13.0Troubleshooting
NOTE: Inspect the unit before proceeding with these steps.
Start-up troubleshooting:
Problems | Possible causes | You should try this |
|
|
|
1. Unit does not work. | • The circuit board may |
|
| be defective. |
|
B
G
|
| VE0082 |
|
| • Unplug the unit. Disconnect the main control |
|
| and the optional(s) control(s) (if need be). Jump |
|
| B and G terminals. Plug the unit. If the motor |
|
| runs on high speed and the damper opens, the |
|
| circuit board is not defective. |
|
|
|
2. The damper actuator | • The | • Unplug the unit and check to make sure all the |
does not work. | have a loose connection. | crimp connections are secured. Check the damper |
|
| actuator connections as well. |
| • The damper actuator may | • Feed 120 V directly to the damper actuator. If the |
| be defective. | problem persists, replace the damper actuator. |
| • The circuit board may | • Replace the circuit board if the problem is not |
| be defective. | solved by the above. |
|
|
|
3. The wall control does | • TBI mode is activated. | • If the outside temperature is below |
not work OR |
| and the unit has an enthalpic recovery core |
the indicators flashes |
| (energy recovery core), then the TBI mode is |
every 8 seconds. |
| probably activated. (See Section 7.5.) |
| • The wires may be in | • Ensure that the color coded wires have been |
| reverse position. | connected to their appropriate places. |
| • Erratic operation of the | • Unplug the unit. Wait 30 seconds. Plug it back in. |
| control every 8 seconds. |
|
| • The wires may be broken. | • Inspect every wire and replace any that are damaged. |
| • There may be a |
•The wire in the wall OR the wall control may be defective.
•Remove the wall control and test it right beside the unit using another shorter wirer. If the wall control works there, change the wire. If it does not, change the wall control.
•The circuit board may be defective.
•If the second wall control does not solve the problem, then replace the circuit board.
30