Bradford-White Corp 07.05.228.00 manual Model Volts Phase Amp Draw, Copper Conduit, Breaker or

Page 6

SPECIFICATIONS

Circuit Breaker and Fused Disconnect Switch Sizes — 6 to 30 kW

Model

 

kW

 

Volts

 

Phase

 

Amp Draw

 

Breaker or

 

Copper

 

Conduit

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Fuse Size

 

Wire Size

 

Size

 

 

 

 

 

 

 

L1

 

L2

 

L3

 

 

LI663CFC

 

6

 

208

 

1

29

 

29

 

-

40

 

8

 

1/2" (13 mm)

LI663CFD

 

6

 

208

 

3

14

 

25

 

14

40

 

8

 

1/2" (13 mm)

LI663CFE

 

6

 

240

 

1

25

 

25

 

-

40

 

8

 

1/2" (13 mm)

LI663CFF

 

6

 

240

 

3

13

 

22

 

13

30

 

10

 

1/2" (13 mm)

LI663CFM

 

6

 

480

 

3

6

 

11

 

6

15

 

14

 

1/2" (13 mm)

LI693CFC

 

9

 

208

 

1

43

 

43

 

-

60

 

6

 

1/2" (13 mm)

LI693CFD

 

9

 

208

 

3

22

 

38

 

22

50

 

8

 

1/2" (13 mm)

LI693CFE

 

9

 

240

 

1

38

 

38

 

-

50

 

8

 

1/2" (13 mm)

LI693CFF

 

9

 

240

 

3

19

 

33

 

19

50

 

8

 

1/2" (13 mm)

LI693CFM

 

9

 

480

 

3

9

 

16

 

9

20

 

12

 

1/2" (13 mm)

LI6123CFC

 

12

 

208

 

1

58

 

58

 

-

90

 

3

 

1" (25 mm)

LI6123CFD

 

12

 

208

 

3

33

 

33

 

33

50

 

8

 

1/2" (13 mm)

LI6123CFE

 

12

 

240

 

1

50

 

50

 

-

70

 

6

 

1/2" (13 mm)

LI6123CFF

 

12

 

240

 

3

29

 

29

 

29

40

 

8

 

1/2" (13 mm)

LI6123CFM

 

12

 

480

 

3

14.5

 

14.5

 

14.5

20

 

12

 

1/2" (13 mm)

LI6153CFC

 

15

 

208

 

1

72

 

72

 

-

90

 

3

 

1" (25 mm)

LI6153CFD

 

15

 

208

 

3

41.7

 

41.7

 

41.7

60

 

6

 

3/4" (19 mm)

LI6153CFE

 

15

 

240

 

1

62.5

 

62.5

 

-

90

 

3

 

1" (25 mm)

LI6153CFF

 

15

 

240

 

3

36.1

 

36.1

 

36.1

50

 

8

 

1/2" (13 mm)

LI6153CFM

 

15

 

480

 

3

18.1

 

18.1

 

18.1

30

 

10

 

1/2" (13 mm)

LI6183CFC

 

18

 

208

 

1

86.5

 

86.5

 

-

125

 

1

 

1-1/4" (32 mm)

LI6183CFE

 

18

 

240

 

1

75

 

75

 

-

100

 

3

 

1" (25 mm)

LI6183CFF

 

18

 

240

 

3

43.4

 

43.4

 

43.4

60

 

6

 

3/4" (19 mm)

LI6183CFM

 

18

 

480

 

3

21.7

 

21.7

 

21.7

30

 

10

 

1/2" (13 mm)

LI6243CFC

 

24

 

208

 

1

115.4

 

115.4

 

-

150

 

1/0

 

1-1/4" (32 mm)

LI6243CFD

 

24

 

208

 

3

66.7

 

66.7

 

66.7

90

 

3

 

1" (25 mm)

LI6243CFE

 

24

 

240

 

1

100

 

100

 

-

125

 

1

 

1-1/4" (32 mm)

LI6243CFF

 

24

 

240

 

3

57.8

 

