3.Duct Work

(1)All series units are equipped with horizontal supply and return air openings. Duct connection to the unit should be made with duct flanges and secured directly to the air openings with flexible duct connectors to avoid normal noise transmission.

(2)For vertical air supply, a field supply plenum should be used.

The figure below shows the recommended method for duct connection.

(3)To prevent air leakage, all duct seams should be taped.

Ducts run in air spaces that are not air-conditioned must be insulated and provided with a vapor barrier. Ducts exposed to the outside must be weatherproofed. For quiet operation, we recommend that the insulation on the supply duct be placed inside, lining the duct.

(4)Where ducts from the outside enter a building, the duct openings in the building should be sealed with weather stripping to prevent rain, duct, sand,etc. from entering the building.

(5)Correctly sized filters must be fitted and there is no provision within the unit, however the filters may be installed in the return air.

4.Drain piping

PRH unit

Vertical air

 

plenum

Plenum

 

divider

 

 

Insulation

Roof curb

Roof curb

 

Duct Singleduct

Roof line

Duct

divider

Duct connection with a vertical air plenum

(1) A 1 FPT condensate drain fitting is provided. The

drain pipe can be led out at the right or left side.

Under standard specifications, it is led out at the left

side and the right side is covered.

(2) The drain pipe must be provided with a trap on the

outside of the unit and also installed at an incline for

proper drainage, as shown below.

A=>70mm B=>2C C=>2XE.S.P

A C

Drain trap

B

Drain piping

The drain pipe should extend below this level.

(3) To prevent condensate formation and leakage,

provide the drain pipe with insulation to safeguard

against sweating.

(4) Upon completion of the piping work, check that there

is no leakage and that the water drains off properly.

Note:ESP=External Static Pressure

Drain trap for condensate

- 52 -

Image 53 Contents
Heat Pump Data BookContents For correct installation Safety for USEDo not wash the unit with water Complete Line UP High Sensible Cooling Capacity FeaturesDescriptions Mechanical SpecificationsPRH PRH-L Typical Installation ExampleGross SpecificationsHeating Electrical DataCooling Cooling Capacity Nominal Air FlowPR-5YC,PRH-5YA,PRH-5YA-L Capacity TablesFactor for Various Air Flow PR-5YC PRH-5YA-LRange PRH-5YA Heating Capacity Nominal Air FlowPRH-5YA,PRH-5YA-LPR-8YC PRH-8YA-L PRH-8YA Cooling Capacity Nominal Air FlowPR-8YC,PRH-8YA,PRH-8YA-LPRH-8YA Heating Capacity Nominal Air FlowPRH-8YA,PRH-8YA-LPR-8YC PRH-8YA-L PR-10YC PRH-10YA-L PRH-10YA Cooling Capacity Nominal Air FlowPR-10YC,PRH-10YA,PRH-10YA-LPRH-10YA Heating CapacityPRH-10YA-L PR-15YC PRH-15YA-L PRH-15YA Cooling Capacity Nominal Air FlowPR-15YC,PRH-15YA,PRH-15YA-LPRH-15YA PR-15YC PRH-15YA-LPR-20YC PRH-20YA-L PRH-20YA Cooling Capacity Nominal Air FlowPR-20YC,PRH-20YA,PRH-20YA-LPRH-20YA PRH-20YA-LPR-YC Operation rangePRH-YA PRH-YA-LRpm FAN PerformanceOperation range Fan speed Pressure Pulley outside dimensions are shown below Unit mm PR-5YC PRH-5YA PRH-5YA-L PR-8YC PRH-8YA PRH-8YA-L NC CurvesPR-15YC PR-10YCPR-20YC Outline DimensionsPR-15,20YC PRH-15, 20YA PRH-15, 20YA-L PR-8,10YC PRH-8, 10YA PRH-8, 10YA-LPR-5, 8, 10YC Standard Wiring DiagramsPR-15, 20YC Standard Special Order K Control PR-5, 8, 10YCInternal Protector Special Order LOW TemperaturePR-15, 20YC 50Hertz Special Order K Control & LOW TemperaturePRH-5, 8, 10YA-L Standard PRH-5, 8, 10YAPRH-15, 20YA-L Standard PRH-5, 8, 10YA PRH-5, 8, 10YA-L 10YA PRH-15, 20YA PRH-15, 20YA-L 21S4 Way valve MC Operate MF2 Operate OFF Safety Device OFF? YES Electrical Operation Flow ChartsOFF 52C OFF MC Stop MF2 Stop RL on CH on Service Call MF1 Operate YESMF1 Operate Start Power on Start Power on PR-8, 10, 15, 20YC Refrigerant SchematicsPR-5YC PRH-8, 10, 15, 20YA PRH-8, 10,15,20YA-L Accessory Availability Safety & Control DevicesElectrical Physical DataRooftop Package AIR Cooled Heatpump and Cooling only Units Roof Mounting InstallationClearances Drain piping Duct WorkTrial Operation Electrical WiringFinal Checks Check Points for Operation Instructions for USEFingermarks MaintenancePreparing for Prolonged Shutdown TroubleshootingPreparing for Operation After Prolonged Shutdown Specification Guidelines Memo Data Book PR,PRH Mitsubishi Electric Corporation