Bradford-White Corp MAGNUM Series Commercial Electric Booster Electrical All Sizes and Voltages

Page 13

INSTALLATION

Outlet

1. Using a 3/4″ union and piping, connect the booster water heater outlet to the commercial dish machine sanitizing rinse pipe connection.

NOTE: The red mark on the inlet and outlet water pipes of Magnum Series units must remain in the top most position.

NOTE: Make sure the connection is made to the final rinse and not to the wash tank.

2. Install a temperature/pressure gauge in the outlet line. The temperature sensing element must be in the water stream and the gauge must be mounted upright. Water temperature at the outlet should be 185°–190°F (85°–88°C).

Temperature/Pressure

Gauge

1/2″ Copper Female

1/2″ pipe thread

Fitting Adapter

 

CAUTION

DO NOT turn on power to the booster water heater until tank has been filled with water and all air has been vented through dish machine rinse nozzle. The heating elements will burn out in seconds if operated when they are not immersed in water.

Electrical — All Sizes and Voltages

General

Bradford White Electric Booster Water Heaters are available for operation on standard power systems. Check the identification decal for the proper power supply.

WARNING

ELECTRIC SHOCK HAZARD:

• Turn power OFF at disconnect switch/circuit breaker and allow unit to cool before performing any maintenance or cleaning.

• Consult a licensed electrical contractor for proper electrical installation conforming to local electrical codes and the National Electrical Code (N.E.C.).

3/4″ Nominal Copper Pipe

Temperature

Sensing

Element

NOTICE

Connect electric booster water heater to the same power

supply as indicated on the specification decal only. Units

connected to an incorrect power supply voids the product

warranty and will damage the equipment.

Figure 8. Recommended Temperature/Pressure Gauge Installation

All internal electrical connections have been made at the

factory. See the “Circuit Breaker and Fused Disconnect Switch

Sizes” charts in the SPECIFICATIONS section for supply wire

Temperature/ Pressure Gauge w/1/2″ pipe thread

Bottom of sensor centered in copper pipe.

3/4″ Nominal

Copper Pipe

3/4″ Copper Tee

1/2″ Copper

Female Fitting

Adapter

Temperature

Sensing

Element

size, fuse, breaker, and conduit recommendations. Consult local

codes for verification and compliance.

Electrical Connections

1.

Remove the front jacket cover screws. Ease the cover

 

forward and upward. The control box is under the front

2.

hinged jacket cover.

Locate the heater terminal or fuse block(s) inside the unit.

NOTE: See the “Circuit Breaker and Fused Disconnect Switch

3.

Sizes” charts for proper connections and wire size.

Bring power leads from a

 

properly sized disconnect

Figure 9. Alternate Temperature/Pressure Gauge Installation

NOTE: Bradford White recommends installing an

optional

 

shock absorber in the outlet line as close as possible

 

to the commercial dish machine solenoid rinse valve.

 

The shock absorber softens the water hammer caused

 

by automatic dish machine valves.

 

Plumbing Installation Inspection

 

1.

Close drain pipe shut-off valve and fill booster water heater

2.

with water.

 

Check all pipe connections for leaks.

 

3.

Make sure the temperature/pressurerelief valve discharge

4.

is not blocked.

 

Vent air from the booster tank before turning on the unit by

 

opening the temperature/pressure relief valve as well as

 

running the dish machine through several cycles.

 

Form No. EBOOSTERBWM-1009

11

switch

or

circuit

breaker

 

through the knockout provided

 

on the unit, and connect to the

 

terminal or fuse block(s).

USE

 

COPPER

WIRE

 

ONLY.

 

TIGHTEN

CONNECTIONS

 

PROPERLY TO A MINIMUM

 

OF 40 INCH POUNDS.

 

rigors

 

NOTE: Due

 

to

the

 

 

Knockout

of

transportation

 

all

Locations

connections

should

be

 

checked for tightness before booster water heater is put into operation.

4. A grounding lug is provided near the supply terminals. An equipment grounding conductor must be properly connected to it.

5. Replace and secure the front jacket cover.

Image 13
Contents Magnum Series Important Owner Information ContentsIntroduction Electric Shock Hazard Important Safety InformationImportant Safety Information Model Description SpecificationsMagnum Series Commercial Electric Booster Fuse Size Wire Size Model Volts Phase Amp DrawCopper Conduit Breaker orCapacity 40F 22C Rise 70F 39C Rise Shipping WeightNational Electrical Code N.E.C ModelGeneral InstallationMounting Brackets with Hardware Shock Absorber Legs Pressure Reducing ValveBlended Phosphate Water Treatment System Back Pressure Relief ValveTemperature/Pressure Gauges Temperature/Pressure Relief Valves Pressure Reducing ValveBlended Phosphate Water Treatment System optionalPlumbing Connections Temperature of 200F 93C. Materials used must meetInlet Consumer dish machines or other domestic utilizedPlumbing Connections Magnum Series 24-57 kW Outlet Electrical All Sizes and VoltagesGeneral Electrical ConnectionsStartup OperationShutdown Burn HazardTemperature/Pressure Relief Valve MaintenanceThermostat Adjustment Service by unqualified personnel may lead to electric Troubleshooting GuideOptional Symptom Probable Cause Corrective Action Make sure tank is full of water at all times Stainless Steel Adjustable Legs Floor Mounting Hardware AccessoriesShock Absorber SystemKW Wiring Diagram, All Voltages, Single- or Three-Phase Wiring Diagrams12 18 kW Wiring Diagram, All Voltages, Three-Phase KW Wiring Diagram, 208 and 240 V, Single-Phase 12 15 kW Wiring Diagram, 208 and 240 V, Single-Phase24 36 kW Wiring Diagram, 208 and 240 V, Three-Phase 24 30 kW Wiring Diagram, 240 V, Single-PhaseKW Wiring Diagram, 240 V, Single-Phase 24 36 kW Wiring Diagram, 480 V, Three-Phase45 57 kW Wiring Diagram, 480 V, Three-Phase 36 57 kW Wiring Diagram, 208 and 240 V, Three-PhaseWhat does this Limited Warranty COVER? Limited Commercial Water Heater WarrantyWhat is the Period of COVERAGE? What will WE not DO?What should YOU do to Keep the Warranty in EFFECT? Form No. EBOOSTERBWM-1009 Ambler, PA Technical Service Service Parts Warranty Service