Bradford-White Corp IGE-199C Series GAS Meter Size -NATURALGAS only, GAS Pressure Regulation

Page 19

Check the type of gas and the gas inlet pressure before connecting the EVERHOT water heater to the gas supply. If the gas supply type does not match the type shown on the water heater rating plate, then DO NOT connect the water heater. Contact your Bradford White supplier for the correct water heater.

GAS METER SIZE –NATURALGAS ONLY

Be sure that the gas meter has sufficient capacity to supply the full rated gas input of the water heater as well as the requirements of all other gas fired equipment supplied by the meter. If the gas meter is too small, ask the gas company to install a larger meter having adequate capacity.

GAS PRESSURE REGULATION

Minimum and maximum gas supply pressures are listed below: The minimum gas pressure specified below is required for the full input rating specified on the water heater rating plate.

Natural Gas: Minimum: 6.0” w.c.

L.P. Gas:

Minimum: 10.0” w.c.

Maximum: 10.5” w.c.

 

Maximum: 13.5” w.c.

BEFORE PLACING THE WATER HEATER IN OPERATION, CHECK FOR GAS LEAKAGE. USE SOAP AND WATER SOLUTION OR OTHER MATERIAL ACCEPTABLE FOR THE PURPOSE OF LOCATING GAS LEAKS.

WARNING

DO NOT use matches, candles, flame or other sources of ignition for this purpose.

Capacity Table for Natural Gas in Cubic Feet/Hour

(Table assumes 0.3 inch pressure drop, specific gravity of 0.60 for gas pressures of 0.5 psi or less)

Pipe

 

 

 

 

Length of Pipe in Feet (Meters)

 

 

 

 

 

Size in

10

20

30

40

50

60

70

80

90

 

100

125

150

175

200

Inches

(3)

(6)

(9)

(12)

(15)

(18)

(21)

(24)

(27)

 

(30)

(38)

(45)

(53)

(61)

¾”

278

190

152

130

115

105

96

90

84

 

79

72

64

59

55

1”

520

350

285

245

215

195

180

170

160

 

150

130

120

110

100

1 ¼”

1050

730

590

500

440

400

370

350

320

 

305

275

250

225

210

1 ½”

1600

1100

890

760

670

610

560

530

490

 

460

410

380

350

320

Note: After determining the length of pipe required, select the pipe size that will supply the cubic feet per hour of gas required for the input rating of the gas appliances on the line.

The formula for figuring the cubic feet per hour required is:

CFH = Gas Input of Appliance on the Line (Btu/hr)

Heating Value of Gas (Btu/Cu. Ft.)

The heating value may be obtained from the local natural gas utility

Capacity Table for LP Gas in MBH of undiluted liquefied petroleum gases

(Table assumes 11 inches of water column pressure at the inlet, 0.5” press. drop)

Pipe

 

 

 

Length of Pipe in Feet (Meters)

 

 

 

 

Size in

10

20

30

40

50

60

70

80

90

100

125

150

Inches

(3)

(6)

(9)

(12)

(15)

(18)

(21)

(24)

(27)

(30)

(38)

(45)

½”

275

189

152

129

 

 

 

 

 

 

 

 

¾”

567

393

315

267

237

217

196

185

173

162

146

 

1”

1071

732

590

504

448

409

378

346

322

307

275

252

1 1/4”

2205

1496

1212

1039

913

834

771

724

677

630

567

511

INITIAL OPERATION AND TESTING (INSTALLER ONLY)

1.Open the gas and water supply valves to the water heater.

2.Check for water and gas leaks. Use soap solution to check for gas leaks.

3.To check inlet supply pressure, remove the 1/8” NPT plug on the gas inlet supply fitting just below the bottom casing and install a barb fitting for attaching a hose to a manometer. For checking the gas manifold pressure, the plug is located just below the gas manifold connection inside the control panel.

