WATER TEMPERATURE ADJUSTMENT

1.The aquastat controls the maximum water temperature in the tank. The differential is a fixed 5°F with a 160°F maximum setting, set at the factory to 120°F.

WARNING

SCALDING

This water heater can deliver scalding temperature water at any faucet in the system. Be careful whenever using hot water to avoid scalding injury. By setting the aquastat on this water heater to obtain an increased water temperature, you may create the potential for scald injury. To protect against injury, you should install an ASSE approved mixing valve (a device to limit the temperature of water to protect against scald injury via mixing hot and cold water supply) in the water system. This valve will reduce point of discharge temperature in branch supply lines. Such valves are available from the manufacturer of this water heater or a local plumbing supplier. Please consult with a plumbing professional.

Table 7 details the approximate relationship of water temperature and time with regard to scald injury and may be used as a guide in determining the safest water temperature for your applications.

APPROXIMATE

TIME/TEMPERATURE

RELATIONSHIPS IN SCALDS

120°F More than 5 minutes

125°F 1 ½ to 2 minutes

130°F About 30 seconds

135°F About 10 seconds

140°F Less than 5 seconds

145°F Less than 3 seconds

150°F About 1 ½ seconds

155°F About 1 second

Table 7 – Scald Relationships

Figure 6 - Scald Warning

38

Image 38
Contents SINGLE-WALL Indirect Page Congratulations Section Important InformationPage If YOU Smell GAS Page Page Page Page Page Table of Contents Specifications ModelSW-2-80-L SW-80C-5 SW-2-120-L Model Gal LbsMinutes Sq Ft Compliance with the code Features General InformationPage Temperature and Pressure Relief Valve Page Page PRE-INSTALLATION UnpackingSystem Zone Control Page Domestic HOT Water Priority Component Location Appliance Location Water Connections Install Temperature and Pressure Relief Valve if not factory installedInstructions for Boiler Connections Connect Water Boiler Supply PipingWater Boiler Piping with Zone Valves Connect Steam Boiler Supply Piping Fill Boiler SystemElectrical Connections Page Aquastat Control Sequence of Operations Operating InstructionsSystem START-UP Water Temperature Adjustment Approximate TIME/TEMPERATURE Relationships in ScaldsPage Aquastat Control Page Maintenance To inspect or replace an anode Page Problem Cause Solution Trouble Shooting GuideProblem Cause Solution Parts List Part Name & Description