Eaton Electrical Magnum Transfer Switch manual Operation of the Bypass Isolation Transfer Switch

Page 25

Instructional Booklet

Fixed and Drawout Magnum Transfer Switches

Effective: March 2007

Page 25

The fixed switching device frame has two mounting feet, one on each side, to permit the fixed switching device to be securely mounted. Each mounting foot has two slotted mounting holes which are used to bolt the switching device securely in place. Use either 3/8” or M 10 bolts for this purpose. Refer to the dimen- sional drawings supplied with the transfer switch for switching device and bus stab dimensions.

6.3 Switching Device Operation

Switching devices should be operated manually and/or electrically before they are put into service. This can be done during the installation process or some later date prior to start-up. To check the switching device operation, follow the operational procedures outlined in switching device manual supplied with the transfer switch for both manually operated and electrically operated switching devices.

Section 7: Operation of the Bypass Isolation Transfer Switch

7.1 Operator Panel

The design of this transfer switch allows quick removal of the dif- ferent switching devices for inspection or maintenance or, if required, quick replacement.

The bypass isolation switch has two operator panels with switches and lights (Figure 35). The following descriptions are for those features that are standard with the bypass isolation switch. Additional features are described in the options section.

Figure 35.Bypass Isolation Switch.

The left door control panel has the following standard features:

1.Light to indicate if the Source 1 power source is available.

2.Light to indicate if the Source 2 power source is available.

3.Light to indicate if the Source 1position is energized, that is, the Source 1 switching device in the automatic transfer switch is closed.

4.Light to indicate if the Source 2 position is energized, that is, the Source 2 switching device in the automatic transfer switch is closed.

5.The Push-To-Test button allows testing of the transfer switch. Pushing the button two times will simulate a power failure, causing the transfer switch to start the transfer sequence. Pressing the button again will restore regular power.

Three-position selector switch to control the generator:

AUTO - The intelligence circuit of the transfer switch will start the generator if the Source 1 power source is not available.

OFF - The intelligence circuit of the transfer switch will not be able to start the generator, which eliminates nuisance starts during maintenance.

RUN - The generator will run regardless of the availability of the Source 1 power source.

IB01602011E

For more information visit: www.Eaton.com

Image 25
Contents Testing and Problem Solving Maintenance Renewal Parts Guide Manual for the Fixed and Drawout Magnum Transfer SwitchesInstructional Booklet Introduction Preliminary Comments and Safety PrecautionsGeneral Information Design Configuration Typical Load Transfer Switch Switching Device Type SchematicWithstand Ratings Typical Bypass Isolation Switch SchematicMagnum Transfer Switch Configurations Magnum Fixed and Drawout Switching DevicesGeneral Magnum Switching Device Fixed Switching Device for the Magnum Transfer Switch Transfer Switch Catalog Number Identification Transfer Switch Catalog Number Explanation Using the Style Identification GuideEquipment Description Receiving, Handling, and StorageSwitch Interlocks Open Transition Only Power PanelDrawout Interlocks Left Side View with Panels Removed Logic Panel Voltage Selection PanelDrawout Mechanism Neutrals FeaturesRelay Auxiliary Contacts Enclosure Transfer Switch Equipment EnclosuresStandards Installation and WiringMounting Location Seismic Tested and Approved Product Mounting Instructions Unpackaging and Inspection Mounting ProcedureWire Size for Available Power Cable Connections Power Cable ConnectionsMounting the Switching Device in the Drawout Mechanism Voltage Selection AdjustmentOperation WiringEngine Start Connection Close Switch by Pushing Close Button Automatic Transfer SwitchInstalling a Drawout Switching Device Drawout and Fixed Switching DevicesSwitching Device Positioning Switching Device in the Connect Position Levering and Position Indication Fixed Switching DeviceSwitching Device Operation Operation of the Bypass Isolation Transfer SwitchOperator Panel Automatic Operation Bypassing the Transfer SwitchSource 1 to Source 1 Bypass Source 2 to Source 2 BypassInto Its Source 2 to Source 1 Bypass Open Transition Only Manual Operation When in Bypass Mode Testing and Problem SolvingTesting Problem SolvingTransfer Switch Will Not Automatically Transfer to Source Transfer Switch Appears InoperativeTransfer Switch Will Not Automatically Recharge Switches Periodic Maintenance Procedures MaintenanceMaintenance Procedures IntroductionCover Removal and Replacement Cover Removal and ReplacementRenewal Parts Guide Instructional Booklet Sensing Harness TSMGH02 Kcmil Neutral Terminal Instructional Booklet

Magnum Transfer Switch specifications

The Eaton Electrical Magnum Transfer Switch is a premium solution designed for reliable power management in various applications, ranging from data centers to critical facilities. Known for its robust performance and advanced technology, the Magnum Transfer Switch ensures seamless transitions between utility and backup power sources, thereby enhancing operational continuity.

One of the standout features of the Eaton Magnum Transfer Switch is its unparalleled reliability. The switch is designed with heavy-duty components that provide up to 3,000 amps of continuous current with exceptional fault protection. Its construction is particularly suited for environments where power availability is crucial, ensuring that critical loads remain powered even during grid failures.

The Magnum Transfer Switch incorporates advanced technologies that simplify the operation and monitoring of power systems. It includes microprocessor-based controls that offer users customizable settings and configurations. These smart controls enable automatic transfer operations, ensuring quick response times when switching between power sources. The intelligent diagnostics feature further enhances reliability by offering predictive maintenance alerts, which help in identifying potential issues before they lead to failures.

Safety is a priority with the Magnum Transfer Switch. It is equipped with multiple interlocking features that prevent accidental switchovers and ensure that maintenance can be performed without the risk of electrical accidents. The design adheres to stringent safety standards, providing users with peace of mind.

Flexibility is another characteristic of the Eaton Magnum Transfer Switch. It offers a range of mounting options and configurations to fit diverse installation needs, whether in commercial infrastructures or industrial settings. The switch can be integrated with various power systems, making it a versatile choice for project developers and facility managers.

Additionally, the Magnum Transfer Switch supports eco-friendly initiatives through energy-efficient designs that minimize power loss during transfer operations. This feature is increasingly important as businesses aim to reduce their carbon footprint and enhance sustainability.

In summary, the Eaton Electrical Magnum Transfer Switch stands out for its reliable performance, advanced technologies, and robust safety measures. It is a versatile solution that meets the demands of modern power management, ensuring that critical systems operate continuously, even in the face of unexpected power interruptions. With its combination of efficiency, safety, and flexibility, the Magnum Transfer Switch remains a trusted choice for professionals in various industries.