American Water Heater 6510319 Air Shutter adjustment for Flame Guard L.P.-30T only

Page 25

Air Shutter adjustment for Flame Guard® (L.P.-30T only)

Important: On initial startup, condensation is normal. If unit is condensating, wait until it has stopped condensating before inspecting burner flames for proper operation. With the water heater on and the burner lit, inspect the burner flames through the viewport and compare them to the drawings in figure

18.A properly operating burner should produce a soft blue flame. Blue tips with yellow inner cones are satisfactory. The tips of the flame may have a slight yellow tint. The flame should not be all yellow or have a sharp blue-orange color. If the flames are not satisfactory then it may be necessary to adjust the air shutter. If you lack the necessary skills to perform the adjustment properly you should not proceed, but get help from a qualified service technician.

1.Remove the manifold assembly using the instructions on page 21.

2.Remove the two screws securing the burner to the manifold assembly, then separate the burner from the manifold assembly (see figure 29).

3.While holding the burner, loosen the air shutter set screw, and rotate the air shutter to adjust air flow to burner (See figure 30). Rotating the shutter to allow more air to the burner sharpens the flame, while restricting the airflow softens the flame. Once adjusted, tighten the set screw.

4.Using the instructions on page 23 replace the manifold door assembly.

5.Verify proper operation of the water heater. If further adjustments are needed repeat process beginning with step #1 above.

Figure 29

Manifold /Burner Assembly

in Combustion Chamber

Figure 30

Air Shutter Adjustment

25

Image 25
Contents Installation Instructions Use & Care Guide Table Of Contents Consumer Responsibilities Consumer InformationUnpacking the Water Heater Site Location Location RequirementsClearances and Accessibility Gas Supply Gas Pressure TestingGas Requirements Gas PressureNatural Gas Pipe Capacity Table Cu. Ft./Hr Combustion Air Supply and VentilationConfined Space Unconfined SpaceAll Air from Inside the Building Louvers and Grilles All Air from OutdoorsVent Connectors Drafthood InstallationVent Pipe System Vent Pipe SizeVertical Exhaust Gas Vent Chimney ConnectionWater System Piping Piping InstallationClosed System/Thermal Expansion Temperature & Pressure Relief Valve Temperature and Pressure Relief ValveSpecial Applications Solar InstallationCombination Space Heating/Potable Water System Installation Checklist G. Bottled Propane Models Lighting InstructionsChecking the Draft Water Temperature RegulationBurn Hazard Do not touch vent Doing so can result in burns Operational Conditions Temperature and Pressure Relief Valve Routine Preventative MaintenanceDraining and Flushing Removing the Manifold Assembly Replacement PartsRemoving the Burner from the Manifold Assembly Natural Gas Burner Low NoxReplacing the Thermocouple External Inspection & Cleaning of the Flame-trapReplacing the Manifold Assembly Cleaning the Combustion Chamber and Flame-trapPiezoelectric Igniter System Testing the Igniter SystemRemoving and Replacing the Gas Control Valve/Thermostat Air Shutter adjustment for Flame Guard L.P.-30T only Flame Guard Safety System Operational Checklist Troubleshooting ChartProblem Possible Causes Corrective Action Troubleshooting ChartRepair Parts List Repair Parts IllustrationListed Parts Kits and Illustrations