DRAIN VALVE AND ACCESS PANELS

The heaters are equipped with a 3/4" drain valve.

An access panel covers the cleanout opening in the tank which is sealed by a gasket and cover, figure 25.

RELIEF VALVE

At least twice a year, the temperature and pressure relief valve should be checked to ensure that it is in operating condition. To check the relief valve, lift the lever at the end of the valve several times. The valve should seat properly and operate freely.

If water does not flow, remove and inspect for obstructions or corrosion. Replace with a new valve of the recommended size as necessary. Inspection of the valve should be performed at least every three years. Do not attempt to repair the valve, as this could result in improper operation and a tank explosion. In areas with poor water conditions, it may be necessary to inspect the T&P valve more often than every three years.

CAUTION

BEFORE MANUALLY OPERATING THE VALVE, MAKE SURE THAT A DRAIN LINE HAS BEEN ATTACHED TO THE VALVE TO DIRECT THE DISCHARGE TO AN OPEN DRAIN. FAILURE TO TAKE THIS PRECAUTION COULD MEAN CONTACT WITH EXTREMELY HOT WATER PASSING OUT THE VALVE DURING THIS CHECKING OPERATION.

If the temperature and pressure relief valve on the heater discharges periodically or continuously, it may be due to thermal expansion of water in a closed water supply system, or, it may be due to a faulty relief valve.

Thermal expansion is the normal response of water when it is heated. In a closed system, thermal expansion will cause the system pressure

to build until the relief valve actuation pressure is equaled. Then, the relief valve will open, allowing some water to escape, slightly lowering the pressure.

Contact your water supplier or local plumbing inspector on how to control this situation.

Two common corrections are listed in the Checklist and Service Information which appears later in this manual.

ABOVE ALL, DO NOT PLUG THE TEMPERATURE AND PRESSURE RELIEF VALVE. THIS IS NOT A SOLUTION AND CAN CREATE A HAZARDOUS SITUATION.

CIRCULATING PUMP

The water heating system may include a circulating pump. Where used, it should be lubricated as directed by the circulator manufacturer.

VENT SYSTEM

Examine the vent system every 3 months. Points of inspection are as follows:

1.Check for obstructions and/or deterioration of vent piping and vent hood. Replace immediately where needed.

2.Vent pipe and vent hood screen should be cleaned of foreign material and soot. The screen is located inside the vent hood outlet and is accessible from the outside of the hood. Do not reach inside the vent hood when the heater is in operation.

3.Check all vent system connections for leakage and reseal as required using Hi Temp Silicone sealer or equivalent.

24

Image 24
Contents Models AJWSH100150 Thru AJWSH100250 PrintedModels AJWSH100150 Thru AJWSH100250 ROUGH-IN-DIMENSIONS ForewordTable of Contents FeaturesInstallation Instructions Locating the Heater ClearancesHard Water AIR RequirementsMechanical Exhausting of Room AIR Unconfined SpaceCanadian Power Vent Canadian Direct Vent Direct Vent Terminal Installation Direct VentingMasonry Side Walls Wooden Side WallsVertical Vent Terminal Installation Installation SequenceInstallation of Vent System Vent Pipe PreparationInitial Preparation Selection of MaterialsControls and Switches GAS PipingConnection of GAS Pipe AJWSH100199 & AJWSH100250 Models OnlySystem Connections Heater Wiring Using the Electronic Controller OverviewOperating States Changing the Display Units Viewing the Fault History Prior to Start UPAdjustment Procedure Operating InstructionsMaintenance General InformationAJWSH100150 only AJWSH100199 & AJWSH100250 Models only Powered Anode System FlushingDraining Sediment RemovalDrain Valve and Access Panels Vent SystemInstallation Diagrams Page Must be Identical Heaters Page Page Manifold Kits Checklist and Service Information TROUBLE-SHOOTINGReplacement Parts Motor will not RUNMotor RUNS, Burner Lights Momentarily Then Locks OUT GAS Fails to Shut OFFModels AJWSH100150 thru AJWSH100250 Limited Warranty Page Page Hill Street West Fergus, on Canada N1M