Instructional Booklet
Fixed and Drawout Magnum Transfer Switches
Effective: March 2007 | Page 21 |
Figure 24. Close Switch by Pushing Close Button.
NOTICE
IF A TRANSFER SWITCH WITH ANY TYPE OF ELECTRICAL OPERAT- ING CAPABILITIES IS TO BE OPERATED MANUALLY UTILIZING THE MANUAL OPERATING HANDLE, IT IS STRONGLY RECOMMENDED THAT THE TRANSFER CONTROL CIRCUIT FIRST BE ISOLATED. THIS IS ACCOMPLISHED BY DISCONNECTING THE S7/P7 PLUG ON THE TRANSFORMER PANEL. AN AUTOMATIC ENGINE START WILL OCCUR UNLESS THE GENERATOR RUN SWITCH SET TO “OFF.” IF,
HOWEVER, A TRANSFER SWITCH IS SUPPLIED WITH A
5.2 Automatic Transfer Switch
The operating sequence of an ATS is dictated by the switch’s standard features and selected options. Operation of an ATS dur- ing Source 1 power source failure, Source 1 power source restora- tion, and testing is described in the associated Controller Instruction Booklet.
WARNING |
OVERLAPPING CONTACTS |
SOURCE 1 AND SOURCE 2 |
must be Synchronized |
7805C60H04 |
THIS PRODUCT CONTAINS A SPECIAL CON- TACT ARRANGEMENT (OVERLAPPING CON- TACTS). MISUSE CAN RESULT IN DEATH SEVERE PERSONAL INJURY OR PROPERTY DAMAGE.
(THIS LABEL IS APPLIED TO THE DOOR )
Do Not Use Without FOLLOW THE INSTRUCTIONS
Reading Manual
Operating Instructions OUTLINED IN THE NEXT
WARNING LABEL.
MANUAL CLOSE BUTTON (THIS LABEL IS APPLIED TO THE COVER OF THE MANUAL CLOSE BUTTON ON EACH
WARNING |
Attempting to close both switching devices simultaneously can cause severe injury
or death.
Follow Manual Operation Instructions Below
Manual Operation Instructions
1.Disconnect Logic Connectors
2.Open both switching devices
3.Verify "OPEN" flags
4.Verify source availability
5.Close switching device on available source
7805C60H05
THESE INSTRUCTIONS ONLY PERTAIN TO MANUALLY CLOSING A SINGLE SWITCHING DEVICE. ATTEMPTING TO CLOSE BOTH SWITCHING DEVICES CAN CAUSE SEVERE INJURY OR DEATH.
THIS LABEL IS APPLIED TO THE DOOR.
Figure 25. Switching Device Closing Precautions (Closed Transition Only).
IB01602011E | For more information visit: www.Eaton.com |