Bradford-White Corp GX1-55S, GX2-25S manual Domestic HOT Water Priority

Page 26

1.Circulators – With space heating zones using circulators, the Single-wall Indirect should be added as an additional zone with a circulator.

2.Zone Valves – Select a valve with a low-pressure drop to assure adequate flow through the water heater.

3.Hybrid – The space heating zone can be zoned using zone valves and the Single-wall Indirect zoned with a circulator.

DOMESTIC HOT WATER PRIORITY

Two options are available, Priority and Non-Priority.

1.Priority – Demand for space heating is interrupted or postponed until the domestic hot water demand is satisfied. This option provides maximum delivery of domestic hot water. Priority is recommended when:

a)Boiler net output is 100,000 Btu per hour or less, or

b)When boiler output required to satisfy domestic hot water demand is at least 50% of the boiler output required to satisfy space heating demand, or

c)When an interruption in space heating can be tolerated during a long domestic hot water draw.

2.Non-PriorityBoiler output is divided between space heating and domestic hot water heating. Delivery of domestic hot water can be reduced during simultaneous space and domestic hot water heating operations, depending on such factors as boiler output, boiler over- sizing, number of space heating zones calling for heat, and the ratio of domestic hot water load to space heating load.

26

Image 26
Contents SINGLE-WALL Indirect Page Congratulations Section Important InformationPage If YOU Smell GAS Page Page Page Page Page Table of Contents Specifications ModelSW-2-80-L SW-80C-5 SW-2-120-L Model Gal LbsMinutes Sq Ft Compliance with the code Features General InformationPage Temperature and Pressure Relief Valve Page Page PRE-INSTALLATION UnpackingSystem Zone Control Page Domestic HOT Water Priority Component Location Appliance Location Water Connections Install Temperature and Pressure Relief Valve if not factory installedInstructions for Boiler Connections Connect Water Boiler Supply PipingWater Boiler Piping with Zone Valves Connect Steam Boiler Supply Piping Fill Boiler SystemElectrical Connections Page Aquastat Control Sequence of Operations Operating InstructionsSystem START-UP Water Temperature Adjustment Approximate TIME/TEMPERATURE Relationships in ScaldsPage Aquastat Control Page Maintenance To inspect or replace an anode Page Problem Cause Solution Trouble Shooting GuideProblem Cause Solution Parts List Part Name & Description