Eaton Electrical Magnum Transfer Switch manual Power Panel, Switch Interlocks Open Transition Only

Page 11

Instructional Booklet

Fixed and Drawout Magnum Transfer Switches

Effective: March 2007

Page 11

The components comprising the three panels are installed in accor- dance with the specific requirements of the circuit being controlled. Each transfer switch is, therefore, tailor-made to a specific applica- tion.

3.2 Power Panel

The power panel consists of a means for making load, power, and neutral connections. The main contacts and the transfer mecha- nism are all on one steel frame (Figure 12). The actual power con- nections are shown in Figure 13.

Figure 12. Insulated Case Switching Device.

3.2.1 Main Contacts

The main contacts connect and disconnect the load to and from the different power sources. High withstand insulated case switches are the main contacts for the Source 1 and Source 2 power sources in standard, unmodified ATSs. Optional integral thermal and short circuit protection in either or both switching devices is available (Section 3.6). These continuous duty devices are rated for all classes of loads. In addition, they have high dielectric strength, heavy-duty switching and withstand capabili- ties, and high interrupting capacity.

3.2.2 Switch Interlocks (Open Transition Only)

Eaton transfer switches are mechanically and electrically inter- locked to prevent the two sets of main contacts from being closed simultaneously.

3.2.3 Drawout Interlocks

The standard closed transition ATS is not provided with a mechanical interlock. All bypass switching devices are mechani- cally interlocked to the drawout mechanism to ensure that the switching device is always open when connecting or disconnect- ing it from the line and load stabs when in the bypass mode.

All open transition switching devices are mechanically interlocked to the drawout mechanism to ensure that the switching device is always open when connecting or disconnecting it from the line and load stabs.

The switching device will close only in the DISCONNECT, TEST, and CONNECT positions.

IB01602011E

For more information visit: www.Eaton.com

Image 11 Contents
Testing and Problem Solving Maintenance Renewal Parts Guide Manual for the Fixed and Drawout Magnum Transfer SwitchesInstructional Booklet General Information Preliminary Comments and Safety PrecautionsIntroduction Design Configuration Typical Load Transfer Switch Switching Device Type SchematicWithstand Ratings Typical Bypass Isolation Switch SchematicGeneral Magnum Switching Device Magnum Fixed and Drawout Switching DevicesMagnum Transfer Switch Configurations Fixed Switching Device for the Magnum Transfer Switch Transfer Switch Catalog Number Identification Transfer Switch Catalog Number Explanation Using the Style Identification GuideEquipment Description Receiving, Handling, and StorageDrawout Interlocks Power PanelSwitch Interlocks Open Transition Only Left Side View with Panels Removed Drawout Mechanism Voltage Selection PanelLogic Panel Relay Auxiliary Contacts FeaturesNeutrals Enclosure Transfer Switch Equipment EnclosuresMounting Location Installation and WiringStandards Seismic Tested and Approved Product Mounting Instructions Unpackaging and Inspection Mounting ProcedureWire Size for Available Power Cable Connections Power Cable ConnectionsMounting the Switching Device in the Drawout Mechanism Voltage Selection AdjustmentEngine Start Connection WiringOperation Close Switch by Pushing Close Button Automatic Transfer SwitchSwitching Device Positioning Drawout and Fixed Switching DevicesInstalling a Drawout Switching Device Switching Device in the Connect Position Levering and Position Indication Fixed Switching DeviceOperator Panel Operation of the Bypass Isolation Transfer SwitchSwitching Device Operation Source 2 to Source 2 Bypass Bypassing the Transfer SwitchAutomatic Operation Source 1 to Source 1 BypassInto Its Source 2 to Source 1 Bypass Open Transition Only Problem Solving Testing and Problem SolvingManual Operation When in Bypass Mode TestingTransfer Switch Will Not Automatically Recharge Switches Transfer Switch Appears InoperativeTransfer Switch Will Not Automatically Transfer to Source Introduction MaintenancePeriodic Maintenance Procedures Maintenance ProceduresCover Removal and Replacement Cover Removal and ReplacementRenewal Parts Guide Instructional Booklet Sensing Harness TSMGH02 Kcmil Neutral Terminal Instructional Booklet