Error Code Abnormal point and detection method | Cause | Countermeasure | ||
| Indoor/outdoor unit communication | 1 Contact failure, short circuit or, ∗ Check LED display on the outdoor control cir- | ||
| error (Signal receiving error) | miswiring (converse wiring) of | cuit board. (Connect | |
| 1 Abnormal if indoor controller board | indoor/outdoor unit connecting |
| |
| cannot receive any signal normally for 6 | Refer to | ||
| wire | |||
| minutes after turning the power on. | 1 Check disconnection or looseness of indoor/ | ||
| 2 Defective transmitting receiving | |||
| 2 Abnormal if indoor controller board | circuit of indoor controller board | outdoor unit connecting wire of indoor unit or | |
| cannot receive any signal normally for 3 | outdoor unit. | ||
| 3 Defective transmitting receiving | |||
E6 | minutes. | Check all the units in case of twin indoor | ||
3 Consider the unit as abnormal under the | circuit of indoor controller board | unit system. | ||
| ||||
| following condition: When 2 or more | 4 Noise has entered into indoor/ | ||
| indoor units are connected to 1 | outdoor unit connecting wire. | check. If abnormality generates again, | |
| outdoor unit, indoor controller board |
| replace indoor controller board or outdoor | |
| cannot receive a signal for 3 minutes |
| controller circuit board. | |
| from outdoor controller circuit board, a |
| ∗ Other indoor controller board may have | |
| signal which allows outdoor controller |
| defect in case of twin indoor unit system. | |
| circuit board to transmit signals. |
|
| |
|
|
| ||
| Indoor/outdoor unit communication | 1 Defective transmitting receiving | ||
| error (Transmitting error) | circuit of indoor controller board | check. If abnormality generates again, | |
E7 | Abnormal if “1” receiving is detected 30 | 2 Noise has entered into power | replace indoor controller board. | |
times continuously though indoor controller | supply. |
| ||
|
| |||
| board has transmitted “0”. | 3 Noise has entered into outdoor |
| |
|
| control wire. |
| |
|
|
|
| |
| Indoor controller board | 1 Defective indoor controller | 1 Replace indoor controller board. | |
Fb | Abnormal if data cannot be normally read | board |
| |
from the nonvolatile memory of the indoor |
|
| ||
|
|
| ||
| controller board. |
|
| |
|
|
|
| |
| Remote controller control board | 1 Defective remote controller | 1 Replace remote controller. |
1Abnormal if data cannot be normally read from the nonvolatile memory of the
E1 | remote controller control board. |
|
|
(Error code: E1) |
|
| |
or |
|
| |
|
|
| |
E2 | 2 Abnormal if the clock function of remote |
|
|
| controller cannot be normally operated. |
|
|
| (Error code: E2) |
|
|
|
|
|
|
| Forced compressor stop | 1 Drain pump trouble | 1 Check the drain pump. |
| (due to water leakage abnormality) |
|
|
| 1 When the intake temperature subtracted | 2 Drain defective | 2 Please confirm whether water can be |
| with liquid pipe temperature is less than | · Drain pump clogging | drained. |
| · Drain pipe clogging |
| |
| whether it is soaked in the water or not |
|
|
| at the interval of 90 seconds. (Drain | 3 Open circuit of drain sensor | 3 Confirm the resistance of the drain sensor. |
| pump will start operating when the drain sen- | side heater |
|
| sor detects to be soaked in the water.) |
|
|
| 2 The unit has a water leakage abnormality | 4 Contact failure of drain sensor 4 Check the connector contact failure. | |
| when the following conditions, a and b, | connector |
|
| are satisfied while the |
|
|
| detection is performed. | 5 Dew condensation on drain | 5 Check the drain sensor leadwire mounted. |
| a) The drain sensor detects to be | sensor | Check the filter clogging. |
PA | soaked in the water 10 times in a row. | · Drain water trickles along |
|
b) The intake temperature subtracted | lead wire. |
| |
(2502) |
| ||
with liquid pipe temperature is detect- | · Drain water waving due to filter |
| |
(2500) |
| ||
ed to be less than | clogging |
| |
|
| ||
| total of 30 minutes. (When the drain |
|
|
| sensor detects to be NOT soaked in | 6 Extension piping connection | 6 Check the piping connection. |
| the water, the detection record of a | difference at twin system |
|
| and b will be cleared.) |
|
|
3The drain sensor detection is performed
in operations other than cooling. (When | 7 Miswiring of indoor/ outdoor | 7 Check the indoor/ outdoor connecting wires. |
the unit stops operating, during heating | connecting at twin system |
|
or fan operation, when the unit stops |
|
|
because of some abnormality) |
|
|
*Once the water leakage abnormality is | 8 Room temperature thermistor / | 8 Check the room temperature display of |
detected, abnormality state will not be | liquid pipe temperature thermis- | remote controller. |
released until the main power is reset. | tor detection is defective. | Check the indoor liquid pipe temperature |
|
| display of outdoor controller board. |