A.O. Smith BTH 120 - 250 warranty Installation Instructions, Insulation Blankets, Circulating Pump

Page 5

DISHWASHING MACHINE REQUIREMENT

All dishwashing machines meeting the National Sanitation Foundation requirements are designed to operate with water flow pressures between 15 and 25 pounds per square inch. Flow pressures above 25 pounds per square inch, or below 15 pounds per square inch, will result in improperly sanitized dishes. Where pressures are high, a water pressure reducing or flow regulating control valve should be used in the 180°F line to the dishwashing machine, and should be adjusted to deliver water between these limits.

The National Sanitation Foundation also recommends circulation of 180°F water. Where this is done, the circulation should be very gentle so that it does not cause any unnecessary turbulence inside the water heater. The circulation should be just enough to provide 180°F water at the point of take-off to the dishwashing machine. Adjust flow by means of the plug cock in the circulating line. (See installation diagrams.)

CIRCULATING PUMP

A circulating pump is used when a system requires a circulating loop or there is a storage tank used in conjunction with the heater. Refer to the piping diagrams at rear of manual for electrical hookup information and install in accordance with the latest version of the National Electric Code ANSI/NFPA No. 70.

Only all bronze circulators are used with commercial water heaters.

Although circulators are oiled and operated by the manufacturer some circulators must be oiled again before operated. Please refer to manufacturer's instructions.

INSTALLATION INSTRUCTIONS

REQUIRED ABILITY

INSTALLATION OR SERVICE OF THIS WATER HEATER REQUIRES ABILITY EQUIVALENT TO THAT OF A LICENSED TRADESMAN IN THE FIELD INVOLVED. PLUMBING, AIR SUPPLY, VENTING, GAS SUPPLY AND ELECTRICAL WORK ARE REQUIRED.

INSULATION BLANKETS

Insulation blankets available to the general public for external use on gas water heaters are not approved for use on your A.O. Smith water heater. The purpose of an insulation blanket is to reduce the standby heat loss encountered with storage tank water heaters. Your A.O. Smith water heater meets or exceeds the ASHRAE/IES 90.1b 1992 standards with respect to insulation and standby loss requirements, making an insulation blanket unnecessary.

WARNING

Should you choose to apply an insulation blanket to this heater, you should follow these instructions. Failure to follow these instructions can result in fire, asphyxiation, serious personal injury or death.

Do not apply insulation to the top, or the upper 15" of the water heater, as this will interfere with safe operation.

Do not cover the temperature & pressure relief valve.

Do not cover the instruction manual. Keep it on the side of the water heater or nearby for future reference.

Do obtain new labels from A.O. Smith for placement on the blanket directly over the existing labels.

LOCATING THE HEATER

WARNING

THERE IS A RISK IN USING FUEL BURNING APPLIANCES SUCH AS GAS WATER HEATERS IN ROOMS, GARAGES OR OTHER AREAS WHERE GASOLINE,OTHERFLAMMABLELIQUIDSORENGINEDRIVENEQUIPMENT OR VEHICLES ARE STORED, OPERATED OR REPAIRED. FLAMMABLE VAPORS ARE HEAVY AND TRAVEL ALONG THE FLOOR AND MAY BE IGNITEDBYTHEHEATER’SIGNITERORMAINBURNERFLAMESCAUSING FIREOREXPLOSION.SOMELOCALCODESPERMITOPERATIONOFGAS APPLIANCES IF INSTALLED 18 INCHES OR MORE ABOVE THE FLOOR. THISMAYREDUCETHERISKIFLOCATIONINSUCHANAREACANNOTBE AVOIDED.

THEHEATERSHALLBELOCATEDORPROTECTEDSOITISNOTSUBJECT TO PHYSICAL DAMAGE BY A MOVING VEHICLE.

DO NOT LOCATE THE HEATER WHERE NOISE FROM THE EXHAUST OR INTAKEWILLBEOBJECTIONABLE.THISINCLUDESLOCATIONSCLOSETO OR ACROSS FROM WINDOWS AND DOORS. AVOID ANCHORING THE VENT AND INTAKE PIPES DIRECTLY TO FRAMED WALLS, FLOORS OF CEILINGS UNLESSRUBBER ISOLATION PIPE HANGERS ARE USED. THIS PREVENTSANYVIBRATIONSFROMBEINGTRANSMITTEDINTOTHELIVING SPACES.

WARNING

FLAMMABLE ITEMS, PRESSURIZED CONTAINERS OR ANY OTHER POTENTIAL FIRE HAZARDOUS ARTICLES MUST NEVER BE PLACED ON OR ADJACENT TO THE HEATER. OPEN CONTAINERS OF FLAMMABLE MATERIALSHOULDNOTBESTOREDORUSEDINTHESAMEROOMWITH THEHEATER.

When installing the heater, consideration must be given to proper location. Location selected should be as close to the intake and exhaust termination points as practicable, with adequate air supply and as centralized with the piping system as possible.

