB-MENU Item # Format CommentsRuntime menu description Description of the Runtimes 2 menu Maintenance menu descriptionDescription of the Runtimes 1 menu Heating/cooling selection Chilss Contact Type Mode ShutdownPRO-DIALOG Plus Control Operation Start/stop controlControl point Evaporator water pump control Control interlock contactCondenser water pump control Evaporator heater controlDetermining the lead circuit Demand limit by 0-10 V d.c. signalDemand limit Capacity controlHead pressure control on water-cooled units Slave compressor start-up sequenceControlling the EXV Head pressure control on air-cooled unitsControlling Pro-Dialog Plus units with a System Manager Master/slave assemblyHigh pressure load shedding function Pumping downOptional heat reclaim module Diagnostics TroubleshootingDisplaying alarms Resetting alarmsAlarm Code Descriptions Alarm codesCCN Starter Guard Compressor faults 6.4.1.1 GeneralDGT only for units with low-temperature option Compressor protection devices

30GK specifications

The Carrier 30GK is a prominent chiller model known for its efficiency and reliability in various commercial and industrial applications. Offering a blend of advanced technology and robust design, the 30GK series caters to diverse cooling needs while maintaining energy efficiency and low operational costs.

One of the standout features of the 30GK is its use of the latest scroll compressor technology. This contributes to its efficient performance, enabling the chiller to operate at optimal levels while minimizing energy consumption. The scroll compressor is known for its quiet operation, which reduces noise pollution, making it an ideal choice for buildings located in noise-sensitive environments.

The 30GK chiller series is equipped with microchannel coil technology, which allows for improved heat exchange efficiency. The microchannel design uses a compact coil structure that enhances refrigerant flow and reduces refrigerant volume, leading to a smaller footprint compared to traditional coil designs. This innovative design not only saves space but also improves the chiller's overall performance.

Another notable characteristic of the Carrier 30GK is its environmental consciousness. The chiller operates using environmentally friendly refrigerants, aligning with modern regulations and sustainability goals. Its design incorporates energy-efficient components that contribute to significant reductions in greenhouse gas emissions, making it suitable for environmentally responsible projects.

Moreover, the 30GK is designed for easy serviceability, with accessible components that simplify maintenance. This feature is particularly important for facility managers seeking to minimize downtime and keep maintenance costs low. The chiller also includes advanced monitoring and control systems, which enable real-time performance tracking and diagnostics, enhancing operational efficiency.

In terms of performance, the 30GK chiller is known for its wide capacity range, making it versatile for various applications. Whether for commercial spaces, industrial processes, or large buildings, the 30GK can meet the cooling demands reliably.

Overall, the Carrier 30GK chiller represents a perfect balance of cutting-edge technology, energy efficiency, and sustainability. Its features make it a leading choice in the market, suited for those looking to invest in high-quality and dependable cooling solutions.