INSTALLATION
Outlet
1. Using a 3/4″ union and piping, connect the booster water heater outlet to the commercial dish machine sanitizing rinse pipe connection.
NOTE: The red mark on the inlet and outlet water pipes of Magnum Series units must remain in the top most position.
NOTE: Make sure the connection is made to the final rinse and not to the wash tank.
2. Install a temperature/pressure gauge in the outlet line. The temperature sensing element must be in the water stream and the gauge must be mounted upright. Water temperature at the outlet should be
Temperature/Pressure
Gauge
1/2″ Copper Female | 1/2″ pipe thread |
Fitting Adapter |
|
CAUTION
DO NOT turn on power to the booster water heater until tank has been filled with water and all air has been vented through dish machine rinse nozzle. The heating elements will burn out in seconds if operated when they are not immersed in water.
Electrical — All Sizes and Voltages
General
Bradford White Electric Booster Water Heaters are available for operation on standard power systems. Check the identification decal for the proper power supply.
WARNING
ELECTRIC SHOCK HAZARD:
• Turn power OFF at disconnect switch/circuit breaker and allow unit to cool before performing any maintenance or cleaning.
• Consult a licensed electrical contractor for proper electrical installation conforming to local electrical codes and the National Electrical Code (N.E.C.).
3/4″ Nominal Copper Pipe
Temperature
Sensing
Element
NOTICE |
Connect electric booster water heater to the same power |
supply as indicated on the specification decal only. Units |
connected to an incorrect power supply voids the product |
warranty and will damage the equipment. |
Figure 8. Recommended Temperature/Pressure Gauge Installation
All internal electrical connections have been made at the |
factory. See the “Circuit Breaker and Fused Disconnect Switch |
Sizes” charts in the SPECIFICATIONS section for supply wire |
Temperature/ Pressure Gauge w/1/2″ pipe thread
Bottom of sensor centered in copper pipe.
3/4″ Nominal
Copper Pipe
3/4″ Copper Tee
1/2″ Copper
Female Fitting
Adapter
Temperature
Sensing
Element
size, fuse, breaker, and conduit recommendations. Consult local | |
codes for verification and compliance. | |
Electrical Connections | |
1. | Remove the front jacket cover screws. Ease the cover |
| forward and upward. The control box is under the front |
2. | hinged jacket cover. |
Locate the heater terminal or fuse block(s) inside the unit. | |
NOTE: See the “Circuit Breaker and Fused Disconnect Switch | |
3. | Sizes” charts for proper connections and wire size. |
Bring power leads from a | |
| properly sized disconnect |
Figure 9. Alternate Temperature/Pressure Gauge Installation
NOTE: Bradford White recommends installing an | optional | |
| shock absorber in the outlet line as close as possible | |
| to the commercial dish machine solenoid rinse valve. | |
| The shock absorber softens the water hammer caused | |
| by automatic dish machine valves. |
|
Plumbing Installation Inspection |
| |
1. | Close drain pipe | |
2. | with water. |
|
Check all pipe connections for leaks. |
| |
3. | Make sure the temperature/pressurerelief valve discharge | |
4. | is not blocked. |
|
Vent air from the booster tank before turning on the unit by | ||
| opening the temperature/pressure relief valve as well as | |
| running the dish machine through several cycles. |
|
Form No. | 11 |
switch | or | circuit | breaker |
| ||||
through the knockout provided |
| |||||||
on the unit, and connect to the |
| |||||||
terminal or fuse block(s). | USE |
| ||||||
COPPER | WIRE |
| ONLY. |
| ||||
TIGHTEN | CONNECTIONS |
| ||||||
PROPERLY TO A MINIMUM |
| |||||||
OF 40 INCH POUNDS. |
| rigors |
| |||||
NOTE: Due |
| to | the |
|
| Knockout | ||
of | transportation |
| all | Locations | ||||
connections | should | be |
|
checked for tightness before booster water heater is put into operation.
4. A grounding lug is provided near the supply terminals. An equipment grounding conductor must be properly connected to it.
5. Replace and secure the front jacket cover.