THE HEATER MUST NOT BE LOCATED IN AN AREA WHERE IT WILL BE SUBJECTTOFREEZING.

LOCATE IT NEAR A FLOOR DRAIN. THE HEATER SHOULD BE LOCATED IN AN AREA WHERE LEAKAGE FROM THE HEATER OR CONNECTIONS WILL NOTRESULTINDAMAGETOTHEADJACENTAREAORTOLOWERFLOORS OFTHESTRUCTURE.

When such locations cannot be avoided, it is recommended that a suitable drain pan, adequately drained, be installed under the appliance.

WARNING

THISWATERHEATERISACONDENSINGUNITANDREQUIRESADRAINTO BE LOCATED IN CLOSE PROXIMITY TO ALLOW THE CONDENSATE TO DRAIN SAFELY. THE CONDENSATE DRAINS FROM THE UNIT AT THE EXHAUST ELBOW LOCATED AT THE BOTTOM OF THE UNIT. NOTE: IT IS IMPORTANT THAT THE CONDENSATE HOSE NOT BE ELEVATED ABOVE THEEXHAUSTELBOW(SEEFIGURE3).THECONDENSATEBUILD-UPWILL BLOCK THE EXHAUST OUTLET, WHICH WILL CAUSE IMPROPER OPERATION.

FIGURE 3

5

Image 5
Contents Notify Owner to Keep for Future Reference Place These Instructions Adjacent to HeaterBTU ROUGH-IN -DIMENSIONS Cyclone XHE BTH 120Foreword Table of ContentsHigh Limit Switch E.C.O FeaturesWater Temperature Control Insulation Blankets Installation InstructionsDishwashing Machine Requirement Circulating PumpHard Water ClearancesAIR Requirements Mechanical Exhausting of Room AIRPage PVC Elbow with Mesh Screen Direct Vent Terminal InstallationDirect Venting Vent Pipe Manufacturers Installation Instructions Installation SequenceMasonry Side Walls Wooden Side WallsInstallation of Vent System Vertical Vent Terminal InstallationVent Pipe Preparation Controls and SwitchesBlower Prover Switch GAS Piping System Connections BSR Board BTH 250 only Figure Water Line Connections Heater WiringClosed System Operation Self Diagnostic ControllerSequence of Operation GAS Valve LED FlashingFault Conditions Error CodesDisplay Flashes 05 when button is pressed Required Ability Initial START-UP Prior to Start UP Adjustment ProcedureOperating Instructions For Your Safety Read Before Operating General Information MaintenanceFlushing Anode Inspection and ReplacementDraining Sediment RemovalVent System Drain Valve and Access PanelsInstallation Diagrams Install in Accordance with Local Codes Page Page Page Manifold Kits TROUBLE-SHOOTING Checklist and Service InformationMotor will not RUN Replacement PartsMotor RUNS, Burner Lights Momentarily Then Locks OUT Noisy Burner OperationClaim Procedure Service and Repair ExpensesTank ALL Other PartsSmith Water Products CO., INC

BTH 120 - 250 specifications

The A.O. Smith BTH 120 - 250 is a high-efficiency water heater designed for commercial and industrial applications, renowned for its advanced technology and durable construction. This model stands out for its ability to provide reliable hot water while minimizing energy consumption, making it an ideal choice for businesses looking to enhance operational efficiency.

One of the main features of the A.O. Smith BTH series is its innovative design that integrates cutting-edge condensing technology. This system maximizes energy use by capturing and reusing heat that would otherwise be lost in traditional water heating methods. As a result, the BTH 120 - 250 delivers exceptional thermal efficiency ratings, often exceeding 90%, thereby reducing overall operating costs.

The BTH series is available in various capacities, ranging from 120,000 to 250,000 BTU per hour, ensuring that it meets the diverse needs of different businesses. This flexibility allows for installation in a variety of settings, from small restaurants to large manufacturing facilities.

Another significant characteristic of the BTH 120 - 250 is its robust construction. Built with high-quality materials, this unit is designed to withstand the rigors of continuous use. Its stainless steel heat exchanger resists corrosion and scale build-up, providing longevity and reduced maintenance requirements.

Safety features are integrated into the BTH series as well. It includes an electronic ignition system that eliminates the need for a standing pilot light, enhancing operational safety and reducing energy waste. Additionally, the built-in diagnostic system allows for quick identification of issues, streamlining maintenance procedures.

The BTH series also emphasizes user-friendly operation. Equipped with advanced control options, operators can monitor and adjust performance settings effortlessly. The digital display provides real-time operational data, which can assist in optimizing performance and ensuring consistent hot water availability.

In summary, the A.O. Smith BTH 120 - 250 is an exceptional choice for commercial water heating, combining high efficiency, advanced technology, and robust durability. Its innovative design, safety features, and user-friendly controls position it as a trusted solution for businesses seeking reliable hot water systems. By investing in this model, operators can ensure optimal performance while enjoying significant energy savings over time.