A.O. Smith BTH 120 - 250 warranty Direct Venting, Direct Vent Terminal Installation

Page 8

IMPORTANT

The vent system must terminate so that proper clearances are maintained as cited in local codes or the latest edition of the National Fuel Gas Code, ANSI Z223.1,7.3.4e and 7.8a,b, as follows:

1.Do not terminate the exhaust vent terminal over public area where condensate or vapor can cause nuisance or hazard.

2.For direct vent, the venting system shall terminate at least 1 foot below, 1 foot horizontally from or 1 foot above any door, window, or gravity air inlet into building.

3.For horizontal the venting system shall terminate 4 foot below, 4 foot horizontally from or 1 foot above any door, window, or gravity air inlet into building.

4.The manufacturer also recommends the vent system terminations not be installed closer than 3 feet from an inside corner of an L shaped structure. And not less than 1 foot above grade or anticipated snow level.

5.The vent termination shall not be mounted directly above or within 3 feet horizontally from an oil tank vent or gas meter to avoid potential freeze- up from condensation.

6.The vent shall terminate a minimum of 12" above expected snowfall level to prevent blockage of vent termination.

Plan the vent system layout so that proper clearances are maintained from plumbing and wiring.

Vent pipes serving power vented appliances are classified by building codes as "vent connectors". Required clearances from combustible materials must be provided in accordance with information in this manual under LOCATION OF HEATER and CLEARANCES, and with National Fuel Gas Code and local Codes.

IMPORTANT

Plan the layout of the vent system backwards from the vent termination to the appliance.

WARNING

USEONLYTHEVENTTERMINALSSUPPLIEDWITHTHISUNIT.TERMINATION OF A VENT SYSTEM WITH A DEVICE OTHER THAN THE SUPPLIED VENT TERMINATIONS WILL AFFECT SYSTEM PERFORMANCE AND RESULT IN A SAFETY HAZARD.

DIRECT VENTING

The air intake provided on the unit contains a mesh screen (see Figure 7) to prevent large particles from entering the unit.

3" 45° PVC ELBOW WITH MESH SCREEN

FIGURE 7

WARNING

WHEN THE UNIT IS TO BE SETUP AS A DIRECT VENT, THE MESH SCREEN MUST BE REMOVED. THE INLET VENT PIPE MAY THEN BE GLUED TO THE AIR INTAKE (see Figure 8) PROVIDED ON THE UNIT.

FIGURE 8

DIRECT VENT TERMINAL INSTALLATION

IMPORTANT

THIS UNIT CONSISTS OF TWO VENT TERMINALS - AN INTAKE VENT TERMINAL AND AN EXHAUST VENT TERMINAL. THE INTAKE VENT TERMINAL IS A 3" 45°PVC ELBOW (OR 3" PVC TEE FOR BTH 250) WITH A MESH WIRE SCREEN AND THE EXHAUST VENT TERMINAL IS A 3" 45°PVC ELBOW WITH A MESH WIRE SCREEN.

BTH 120

BTH 150

& 199

BTH 250

FIGURE 9

8

Image 8 Contents
Place These Instructions Adjacent to Heater Notify Owner to Keep for Future ReferenceROUGH-IN -DIMENSIONS Cyclone XHE BTH 120 BTUTable of Contents ForewordHigh Limit Switch E.C.O FeaturesWater Temperature Control Installation Instructions Insulation BlanketsDishwashing Machine Requirement Circulating PumpClearances Hard WaterAIR Requirements Mechanical Exhausting of Room AIRPage PVC Elbow with Mesh Screen Direct Vent Terminal InstallationDirect Venting Installation Sequence Vent Pipe Manufacturers Installation InstructionsMasonry Side Walls Wooden Side WallsVertical Vent Terminal Installation Installation of Vent SystemVent Pipe Preparation Controls and SwitchesBlower Prover Switch GAS Piping System Connections BSR Board BTH 250 only Figure Water Line Connections Heater WiringClosed System Self Diagnostic Controller OperationSequence of Operation GAS Valve LED FlashingError Codes Fault ConditionsDisplay Flashes 05 when button is pressed Required Ability Initial START-UP Prior to Start UP Adjustment ProcedureOperating Instructions For Your Safety Read Before Operating Maintenance General InformationAnode Inspection and Replacement FlushingDraining Sediment RemovalDrain Valve and Access Panels Vent SystemInstallation Diagrams Install in Accordance with Local Codes Page Page Page Manifold Kits Checklist and Service Information TROUBLE-SHOOTINGReplacement Parts Motor will not RUNMotor RUNS, Burner Lights Momentarily Then Locks OUT Noisy Burner OperationService and Repair Expenses Claim ProcedureTank ALL Other PartsSmith Water Products CO., INC