Eaton Electrical Magnum Transfer Switch manual Transfer Switch Appears Inoperative

Page 30

Instructional Booklet

Page 30

Effective: March 2007

Fixed and Drawout Magnum Transfer Switches

If a problem persists after having completed the problem solving procedure, contact an Eaton representative for further assistance. When calling for assistance, the following is the MINIMUM infor- mation required to properly address the need:

1.Shop Order Number (SO #) or General Order Number (GO #) of the transfer switch, plus related Item Number;

2.Catalog and/or Style Number of the transfer switch;

3.Actual location of transfer switch (type of facility, address, etc.);

4.Company name;

5.Name and position of individual representing company;

6.Basic description of situation as it exists; and

7.Any results of problem solving steps taken and/or readings taken.

WARNING

THIS CLOSED TRANSITION PRODUCT CONTAINS A SPECIAL CON- TACT ARRANGEMENT (OVERLAPPING CONTACTS). MISUSE CAN RESULT IN DEATH, SEVERE PERSONAL INJURY, AND/OR PROPERTY DAMAGE.

8.2.1 Transfer Switch Appears Inoperative

Step 1: Verify that all plugs and sockets are properly intercon- nected.

Step 2: Verify that the correct system voltage appears at Source 1 switch. Measure the voltage at the breaker lugs.

Step 3: Verify that the voltage selection plug is in the proper posi- tion to match the system voltage.

Step 4: Look for any obviously burned components. Determine the cause and rectify, if possible. Replace any defective components after the cause is determined.

Step 5: For closed transition, refer to Figure 25 for manual oper- ating instructions. Verify whether or not the system volt- age now appears on the load terminals.

If YES: Check the logic for problems in the respective logic instruction book.

If NO: Check all power connections and the switching mechanism.

Step 5: For open transition, press the Push-To-Close button on the Source 1 switching device. Verify whether or not the system voltage now appears on the load terminals.

If YES: Check the logic for problems in the respective logic instruction book.

If NO: Check all power connections and the switching mechanism.

8.2.2Transfer Switch Will Not Automatically Transfer to Source 1

Step 1: Check for the proper line voltage on N1, N2, and N3.

Step 2: Is the Source 1 switching device charged? If YES: Continue with the other procedures.

If NO: Go through section 8.2.4 first before continuing.

Step 3: Is the Source 2 switch OPEN? If YES: Proceed to Step 5. If NO: Proceed to Step 4.

Step 4: Measure the voltage between terminals S2B1O and S2B11 on the Source 2 switching device (shunt trip). Does the voltage measure 120 Vac ±10 volts? Record the reading.

If YES: Check the shunt trip in the Source 2 switch.

If NO: Check the wiring to S2B10 and S2B11.

Step 5: Measure the voltage between terminals S1B12 and S1B13 on the Source 1 switching device (spring release coil). Does the voltage measure 120 Vac ± 10 volts? Record the reading.

If YES: Check the spring release coil in Source 1 switch- ing device.

If NO: Check the wiring to S1B12 and S1B13.

8.2.3Transfer Switch Will Not Automatically Transfer to Source 2

Step 1: Check for the proper line voltage on E1, E2, and E3.

Step 2: Is the Source 2 switching device charged? If YES: Continue with the other procedures.

If NO: Go through Section 8.2.4 first before continuing.

Step 3: Is the Source 1 switching device OPEN? If YES: Proceed to Step 5.

If NO: Proceed to Step 4.

Step 4: Measure the voltage between terminals S1B10 and S1B11 on the Source 1 switching device (shunt trip). Does the voltage measure 120 Vac ± 10 volts? Record the reading.

If YES: Check the shunt trip in the Source 1 switch.

If NO: Check the wiring to S1B10 and S1B11.

Step 5: Measure the voltage between terminals S2B12 and S2B13 on the Source 2 switching device (spring release coil). Does the voltage measure 120 Vac+ 10 volts? Record the reading.

If YES: Check the spring release coil in Source 2 switch.

If NO: Check the wiring to S2B12 and S2B13.

8.2.4 Transfer Switch Will Not Automatically Recharge Switches

Step 1: Measure the voltage between terminals B15 and B14 on the switching device that does not automatically recharge. Does the voltage read 120 Vac + 10 volts? Record the reading.

If YES: Check the electrical operator inside the switching device.

If NO: Verify the wiring to B15 and B14.

Step 2: If problem persists, contact Eaton.

For more information visit: www.Eaton.com

IB01602011E

Image 30 Contents
Manual for the Fixed and Drawout Magnum Transfer Switches Testing and Problem Solving Maintenance Renewal Parts GuideInstructional Booklet Preliminary Comments and Safety Precautions IntroductionGeneral Information Typical Load Transfer Switch Switching Device Type Schematic Design ConfigurationTypical Bypass Isolation Switch Schematic Withstand RatingsMagnum Fixed and Drawout Switching Devices Magnum Transfer Switch ConfigurationsGeneral Magnum Switching Device Fixed Switching Device for the Magnum Transfer Switch Transfer Switch Catalog Number Identification Using the Style Identification Guide Transfer Switch Catalog Number ExplanationReceiving, Handling, and Storage Equipment DescriptionPower Panel Switch Interlocks Open Transition OnlyDrawout Interlocks Left Side View with Panels Removed Voltage Selection Panel Logic PanelDrawout Mechanism Features NeutralsRelay Auxiliary Contacts Transfer Switch Equipment Enclosures EnclosureInstallation and Wiring StandardsMounting Location Unpackaging and Inspection Mounting Procedure Seismic Tested and Approved Product Mounting InstructionsPower Cable Connections Wire Size for Available Power Cable ConnectionsVoltage Selection Adjustment Mounting the Switching Device in the Drawout MechanismWiring OperationEngine Start Connection Automatic Transfer Switch Close Switch by Pushing Close ButtonDrawout and Fixed Switching Devices Installing a Drawout Switching DeviceSwitching Device Positioning Switching Device in the Connect Position Fixed Switching Device Levering and Position IndicationOperation of the Bypass Isolation Transfer Switch Switching Device OperationOperator Panel Source 1 to Source 1 Bypass Bypassing the Transfer Switch Automatic Operation Source 2 to Source 2 BypassInto Its Source 2 to Source 1 Bypass Open Transition Only Testing Testing and Problem SolvingManual Operation When in Bypass Mode Problem SolvingTransfer Switch Appears Inoperative Transfer Switch Will Not Automatically Transfer to SourceTransfer Switch Will Not Automatically Recharge Switches Maintenance Procedures MaintenancePeriodic Maintenance Procedures IntroductionCover Removal and Replacement Cover Removal and ReplacementRenewal Parts Guide Instructional Booklet Sensing Harness TSMGH02 Kcmil Neutral Terminal Instructional Booklet