Rheem RTG2-53-(PVN)(PVP)(XN)(XP) Vertical Vent Termination Location, Vertical Vent Installation

Page 15

Vertical Vent Termination Location

Small (6” min) (15 cm) section of vent

Elbow

The location of the vent terminal depends on the following minimum clearances and considerations (see diagram at left):

Minimum twelve (12) inches (30 cm) above roof.

Minimum twelve (12) inches (30 cm) above anticipated snow level.

Min. 12" (30 cm) Above Roof

Min. 12" (30 cm) Above Anticipated Snow Level

Max. 24" (60 cm) Above Roof (Without Additional Support)

Vent Pipe

Through Roof

Termination Elbow w/ Protective Screen

Maximum twenty-four (24) inches (60 cm) above roof level without additional support for vent.

Four (4) feet (1.2 m) from any gable, dormer or other roof structure with building interior access (i.e., vent, window, etc.).

Ten (10) feet (3 m) from any forced air inlet to the building. Any fresh or make-up air inlet such as a dryer or furnace area is considered to be a forced air inlet.

Vertical Vent Installation

Notice: Only Rheem

 

A fire stop plate should be installed at every

Install adequate flashing where the vent pipe

 

penetration of a floor or ceiling if the vent is

passes through the roof. Determine the vent

approved termination

 

 

not running in a fire-rated shaft. Maintain the

terminal height and install the vent pipe

and parts should be used

 

 

recommended air space clearance to

 

 

 

 

accordingly. Refer to the diagram above for

during installation.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

combustible materials and building insulation.

proper vent terminal height. Connect vent

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Notice: Follow vent

 

 

 

 

 

Once the vent terminal location has been

elbow onto vertical pipe through roof.

 

 

 

 

 

Connect short piece of vent pipe

manufacturer’s installation

determined, make a hole through the roof and

(approximately 6” long [15 cm]) to

instructions and their

 

interior ceiling to accommodate the vent pipe.

 

elbow, and the terminal elbow with the

recommended clearances to

Complete the vent pipe installation to the

protective screen.

 

combustibles as required.

water heater’s vent connector fitting on the

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

water heater vent collar outlet. Support

 

 

 

 

The vent roof system must terminate at least

 

 

 

 

 

 

 

 

 

 

 

 

 

 

vertical or horizontal runs as previously

1 foot (30 cm) above the roof line and at least

 

 

 

 

 

 

 

 

 

 

 

 

 

 

mentioned. If required, use silicone sealant

2 feet (61 cm) higher than any portion of the

 

 

 

 

 

 

 

 

 

 

 

 

 

 

at the point the vent connector joins the

 

 

 

 

building within 10 feet (3 m).

 

 

 

 

 

 

 

 

 

 

 

 

 

 

water heater.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Install supports every 5 feet (1.5 m) vertically

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

along the vent pipe route. Vertical supports

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

are required after every transition to vertical

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

and are required after

 

 

 

 

 

 

 

 

 

Storm

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Rain Cap

every offset elbow.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Storm

 

 

 

When the vent is free-

 

 

 

 

 

 

 

 

 

Collar

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Collar

 

Adjustable

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Adjustable

 

 

 

 

 

 

 

 

 

 

 

standing and penetrates

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Roof

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Roof Flashing

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Flashing

a roof/ceiling, another

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Vent Pipe

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Vent Pipe

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

means of support must

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Support

 

 

 

 

 

 

 

 

 

 

 

Support

 

 

 

 

 

 

 

 

 

 

 

 

Firestop

 

 

 

 

 

 

 

 

 

 

Firestop

be used at a second

 

 

 

 

 

 

 

 

 

Clamp

 

 

 

 

 

 

 

 

 

 

 

 

Clamp

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

location.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Chase Requires

 

 

 

 

 

 

 

 

 

 

Chase Requires

 

 

 

 

 

 

 

Follow the vent

 

 

 

6" (15 cm) Clearance

 

 

 

 

 

 

6" (15 cm) Clearance

 

 

 

manufacturer’s

 

 

 

to Combustibles

 

 

 

 

 

 

 

 

 

 

to Combustibles

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

recommended

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

installation instructions

 

 

1/4" per foot upward slope

 

 

 

 

 

1/4" per foot upward slope

 

 

 

provided with the vent

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

purchased from the

3" (8 cm) Clearance

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

manufacturer.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Firestop

 

3" (8 cm) Clearance

 

 

 

 

 

 

Firestop

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2'

 

 

 

 

 

 

 

 

 

 

 

Support

 

 

2'

 

 

 

 

 

 

 

 

 

 

Support

 

 

(61 cm)

 

 

 

 

 

 

 

 

 

 

 

 

(61 cm)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Hanger

 

 

 

 

 

 

 

 

 

 

 

Hanger

 

 

Max

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Condensate

 

 

Max

 

 

 

 

 

 

Condensate

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Trap

 

 

 

 

 

 

 

 

 

 

 

 

 

Trap

 

 

 

 

 

 

 

 

 

 

 

 

Vent

 

To Drain. Dispose of

 

 

 

 

 

 

 

 

 

Vent

To Drain. Dispose of

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

condensate in accordance

 

 

 

 

 

 

 

 

 

condensate in accordance

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Adapter

with local codes

 

 

 

 

 

 

 

 

 

Adapter

 

 

to local codes

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Standard Vertical Vent Termination

 

Alternate Vertical Vent Termination

 

with Rain Cap

15

Image 15 Contents
Defects or other reproductive harm Tankless Water HeaterYou can find them on a label on the appliance That will result in death or seriousInjury Install and Properly Vent the Water HEATER… N G E R Natural GAS and Liquefied Petroleum Models Read and Follow this Safety Information Carefully Location of the Outdoor water heater Installing the Outdoor water heaterLocation of Indoor Water Heater Installing the Indoor water heaterInspect Shipment Installing the water heaterCombustion and Ventilation Air Indoor Water Heater Only Corrosive AtmospheresMinimum Vent Length The venting VentingVenting Lengths Maximum Vent Length Venting Through Closed Spaces Appliance Vent Adapter Draining the Condensate Horizontal Vent Terminal Location Canadian InstallationsAdditional Considerations Indoor Water HeaterVent Horizontal Wall Thimble Installation Vertical Vent Termination Location Vertical Vent InstallationMounting the Water Heater Thermal ExpansionWater Supply Connections Lines.Relief Inlet Relief ValveHigh Altitude Leak TestingPressure Testing the Gas Supply System Gas SupplyRemote Control Installation Connecting the remote control to the water heater Remote Control InstallationElectrical Connection Indoor water heaters onlyIndoor or Outdoor water heaters Indoor Models SwitchDo’s Hot and Cold Pipe Insulation InstallationDuring Installation of this water heater… Insulation BlanketsInstallation Check List To Turn OFF GAS to Appliance Lighting the water heaterOperating the water heater Safety PrecautionsWater Temperature Setting Time/Temperature Relationship in ScaldsWater Temperature Setting… Routine Preventative Maintenance HousekeepingDrain heater. See Draining Water Heater section on Condensate Trap Inspection Venting System InspectionBurner Inspection Vacation and Extended Shut-DownFreeze Protection Draining the Water HeaterBefore You Call For Service… Outdoor Water Heater Only Indoor Water Heater OnlyInstructions For Placing a Parts Order Replacement PartsTemperature Setting DIP Switch Adjustment If YOU Need Service