Touch panel / Buttons
①Display/Touch panel
②Collective ON/OFF Button *1
The Collective ON/OFF button enables the collective ON/OFF function that allows the user to turn on/off the air conditioning units, LOSSNAY, and DIDO controllers in all groups collectively. The LED corresponds to the operation status of controlled units.
Unlit : Indicates that all units are stopped.
Lit : Indicates that one or more units are in operation.
Blink : Indicates that an error is occurring.
③HOLD Button *1, *2, *3
The Hold button enables the hold function that allows the user to retain the current operation status for all selected groups collectively.
While the hold function is enabled, the scheduled operation is suspended, and the local remote controller operation is also prohibited.
Unlit : Normal operation
Lit :
④SET BACK
Button *1, *2, *3
The Setback button enables the setback mode for all selected groups collectively. The setback function automatically switches the system between cooling and heating to maintain the room temperature within the set temperature range. The wider the set temperature range, the greater the energy saving.
To keep the setback mode, enable the hold function. Unlit : Normal operation mode
Lit : Setback mode
⑤Power indicator
The power indicator lights up when the power to
Unlit : Power OFF
Lit : Power ON
*1 When the button is pressed while the operation is prohibited, the LED will blink twice. *2 The hold and setback functions can be enabled only through the HOME screen.
*3 The LED lights on and off only when the button ③ / ④ is pressed.