SPECIFICATIONS
Circuit Breaker and Fused Disconnect Switch Sizes — 36 to 57 kW
Model |
| kW |
| Volts |
| Phase |
| Amp Draw |
|
| Breaker or |
| Copper |
| Conduit | ||
|
|
|
|
|
|
|
| ||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
| Fuse Size |
| Wire Size |
| Size |
|
|
|
|
|
|
| L1 |
| L2 |
| L3 |
|
| ||||
LI6363CFC |
| 36 |
| 208 |
| 1 | 173 |
| 173 |
| - |
| 225 |
| 4/0 |
| |
LI6363CFD |
| 36 |
| 208 |
| 3 | 100 |
| 100 |
| 100 |
| 125 |
| 1 |
| |
LI6363CFE |
| 36 |
| 240 |
| 1 | 150 |
| 150 |
| - |
| 200 |
| 3/0 |
| |
LI6363CFF |
| 36 |
| 240 |
| 3 | 86.7 |
| 86.7 |
| 86.7 |
| 125 |
| 1 |
| |
LI6363CFM |
| 36 |
| 480 |
| 3 | 43.3 |
| 43.3 |
| 43.3 |
| 60 |
| 6 |
| 3/4" (19 mm) |
LI6453CFD |
| 45 |
| 208 |
| 3 | 125 |
| 125 |
| 125 |
| 175 |
| 2/0 |
| |
LI6453CFE |
| 45 |
| 240 |
| 1 | 188 |
| 188 |
| - |
| 250 |
| 250 kcmil |
| 2" (51 mm) |
LI6453CFF |
| 45 |
| 240 |
| 3 | 108 |
| 108 |
| 108 |
| 150 |
| 1/0 |
| |
LI6453CFM |
| 45 |
| 480 |
| 3 | 54 |
| 54 |
| 54 |
| 70 |
| 4 |
| 1" (25 mm) |
LI6543CFD |
| 54 |
| 208 |
| 3 | 150 |
| 150 |
| 150 |
| 200 |
| 3/0 |
| 2" (51 mm) |
LI6543CFF |
| 54 |
| 240 |
| 3 | 130 |
| 130 |
| 130 |
| 175 |
| 2/0 |
| |
LI6543CFM |
| 54 |
| 480 |
| 3 | 65 |
| 65 |
| 65 |
| 90 |
| 3 |
| 1" (25 mm) |
LI6573CFD |
| 57 |
| 208 |
| 3 | 158.4 |
| 158.4 |
| 158.4 |
| 200 |
| 3/0 |
| 2" (51 mm) |
LI6573CFF |
| 57 |
| 240 |
| 3 | 137.3 |
| 137.3 |
| 137.3 |
| 175 |
| 2/0 |
| |
LI6573CFM |
| 57 |
| 480 |
| 3 | 68.6 |
| 68.6 |
| 68.6 |
| 90 |
| 3 |
| 1" (25 mm) |
Wire size is based on |
| THHN wire |
| for branch circuit protection at .91 derate | factor. Circuit breakers and fused disconnects are to | ||||||||||||
be mounted remote and wired by contractor. Sizes are based on the 2002 NEC table | |||||||||||||||||
plus ground wire sizing per Table C1 from Appendix C. |
|
|
|
|
|
|
|
|
|
| |||||||
NOTE: 250 kcmil maximum wire size for terminal block. |
|
|
|
|
|
|
| ||||||||||
WARNING! Consult a licensed electrical contractor for proper electrical installation conforming to local electrical codes | |||||||||||||||||
and the National Electrical Code (N.E.C.). |
|
|
|
|
|
|
|
|
|
|
|
Capacity | kW | 40°F (22°C) Rise | 70°F (39°C) Rise | Shipping Weight |
Model | ||||
LI663XXX Models | 6 | 60 gph (227 lph) | 34 gph (129 lph) | 118 lbs. (54 kg) |
LI693XXX Models | 9 | 90 gph (341 lph) | 52 gph (197 lph) | 118 lbs. (54 kg) |
LI6123XXX Models | 12 | 120 gph (454 lph) | 69 gph (261 lph) | 120 lbs. (54 kg) |
LI6153XXX Models | 15 | 151 gph (572 lph) | 86 gph (326 lph) | 120 lbs. (54 kg) |
LI6183XXX Models | 18 | 181 gph (685 lph) | 103 gph (390 lph) | 120 lbs. (54 kg) |
LI6243XXX Models | 24 | 241 gph (912 lph) | 138 gph (522 lph) | 142 lbs. (64 kg) |
LI6303XXX Models | 30 | 301 gph (1139 lph) | 172 gph (651 lph) | 142 lbs. (64 kg) |
LI6363XXX Models | 36 | 361 gph (1367 lph) | 206 gph (780 lph) | 142 lbs. (64 kg) |
LI6453XXX Models | 45 | 452 gph (1711 lph) | 258 gph (977 lph) | 142 lbs. (64 kg) |
LI6543XXX Models | 54 | 542 gph (2052 lph) | 310 gph (1174 lph) | 142 lbs. (64 kg) |
LI6573XXX Models | 57 | 573 gph (2169 lph) | 326 gph (1234 lph) | 142 lbs. (64 kg) |
NOTE: Storage capacity is 6 gallons (23 liters).
Form No. | 5 |