19

Image 19
Contents IGE-199R and IGE-199C Model Series Table of Contents Page Do not Operate the Appliance Until the Leakage is Corrected IGE-199R-10X Section II SpecificationsEVERHOT→ IGE Model Series Dimensions Section III General Information FeaturesDo not Operate the Appliance Until the Leakage is Corrected Section IV Installation InstructionsWater Heater Location UnpackingMount Water Heater on the Wall Build Opening Clearances FigReference Description Minimum Distance Inches cm Remove CartonInstructions for Connections Lime Condition Warning SignalSection V Water Connections Water QualityPage Recommended Piping for a Basic Installation Drain Solenoid Piping Fig Recommended Piping for Power Failure Freeze ProtectionRecommended Piping for a Circulation System Page Pressure Relief Valve Section VI GAS Connections Never USE a Match or Open Flame for TestingGAS Meter Size -NATURALGAS only Initial Operation and Testing Installer onlyGAS Pressure Regulation Page Section VII Electrical Connections Wiring Diagram Wiring Diagram Schematic Residential Models Remote Temperature ControlsEndless hot water system Commercial Models Initial Operation and Testing of Controls Installer only Control Wiring Connections Inside Water HeaterTo Fill the Water Heater Section Viii Operating InstructionsSequence of Operation Manual Gas Valve Fig To Turn OFF GAS to the ApplianceResidential Models see Figure Turning OFF the Water Heater for AN Extended Period of TimeControl For Residential Models Fig Control for Commercial Models Fig Commercial Models see FigureScalding Error Messages on Remote Temperature Control Display Approximate TIME/TEMPERATURE Relationships in ScaldsFirst AID for Scalds Burner Flame Appearance Fig Section IX MaintenancePage Lime Scale Flushing Diagram Fig Schematic Diagram of Internal Parts Section X Parts List Internal Components Internal Components Electrical Components Parts List Anti-Frost Heater Clip

IGE-199R Series, IGE-199C Series specifications

Bradford-White Corporation is a renowned manufacturer in the water heating industry, providing high-quality solutions for residential and commercial applications. Among its innovative line of products, the IGE-199R and IGE-199C Series stand out for their exceptional performance and efficiency in delivering hot water.

The IGE-199R and IGE-199C Series are powered by advanced technology designed to meet the demands of both modern homes and commercial settings. They feature advanced tankless water heating systems that offer continuous hot water on demand, eliminating the need for bulky storage tanks. This not only saves space but also enhances energy efficiency, as hot water is produced only when needed.

One of the key features of the IGE-199R and IGE-199C is their Energy Star certification, attesting to their high efficiency. These units utilize a powerful, high-efficiency condensing heat exchanger, which maximizes heat transfer while minimizing energy loss. The design facilitates a uniform and solid flow rate, ensuring that multiple outlets can be served simultaneously without compromising performance.

Both series also incorporate cutting-edge technology, such as modulating gas burners that adjust the heat output to match the hot water demand. This means that these units can efficiently operate at varying levels of energy consumption, ultimately resulting in lower utility bills for the consumer. Additionally, the units are equipped with an integrated control system that monitors system performance and provides digital diagnostics, making maintenance and troubleshooting straightforward.

Safety features are also paramount in the design of the IGE-199R and IGE-199C models. The units are outfitted with a range of safety sensors, including temperature and pressure relief valves, ensuring safe operation and preventing potential hazards. Furthermore, the innovative venting options allow for flexible installation, even in tight spaces, without compromising safety or efficiency.

The IGE-199R and IGE-199C Series are engineered to be user-friendly, offering a clear interface for easy operation and monitoring. Their robust construction ensures durability and reliability, making them an excellent choice for long-term investment in hot water solutions.

In summary, Bradford-White's IGE-199R and IGE-199C Series deliver exceptional quality and performance in tankless water heating. With their focus on energy efficiency, advanced technologies, and safety features, these units provide a reliable and effective solution for meeting the hot water needs of any household or commercial space.