[2] Additional refrigerant charge
When charging directly from cylinder
·Check that cylinder for R410A on the market is syphon type.
·Charging should be performed with the cylinder of syphon stood vertically. (Refrigerant is charged from liquid phase.)
Unit
Gravimeter
[3] Service tools
Use the below service tools as exclusive tools for R410A refrigerant.
No. |
| Specifications |
1 | Gauge manifold | ·Only for R410A |
|
|
|
|
| ·Use the existing fitting specifications. (UNF1/2) |
|
|
|
|
| ·Use |
|
|
|
2 | Charge hose | ·Only for R410A |
|
|
|
|
| ·Use pressure performance of 5.09MPa·G or over. |
3Electronic scale
4 | Gas leak detector | ·Use the detector for R134a, R407C or R410A. |
|
|
|
5 | Adaptor for reverse flow check | ·Attach on vacuum pump. |
6Refrigerant charge base
7 Refrigerant cylinder | ·Only for R410A Top of cylinder (Pink) |
Cylinder with syphon
8Refrigerant recovery equipment
4