Instructional Booklet
Page 26 | Effective: March 2007 |
Fixed and Drawout Magnum Transfer Switches
Figure 36. Magnum Bypass Lights.
The right door control panel has the following standard features:
1.Light to indicate if the Source 1 switching device is isolated (only if the Source 1 switching device is racked out).
2.Light to indicate if the Source 2 switching device is isolated (only if the Source 2 switching device is racked out).
3.Light to indicate if the Source 1 bypass switching device is closed.
4.Light to indicate if the Source 2 bypass switching device is closed.
7.3 Bypassing the Transfer Switch
WARNING
THE CLOSED TRANSITION PRODUCT CONTAINS A SPECIAL CON- TACT ARRANGEMENT (OVERLAPPING CONTACTS). MISUSE CAN RESULT IN DEATH, SEVERE PERSONAL INJURY, AND/OR PROPERTY DAMAGE.
7.3.1 Source 1 to Source 1 BYPASS
The Source 1 switching device can be bypassed and isolated by the following sequence (Figures 36 and 37):
1.Move the generator selector switch to the OFF position to avoid nuisance starts.
2.Close the Source 1 bypass switch manually. The Source 1 bypassed light will illuminate.
3.Open and rack out the Source 1 switching device (see Section 6). The Source 1 isolated light will illuminate and the Source 1 position energized light will no longer be illuminated.
4.Inspect and/or perform the needed maintenance on the Source 1 switching device.
5.Rack in the Source 1 switching device (see Section 6). The Source 1 switching device will automatically recharge and close when it is in the CONNECT position. The Source 1 iso- lated light will no longer be illuminated, but the Source 1 posi- tion energized light will be illuminated.
6.Open the Source 1 bypass switch. The Source 1 bypassed light will no longer be illuminated.
7.The Source 1 switching device is now back in automatic oper- ation.
7.3.2Source 2 TO Source 2 BYPASS
The Source 2 switching device can be bypassed and isolated by the following sequence:
1.Move the generator selector switch to the RUN position to avoid losing power.
2.Close the Source 2 bypass switching device manually. The Source 2 bypass light will illuminate.
7.2 Automatic Operation
The intelligence/supervisory circuits on Eaton transfer switches constantly monitor the condition of both the Source 1 and Source 2 power sources. These circuits automatically initiate an immedi- ate transfer of power from the Source 1 to the Source 2 power source when the power source fails or the voltage level drops below a preset value. Transfer back to the Source 1 power source is automatic upon return of the Source 1 power source.
Monitoring the power source is always performed on the line side of the power source to which the switch is connected. The Source 1 power source is the preferred source and the transfer switch will always seek this source when it is available.
3.Open and rack out the Source 2 switching device
(see Section 6). The Source 2 isolated light will illuminate and the Source 2 position energized light will no longer be illumi- nated.
4.Inspect and/or perform the needed maintenance on the Source 2 switching device.
5.Rack in the Source 2 switching device (see Section 6). The Source 2 switching device will automatically recharge and close when in the CONNECT position. The Source 2 isolated light will no longer be illuminated, and the Source 2 position energized light will illuminate.
6.Open the Source 2 Bypass switch. The source 2 Bypass light will no longer be illuminated.
7.The Source 2 Switch is now back in automatic operation.
For more information visit: www.Eaton.com | IB01602011E |