Ferguson JWSH100250, JWSH100150 warranty Heater Wiring

Page 14

3.This unit may never be connected to any existing heating system or component(s) previously used with non-potable water heating appliance.

4.When the system requires water for space heating at temperatures higher than required for domestic water purposes, a tempering valve must be installed. Please refer to installation diagrams on pages 23 through 28 in back of manual for suggested piping arrangements.

HEATER WIRING

IF ANY OF THE ORIGINAL WIRE AS SUPPLIED WITH THE APPLIANCE MUST BE REPLACED, IT MUST BE REPLACED WITH 105°C OR ITS EQUIVALENT, EXCEPT IN THE BURNER HOUSING. IN THIS CASE USE 200°C WIRE.

THE COMPUTER CONTROL REQUIRES A SOURCE OF STABLE CLEAN ELECTRICITY FOR PROPER OPERATION. INSTALLING THE HEATER ON A BRANCH CIRCUIT THAT HAS ELECTRONIC NOISE, IS SUBJECT TO FLUCTUATIONS IN VOLTAGE LEVEL OR HAS AN APPLIANCE WHICH GENERATES EMF OF RFI INTERFERENCE CAN CAUSE

THE CONTROLLER TO MALFUNCTION. A HIGH QUALITY POWER CONDITIONER MUST BE INSTALLED IF THE ABOVE CONDITIONS EXIST. MALFUNCTIONS CAUSED BY A POOR ELECTRICAL SUPPLY ARE NOT COVERED UNDER YOUR WARRANTY.

The controller is wired to the heater as shown in Figure 15. The model and rating plate provides the electrical information needed to size the complete heater branch supply.

All electrical work must be installed in accordance with the Canadian Electrical Code, CSA C22.1 and local requirements.

When installed, the appliance must be electrically grounded in accordance with local codes or, in the absence of local codes, with the Canadian Electrical Code, CSA C22.1.

DO NOT ENERGIZE THE BRANCH CIRCUIT BEFORE THE HEATER TANK IS FILLED WITH WATER.

NOTE: This controller is Polarity Sensitive. If the Hot and Neutral Supply Voltage is reversed, the controller will not sense flame. Verify polarity before connecting the unit.

FIGURE 15.

14

Image 14
Contents Models AJWSH100150 Thru AJWSH100250 PrintedModels AJWSH100150 Thru AJWSH100250 ROUGH-IN-DIMENSIONS ForewordTable of Contents FeaturesInstallation Instructions Locating the Heater ClearancesMechanical Exhausting of Room AIR Hard WaterAIR Requirements Unconfined SpaceCanadian Power Vent Canadian Direct Vent Masonry Side Walls Direct Vent Terminal InstallationDirect Venting Wooden Side WallsVertical Vent Terminal Installation Installation SequenceInitial Preparation Installation of Vent SystemVent Pipe Preparation Selection of MaterialsControls and Switches GAS PipingConnection of GAS Pipe AJWSH100199 & AJWSH100250 Models OnlySystem Connections Heater Wiring Using the Electronic Controller OverviewOperating States Changing the Display Units Viewing the Fault History Prior to Start UPAdjustment Procedure Operating InstructionsMaintenance General InformationAJWSH100150 only AJWSH100199 & AJWSH100250 Models only Draining Powered Anode SystemFlushing Sediment RemovalDrain Valve and Access Panels Vent SystemInstallation Diagrams Page Must be Identical Heaters Page Page Manifold Kits Checklist and Service Information TROUBLE-SHOOTINGMotor RUNS, Burner Lights Momentarily Then Locks OUT Replacement PartsMotor will not RUN GAS Fails to Shut OFFModels AJWSH100150 thru AJWSH100250 Limited Warranty Page Page Hill Street West Fergus, on Canada N1M