A.O. Smith BTH 120 - 250 warranty Display Flashes 05 when button is pressed

Page 17

Display Flashes “05” when button is pressed:

 

 

 

 

 

 

 

Possible Cause

Remedy

 

 

 

 

 

 

 

1.

Temperature Probe wiring

1. Repair Wiring

 

 

 

open

 

 

 

2.

Defective probe

2. Replace probe

 

 

 

 

 

 

 

 

 

 

 

Display Flashes “15” when button is pressed:

 

 

 

 

 

 

Possible Cause

Remedy

 

 

 

 

 

 

 

1.

No water in tank and tank

1. The symptom does not

 

 

 

in freezing conditions

reflect a control problem

 

 

2.

Water in tank above freezing

2. Temperature probe out of

 

 

 

 

tolerance, replace temp.

 

 

 

 

probe

 

 

 

 

 

 

 

 

 

 

 

Display Flashes “25” when button is pressed:

 

 

 

 

 

 

 

Possible Cause

Remedy

 

 

 

 

 

 

 

1.

Water in tank is low, probe

1. Fill tank

 

 

 

immersed in steam

 

 

 

2.

Probe wiring shorted

2. Repair wiring

 

 

3.

Defective probe

3. Replace probe

 

 

 

 

 

 

 

 

 

 

 

ECO SWITCH OPEN (Figure 22)

ECO LED Flashing:

ECO SWITCH OPEN, ECO LED Flashing

FIGURE 22

 

 

 

 

 

Possible Cause

Remedy

 

 

 

 

 

 

1. This indicates the control has

1. Press button on the

 

 

failed on of its internal

display board to reset

 

 

diagnostic self-tests.

control. If this error

 

 

 

occurs repeatedly,

 

 

 

replace control.

 

 

 

 

 

 

 

 

 

CONTROL BAD (Figure 23)

 

 

All LEDs Flashing:

 

 

CONTROL BAD, All LEDs Flashing

FIGURE 23

 

Possible Cause

Remedy

 

 

 

1.

Temp. Probe unplugged

1. Check connectors

2.

Temp. probe wiring damaged

2. Repair wiring

3.

Water in tank too hot

3. Normal condition when

water t e m p e r a t u r e exceeds safety limit. Allow water to cool or admit water into tank and manually reset the control. Determine cause for overtemp condition.

COMBUSTION AIR BLOCKAGE (Figure 24)

Pressure Switch LED Flashing:

COMBUSTION AIR BLOCKAGE, Pressure Switch LED Flashing

FIGURE 24

Possible Cause

 

Remedy

 

 

 

 

1.

Combustion air blocked

1.

Check exhaust piping and

 

 

 

flue for obstructions

2.

Blower not operating:

2.

a. Repair wiring

 

a. Check blower wiring

 

b. Replace blower motor

 

b. Check blower motor

 

 

3.

Defective air switch

3.

Replace air switch

4.

Pressure switch jumped out

4.

This controller must sense

 

 

 

an open contact on the

 

 

 

blower proving airflow

switch before the blower comes on. Check to see if blower proving airflow switch is still connected to the unit.

17

Image 17 Contents
Notify Owner to Keep for Future Reference Place These Instructions Adjacent to HeaterBTU ROUGH-IN -DIMENSIONS Cyclone XHE BTH 120Foreword Table of ContentsHigh Limit Switch E.C.O FeaturesWater Temperature Control Insulation Blankets Installation InstructionsDishwashing Machine Requirement Circulating PumpHard Water ClearancesAIR Requirements Mechanical Exhausting of Room AIRPage PVC Elbow with Mesh Screen Direct Vent Terminal InstallationDirect Venting Vent Pipe Manufacturers Installation Instructions Installation SequenceMasonry Side Walls Wooden Side WallsInstallation of Vent System Vertical Vent Terminal InstallationVent Pipe Preparation Controls and SwitchesBlower Prover Switch GAS Piping System Connections BSR Board BTH 250 only Figure Water Line Connections Heater WiringClosed System Operation Self Diagnostic ControllerSequence of Operation GAS Valve LED FlashingFault Conditions Error CodesDisplay Flashes 05 when button is pressed Required Ability Initial START-UP Prior to Start UP Adjustment ProcedureOperating Instructions For Your Safety Read Before Operating General Information MaintenanceFlushing Anode Inspection and ReplacementDraining Sediment RemovalVent System Drain Valve and Access PanelsInstallation Diagrams Install in Accordance with Local Codes Page Page Page Manifold Kits TROUBLE-SHOOTING Checklist and Service InformationMotor will not RUN Replacement PartsMotor RUNS, Burner Lights Momentarily Then Locks OUT Noisy Burner OperationClaim Procedure Service and Repair ExpensesTank ALL Other PartsSmith Water Products CO., INC