57.8

 

57.8

90

 

3

 

1-1/4" (32 mm)

LI6243CFM

 

24

 

480

 

3

29.9

 

29.9

 

29.9

40

 

8

 

1/2" (13 mm)

LI6303CFC

 

30

 

208

 

1

144

 

144

 

-

200

 

3/0

 

1-1/2" (38 mm)

LI6303CFD

 

30

 

208

 

3

83.3

 

83.3

 

83.3

125

 

1

 

1-1/4" (32 mm)

LI6303CFE

 

30

 

240

 

1

125

 

125

 

-

175

 

2/0

 

1-1/2" (38 mm)

LI6303CFF

 

30

 

240

 

3

72.3

 

72.3

 

72.3

100

 

3

 

1" (25 mm)

LI6303CFM

 

30

 

480

 

3

36

 

36

 

36

50

 

8

 

1/2" (13 mm)

Wire size is based on THHN wire for branch circuit protection at .91 derate factor. Circuit breakers and fused disconnects are to be mounted remote and wired by contractor. Sizes are based on the 2002 NEC table 310-16. Conduit size based on conductors plus ground wire sizing per Table C1 from Appendix C.

Only 6 and 9 kW models can be field converted to single- or three-phase (open delta on 3-phase). Check wiring diagram supplied with the unit when converting the phase of a unit. Larger branch circuit required than for balanced 3-phase of equal kW. Balanced 3-phase available, consult factory.

NOTE: 250 kcmil maximum wire size for terminal block.

WARNING! Consult a licensed electrical contractor for proper electrical installation conforming to local electrical codes and the National Electrical Code (N.E.C.).

4

Form No. EBOOSTERBWM-1009

Image 6
Contents Magnum Series Contents Important Owner InformationIntroduction Important Safety Information Electric Shock HazardImportant Safety Information Specifications Model DescriptionMagnum Series Commercial Electric Booster Copper Conduit Model Volts Phase Amp DrawFuse Size Wire Size Breaker orNational Electrical Code N.E.C 40F 22C Rise 70F 39C Rise Shipping WeightCapacity ModelInstallation GeneralBlended Phosphate Water Treatment System Legs Pressure Reducing ValveMounting Brackets with Hardware Shock Absorber Back Pressure Relief ValveBlended Phosphate Water Treatment Temperature/Pressure Relief Valves Pressure Reducing ValveTemperature/Pressure Gauges System optionalInlet Temperature of 200F 93C. Materials used must meetPlumbing Connections Consumer dish machines or other domestic utilizedPlumbing Connections Magnum Series 24-57 kW General Electrical All Sizes and VoltagesOutlet Electrical ConnectionsShutdown OperationStartup Burn HazardMaintenance Temperature/Pressure Relief ValveThermostat Adjustment Troubleshooting Guide Service by unqualified personnel may lead to electricOptional Symptom Probable Cause Corrective Action Make sure tank is full of water at all times Shock Absorber AccessoriesStainless Steel Adjustable Legs Floor Mounting Hardware SystemWiring Diagrams KW Wiring Diagram, All Voltages, Single- or Three-Phase12 18 kW Wiring Diagram, All Voltages, Three-Phase 12 15 kW Wiring Diagram, 208 and 240 V, Single-Phase KW Wiring Diagram, 208 and 240 V, Single-Phase24 30 kW Wiring Diagram, 240 V, Single-Phase 24 36 kW Wiring Diagram, 208 and 240 V, Three-Phase24 36 kW Wiring Diagram, 480 V, Three-Phase KW Wiring Diagram, 240 V, Single-Phase36 57 kW Wiring Diagram, 208 and 240 V, Three-Phase 45 57 kW Wiring Diagram, 480 V, Three-PhaseWhat is the Period of COVERAGE? Limited Commercial Water Heater WarrantyWhat does this Limited Warranty COVER? What will WE not DO?What should YOU do to Keep the Warranty in EFFECT? Form No. EBOOSTERBWM-1009 Ambler, PA Technical Service Service Parts Warranty Service