American Standard 6059.193 Test Installed Faucet, Maintenance, Handwash Sensor Operation

Page 7

TEST INSTALLED FAUCET

TO ENSURE A LAMINAR WATER FLOW the air must be slowly purged from the spout. To do so, cover the SENSOR (1) while slowly opening the water supply valves. When the water flows as a solid, smooth, steady stream, uncover the SENSOR (1) and fully open the water supply valve. Fig. 1.

MAINTENANCE

1HOW TO CHANGE SENSOR RANGE; (Factory set at 6") Fig. 2

1.Setting the Detection Zone (Distance): Fig. 1.

Detection Zone: 2" - 10" (50mm - 250mm)

Default: Set at Factory 6" (150mm)

Remove cover from ENCLOSURE. Disconnect GRAY SENSOR WIRE (1) from circuit board, then reconnect.

Fig. 2.

2.While the SENSOR CONTROL LED (2) is blinking slowly, place your hand 1 - 2 in. (30-50mm) in front of the sensor. Fig. 2a.

3.When the LED stops blinking and stays "ON", move your hand to the desired position and hold in place until the LED begins to blink again. Fig. 2a.

4.Once the SENSOR CONTROL LED (2) begins to blink again, remove your hand from the detection zone. When the flashing stops, the detection distance is set.

Fig. 2a.

2HANDWASH SENSOR OPERATION;

When the Sensor detects a user, the water immediately starts to flow. Water flow will stop Two seconds after user is out of sensor range. The off delay allows the user to comfortably move his hands without the flow cycling on to off. As a precaution, a safety timer will turn off the water, after the sensor has been blocked for 59 seconds. The water will stay off until the blockage is removed from the detection zone.

3HOW TO CLEAN FILTER; Fig. 3

CAUTION Before opening ENCLOSURE disconnect AC power supply.

1. Remove ENCLOSURE COVER.

2. Close SUPPLY STOP (5) with 4mm Hex wrench. Note: Keep water flowing out of faucet while shutting off.

3. Pull off Red (1) and Black (2) CONNECTORS from SOLENOID VALVE (3).

4. Unthread STRAINER (4) using a 7/16" socket.

5. Pull out the STRAINER (4) and clean with an old toothbrush. Rinse thoroughly with water.

6. Install the STRAINER (4) back in its place and tighten with a 7/16" socket.

Caution: do not over tighten strainer.

Note: It is recommended to clean strainer every 6 months.

7. Replace ENCLOSURE COVER. Tighten cover screws firmly.

Fig 1

DETECTION

ZONE

1

Fig. 2

1

Fig. 2a

1" - 2" (30mm - 50mm

UP TO 10" (250mm)

2BLINKING LED

2BLINKING LED

Fig.3

3

4

CLEAN

SCREENS

2

1

5

4

 

 

6

M 9 6 5 2 7 1

 

Image 7 Contents
Installation Instructions GN Spout UnpackingRecommended Tools InstallationRoughing-in Dimensions Install Spout Assembly FigConnect Spout Hose to Enclosure Fig Mount Enclosure FigConnect Water Supply to Enclosure and Wall Supply Fig Electrical Connections Fig Electrical InstallationMulti HOOK-UP Unit #1 Unit #2Unit #3 For AC-VERSIONHOW to Clean Filter Fig Test Installed FaucetMaintenance HOW to Change Sensor Range Factory set at 6 FigHOW to Clean and Remove the Flow Restrictor Fig General Cleaning FigFaqs