American Water Heater ADCG, DCG3-Series Temperature & Pressure Relief Valve, Discharge Line

Page 13

Index

Temperature and Pressure

 

must not exceed the working pressure of the water

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Relief Valve

 

heater as stated on the data plate.

 

Important: Only a new temperature and pressure relief

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

valve should be used with this water heater. Do not use

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

an old or existing valve as it may be damaged or not

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

adequate for the working pressure of the new water

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

heater. Do not place any valve or piping between the

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

relief valve and the tank.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

The Temperature & Pressure Relief Valve:

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

• Must not be in contact with any electrical part.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

• Must be connected to an adequate discharge

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

line.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

• Must not be rated higher than the working

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

pressure shown on the data plate of the water

 

 

 

 

 

 

 

 

 

 

Explosion Hazard

 

 

 

 

 

 

 

 

 

 

 

 

 

 

heater.

 

 

If the temperature and pressure relief

 

 

 

 

 

 

• The BTUH rating of the T & P valve must be

 

 

valve is dripping or leaking, have a

 

 

greater than, or equal to, the input rating of the

 

 

qualified service technician replace it.

 

 

water heater.

 

 

• Do not plug valve.

 

 

The Discharge Line:

 

 

• Do not remove valve.

 

 

• Must not be smaller than the pipe size of the

 

 

 

 

relief valve or have any reducing coupling

 

 

Failure to follow these instructions can

 

 

 

 

 

 

installed in the discharge line.

 

 

result in death or explosion.

 

 

• Must not be capped, blocked, plugged or

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

contain any valve between the relief valve and

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

the end of the discharge line.

 

 

Figure 9: T&P Relief Valve

 

 

 

• Must terminate a maximum of 6 inches (152mm)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

above a floor drain or external to the building.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

• Must be capable of withstanding 250°F (121°C)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

without distortion.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

• Must be installed to allow complete drainage of

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

both the valve and discharge line.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Index

For protection against excessive pressures and temperatures, a temperature and pressure relief valve must be installed in the opening marked “T & P RELIEF VALVE” (See Figure 9). This valve must be design certified by a nationally recognized testing laboratory that maintains periodic inspection of the production of listed equipment or materials as meeting the requirements for Relief Valves and Automatic Shut-off Devices for Hot Water Supply Systems, ANSI Z21.22. (CSA4.4, Temperature, Pressure, Temperature and Pressure Relief Valves and Vacuum Relief Valves in Canada). The function of the temperature and pressure relief valve is to discharge water in large quantities in the event of excessive temperature or pressure devel- oping in the water heater. The valve's relief pressure

13

13

Image 13
Contents Installation Instructions Use & Care Guide Table of Contents Installer and Owner Responsibilities Installation InstructionsConsumer Information Unpacking the Water HeaterSite Location Installation RequirementsFloors of the structure. Due to the normal corrosive Clearances and AccessibilityPan must not restrict combustion airflow. Locate Combustion COMBUSTION/VENT Pipe SystemVenting General Air RequirementsCombustion Air Supply Ducts Louvers and GrillsEquipment Located in Confined Spaces ALL AIR from Outdoors Air Opening RequirementsFlue Outlet Reducer Draft Hood/Damper InstallationTempering Valve Installation Piping InstallationWater System Piping Space HeatingRelief valve if required Please note the following Discharge Line Temperature & Pressure Relief ValveGas Requirements GAS Supply and PipingGas Piping Gas PressureGas Pressure Testing Electrical Connections Electrical InstallationWiring Diagram Water Heater Location Requirements Installation ChecklistVent Pipe System Vent TerminationPropane Models Operating Your Water HeaterWater Heater Operation Stacking Water Temperature RegulationChecking the Draft Emergency Shut DownBurner Flames Operational ConditionsDraining and Flushing Maintenance of Your Water HeaterPilot Burner and Main Burner Assembly Inspection Clean flame PowerFaulty Check continuitySensor Resistance vs. Temperature Resistance K ohms Thermostat Troubleshooting Flow ChartPart Name and Description Repair Parts Illustration