Franklin 5870206300 installation manual Pump Sizing, Drive Configuration

Page 8

Pump Sizing

The SubDrive300 is configured at the factory for use with 3 Hp pumps that are mounted to 5 Hp Franklin Electric three-phase motors. In general, the

SubDrive300 will enhance the performance of a 3 Hp pump to a similar or better performance than a conventional 5 Hp pump of the same flowrating (pump series).

To select the proper 3 Hp pump, first choose a 5 Hp curve that meets the application’s head and flow requirements. Use the 3 Hp pump in the same pump series (flow rating). The SubDrive300 will adjust the speed of this pump to produce the performance of the 5 Hp curve. An example of this is illustrated in the graph at right.

Total Head (ft)

Typical SubDrive300 Performance

700 )Q(1.XJUI4VC%SJWF

$POWFOUJPOBM)Q(1.1VNQ $POWFOUJPOBM)Q(1.1VNQ

600

500

400

300

200

100

5

15

30

45

60

75

Flow GPM

Drive Configuration

The SubDrive300 can also be set up to run a 5 Hp pump if desired, but the larger pump will still produce to the 5 Hp curve and may only be operated with a 5 Hp motor. To operate a different pump size, a DIP switch must be positioned to select the correct pump rating. Otherwise, the SubDrive300 may trigger erroneous faults.

To configure the SubDrive300 for a 5 Hp pump, locate the DIP switch marked “SW1” at the lower right corner of the main circuit board. Use a small screwdriver (provided)

to change the DIP switch setting according to the chart as shown.

SW1

O N

Configuration Switch

1

Pump Size

OFF

3.0 Hp

ON

5.0 Hp

! WARNING

Serious or fatal electrical shock may result from contact with internal electrical components. DO NOT, under any circumstances, attempt to modify DIP switch settings until power has been removed and 5 minutes have passed for internal voltages to discharge!

8

Image 8
Contents SubDrive300 Contents SubDrive Models Description and Features Included Items YearsHow It Works Constant PressureMotor Soft Start System DiagnosticsUnique Features Pump Sizing Drive ConfigurationUnderload Sensitivity for Shallow Wells POS Underload SensitivityBefore Getting Started Controller Location Selection MinCorrectincorrect Circuit Breaker and Wire Sizing Quick Reference Guide SubDrive300 not to scale Pressure Tank Minimum Tank SizeInstallation Procedure Mounting ScrewsWiring Connections Motor Lead ConnectionsPower and Pressure Sensor Connections Pressure Sensor Pressure Shut-off Sensor Start-Up and Operation Leaky SystemsSpecifications For Use With CMounting Dimensions Diagnostic Fault Codes Flashes Fault Possible Cause Corrective ActionSystem Troubleshooting Guide Symptom Possible Cause Corrective ActionUnderload Smart Reset Over-Temperature FoldbackTOLL-FREE Help from a Friend 400 E. Spring Street Bluffton, Tel