Ferguson JWSH100150, JWSH100250 warranty Flushing, Draining, Sediment Removal, Lime Scale Removal

Page 23

FLUSHING

1.Turn off the heater electrical disconnect switch.

2.Open a hot water faucet until the water runs cool and then close the hot water faucet.

3.Open the drain valve and allow water to flow until it runs clean.

4.Close the drain valve when finished flushing.

5.Turn on the heater electrical disconnect switch.

DRAINING

The heater must be drained if it is to be shut down and exposed to freezing temperatures. Maintenance and service procedures may also require draining the heater.

1.Turn off the heater electrical disconnect switch.

2.Open a nearby hot water faucet until the water runs cool.

3.Close the cold water inlet valve to heater.

4.Open the heater drain valve.

5.If the heater is being drained for an extended shutdown, it is suggested the drain valve be left open during this period.

• Follow FILLING instructions when restoring hot water service.

SEDIMENT REMOVAL

Waterborne impurities consist of the particles of soil and sand which settle out and form a layer of sediment on the bottom of the tank.

For convenience, sediment removal and lime scale removal should be performed at the same time.

LIME SCALE REMOVAL

The amount of calcium carbonate (lime) released from water is in direct proportion to water temperature and usage. The higher the water temperature or water usage, the more lime deposits are dropped out of the water. This is the lime scale which forms in pipes, heaters and on cooking utensils.

Lime accumulation not only reduces the life of the equipment but also reduces efficiency of the heater and increases fuel consumption.

The usage of water softening equipment greatly reduces the hardness of the water. However, this equipment does not always remove all of the hardness (lime). For this reason it is recommended that a regular schedule for deliming be maintained.

The depth of lime buildup should be measured periodically. Heaters will have about 3" (7.6cm) of lime buildup when the level of lime has reached the bottom of the cleanout opening or about 1" (2.5cm) of lime buildup if it has reached the drain valve opening. A schedule for deliming should be set up, based on the amount of time it would take for a 1" (2.5cm) buildup of lime.

Example 1:

Initial inspection shows 1/2" (1.3cm) of lime accumulation. Therefore, the heater can be delimed once a year.

Example 2 :

Initial inspection shows 2" (5cm) of lime accumulation. Therefore, the heater should be delimed every 3 months.

Sediment and lime scale removal may be accomplished through the cleanout opening furnished on the heater, see Figure 25. The heater must be drained, see DRAINING, before removing cleanout cover on tank.

FIGURE 16.

To dissolve and remove the more stubborn mineral deposits, UN•LIME® Professional Delimer should be used.

UN•LIME® Professional Delimer is an easy to handle patented food grade acid formulated specifically for lime scale removal from all types of water using equipment. Available in 1 gallon (3.8L) (part no. 4763) and 5 gallon (19L) (part no. 4813) sizes. Hydrochloric base acids are not recommended for use on glass-lined tanks.

Form No. 4800, entitled “Why, When and How”, describes tank cleaning methods and materials. UN•LIME and the booklet may be obtained through the tech. center.

The cleanout opening is shown in Figure 16. To clean heater through cleanout opening, proceed as follow:

1.Turn off the water heater electrical disconnect switch and open a nearby hot water faucet until the water runs cool, draining the water heater completely.

2.Remove outer cover plate from lower side of heater jacket.

3.Remove cover from cleanout opening.

4.Remove lime, scale or sediment using care not to damage the glass-lining.

5.Inspect cleanout plate gasket: If new gasket is required, replace with kit # 9004099215.

6.Install cleanout plate. Be sure to draw plate up tight by tightening screws securely.

7.Close drain valve, open water inlet line and turn on the water heater electrical disconnect switch.

8.Check for water leakage.

9.Replace outer jacket cover plate.

POWERED ANODE SYSTEM

The (A)JWSH heaters are factory equipped with a powered anode system. The anodes are of a permanent design and do not need replacing unless damaged.

23

Image 23
Contents Printed Models AJWSH100150 Thru AJWSH100250Foreword Models AJWSH100150 Thru AJWSH100250 ROUGH-IN-DIMENSIONSFeatures Table of ContentsInstallation Instructions Clearances Locating the HeaterUnconfined Space Hard WaterAIR Requirements Mechanical Exhausting of Room AIRCanadian Power Vent Canadian Direct Vent Wooden Side Walls Direct Vent Terminal InstallationDirect Venting Masonry Side WallsInstallation Sequence Vertical Vent Terminal InstallationSelection of Materials Installation of Vent SystemVent Pipe Preparation Initial PreparationGAS Piping Controls and SwitchesAJWSH100199 & AJWSH100250 Models Only Connection of GAS PipeSystem Connections Heater Wiring Overview Using the Electronic ControllerOperating States Changing the Display Units Prior to Start UP Viewing the Fault HistoryOperating Instructions Adjustment ProcedureGeneral Information MaintenanceAJWSH100150 only AJWSH100199 & AJWSH100250 Models only Sediment Removal Powered Anode SystemFlushing DrainingVent System Drain Valve and Access PanelsInstallation Diagrams Page Must be Identical Heaters Page Page Manifold Kits TROUBLE-SHOOTING Checklist and Service InformationGAS Fails to Shut OFF Replacement PartsMotor will not RUN Motor RUNS, Burner Lights Momentarily Then Locks OUTModels AJWSH100150 thru AJWSH100250 Limited Warranty Page Page Hill Street West Fergus, on Canada N1M