American Water Heater ADCG, DCG3-Series, 71681 warranty Air Opening Requirements

Page 8

Index

Air Opening Requirements

(a)EQUIPMENT LOCATED IN CONFINED SPACES; ALL AIR FROM INSIDE THE BUILDING.

Two permanent openings (top and bottom) shall be provided connecting the confined space (e.g., closet/small room) with the unconfined space. Each opening shall have a free area of one square inch per 1,000 BTU/hour (22 cm²/kW) input of all appliances in the confined space, but not less than 100 square inches (645 cm²).

b)BASEMENT INSTALLATION, EQUIPMENT LOCATED IN CON- FINED SPACES; ALL AIR FROM OUTDOORS.

Outside air inlets shall be a minimum of 12” (300mm) above the grade (snow) line. When supplying air directly from the outdoors:

For American installations: Two openings (top and bottom) shall be provided with each opening having a minimum free area of one square inch per 4,000 BTU/hour input (5.5 cm²/kW) of total input rating of all appliances in the confined space.

For Canadian installations: Canadian codes specify single air supply source. Canadian customers and authorities having jurisdiction may use the sizing listed in Table 1. When using a single air supply, the duct shall terminate within 1 foot (300 mm) above and within 2 feet (600 mm) hori- zontally from the burner level of the appliance having the largest input.

Table 1

Combined input of all

Required

Acceptable Equivalent duct

appliances in

free area of

diameter

confined space

duct

A1

B2

BTU/hr(kW)

in2(mm2)

in(mm)

in(mm)

75,000(23)

11(7,000)

4(100)

5(125)

100,000(30)

14(9,000)

4(100)

5(125)

125,000(37)

18(12,000)

5(125)

6(150)

150,000(45)

22(14,000)

5(125)

6(150)

175,000(53)

25(16,000)

6(150)

7(175)

200,000(60)

29(19,000)

6(150)

7(175)

225,000(68)

32(21,000)

6(150)

7(175)

250,000(75)

36(23,000)

7(175)

8(200)

275,000(83)

40(26,000)

7(175)

8(200)

300,000(90)

43(28,000)

7(175)

8(200)

325,000(98)

47(30,000)

8(200)

9(225)

350,000(105)

50(32,000)

8(200)

9(225)

375,000(113)

54(35,000)

8(200)

9(225)

400,000(120)

58(37,000)

9(225)

10(250)

Notes:

1.Maximum lenght of ducts in column A is 20 equivalent feet(6.1 meters). 2.Maximum lenght of ducts in column B is 50 equivalent feet(15.2 meters).

(c)EQUIPMENT LOCATED IN CONFINED SPACES; ALL AIR FROM OUTDOORS.

For American installations: When supplying air directly from the out- doors using horizontal ducting, each opening shall have a free minimum area of one square inch per 2,000 BTU/hour (11 cm²/kW) of total input rating of all appliances in the confined space.

For Canadian installations: Refer to Table 1 of part (b).

(d)EQUIPMENT LOCATED IN CONFINED SPACES; ALL AIR FROM OUTDOORS THROUGH VENTILATED ATTIC.

For American installations: When supplying air directly through vertical ducting, each opening shall have a free minimum area of one square inch per 4,000 BTU/hour (5.5 cm²/kW) of total input rating of all appli- ances in the confined space.

8

Figure: 2 Equipment Location

and Combustion/Ventilation Air

Requirements

(a)

Permanent

 

 

 

 

 

 

 

 

Ventilation

 

 

 

 

 

 

12” Grade

Air

 

 

 

 

 

 

Combustion

Air Duct

12”

(b)

Venting

Outdoor

Air Ducts

Combustion

(c)

Outlet Air

Inlet

Air Ducts

(d)

*U.S. installations require a dual duct system.

Image 8
Contents Installation Instructions Use & Care Guide Table of Contents Installation Instructions Installer and Owner ResponsibilitiesConsumer Information Unpacking the Water HeaterInstallation Requirements Site LocationPan must not restrict combustion airflow. Locate Clearances and AccessibilityFloors of the structure. Due to the normal corrosive Venting COMBUSTION/VENT Pipe SystemCombustion Air Requirements GeneralCombustion Air Supply Ducts Louvers and GrillsAir Opening Requirements Equipment Located in Confined Spaces ALL AIR from OutdoorsDraft Hood/Damper Installation Flue Outlet ReducerPiping Installation Tempering Valve InstallationWater System Piping Space HeatingRelief valve if required Please note the following Temperature & Pressure Relief Valve Discharge LineGAS Supply and Piping Gas RequirementsGas Piping Gas PressureGas Pressure Testing Electrical Installation Electrical ConnectionsWiring Diagram Installation Checklist Water Heater Location RequirementsVent Pipe System Vent TerminationWater Heater Operation Operating Your Water HeaterPropane Models Water Temperature Regulation StackingEmergency Shut Down Checking the DraftBurner Flames Operational ConditionsMaintenance of Your Water Heater Draining and FlushingPilot Burner and Main Burner Assembly Inspection Power Clean flameFaulty Check continuityThermostat Troubleshooting Flow Chart Sensor Resistance vs. Temperature Resistance K ohmsRepair Parts Illustration Part Name and Description