Jenn-Air W10197059B Venting Requirements, Cutout Dimensions, For Best Performance, Makeup Air

Page 5

Cutout Dimensions

A B

D

C

E

F

H

I

J

G

A. 28⁷⁄₈" (73.4 cm) maximum on 30" (76.2 cm) models 34½" (87.6 cm) maximum on 36" (91.4 cm) models

B. 21¹⁄₈" (53.7 cm)maximum on both 30" (76.2 cm) and 36" (91.4 cm) models

C. 8⁵⁄₈" (21.9 cm) on 30" (76.2 cm) models 15⁷⁄₁₆" (39.2 cm) on 36" (91.4 cm) models

D. 6⁵⁄₁₆" (16.0 cm) on both 30" (76.2 cm) and 36" (91.4 cm) models E. 2" (5.1 cm) minimum space to front edge of cooktop

F. Floor exhaust option

G. 6¹⁄₈" (15.6 cm) for 6" vent system

H. 8⁵⁄₈" (21.9 cm) on 30" (76.2 cm) models 15⁷⁄₁₆" (39.2 cm) on 36" (91.4 cm) models

I. 16" (40.6 cm) on both 30" (76.2 cm) and 36" (91.4 cm) models J. Wall exhaust option

Venting Requirements

IMPORTANT: This cooktop must be exhausted outdoors unless using the Jenn-Air®Duct Free Filter Accessory Kit. See “Venting Methods” section.

Do not terminate the vent system in an attic or other enclosed area.

Use a Jenn-Air®vent cap.

Vent system must terminate to the outside.

Use only a 6" (15.2 cm) round metal vent. Rigid metal vent is recommended. For best performance, do not use plastic or metal foil vent.

Before making cutouts, make sure there is proper clearance within the wall or floor for the exhaust vent.

Do not cut a joist or stud unless absolutely necessary. If a joist or stud must be cut, then a supporting frame must be constructed.

The size of the vent should be uniform.

The vent system must have a damper. If roof or wall cap has a damper, do not use damper supplied with the range hood.

Use vent clamps to seal all joints in the vent system.

Use caulking to seal exterior wall or roof opening around the cap.

Determine which venting method is best for your application.

For Best Performance:

Use 26-gauge minimum galvanized or 25-gauge minimum aluminum metal vent. Poor quality pipe fittings can reduce airflow. Flexible metal vent is not recommended.

NOTE: Local codes may require a heavier gauge material.

Metal duct may be reduced to 30-gauge galvanized steel or 26-gauge aluminized steel if allowed by local codes. This reduction is based on information in the International Residential Codes Section M1601.1 (2006 edition).

Do not install 2 elbows together.

Use no more than three 90° elbows.

If an elbow is used, install it as far away as possible from the hood’s vent motor exhaust opening.

Make sure there is a minimum of 18" (45.7 cm) of straight vent between the elbows if more than one elbow is used.

Elbows too close together can cause excess turbulence that reduces airflow.

Do not use a 5" (12.7 cm) elbow in a 6" (15.2 cm) or 3¹⁄₄" x 10" (8.3 x 25.4 cm) system.

Do not reduce to a 5" (12.7 cm) system after using 6" (15.2 cm) or 3¹⁄₄" x 10" (8.3 x 25.4 cm) fittings.

Avoid forming handmade crimps. Handmade crimps may restrict airflow.

Use a Jenn-Air®vent cap for proper performance. If an alternate wall or roof cap is used, be certain the cap size is not reduced and that it has a backdraft damper.

Use vent clamps to seal all joints in the vent system.

Use caulking to seal exterior wall or roof opening around the cap.

The length of vent system and number of elbows should be kept to a minimum to provide efficient performance.

The maximum equivalent length of the vent system is

60 ft (18.3 m). For altitudes above 4,500 ft (1272 m), reduce recommended vent run by 20% for best performance.

Cold Weather Installations

An additional backdraft damper should be installed to minimize backward cold air flow and a thermal break installed to minimize conduction of outside temperatures as part of the vent system.

The damper should be on the cold air side of the thermal break.

Makeup Air

Local building codes may require the use of makeup air systems when using ventilation systems greater than specified CFM of air movement. The specified CFM varies from locale to locale.

Consult your HVAC professional for specific requirements in your area.

5

Image 5
Contents 30 76.2 CM and 36 91.4 CM Electric Your safety and the safety of others are very important Cooktop SafetyLocation Requirements Installation RequirementsTools and Parts 36 91.4 cm Cooktop for standard and electric models Cabinet DimensionsCold Weather Installations Cutout DimensionsVenting Requirements For Best PerformanceJenn-AirDuct Free Filter Accessory Kit Concrete Slab Installations Exhaust Through WallVenting Methods Option 1 Roof Venting Option 2 Wall VentingCalculating Vent System Length Electrical RequirementsExample vent system Vent Piece Cm RoundInstall Foam Strip Installation InstructionsPrepare Cooktop Rotate Blower OptionalTo rotate blower motor To rotate blowerIf your home has You will be Go to Section Connecting to Install CooktopMake Electrical Connection Electrical Connection OptionsIf you need Assistance or Service Complete InstallationPage Votre sécurité et celle des autres est très importante Sécurité DE LA Table DE CuissonOutillage et pièces Exigences DinstallationExigences demplacement Dimensions du placard Installations pour régions à climat froid Dimensions de l’ouverture à découperExigences concernant lévacuation Pour obtenir la meilleure performanceMéthodes dévacuation La trousse accessoire de filtration sans conduit Jenn-AirCalcul de la longueur effective du circuit dévacuation Spécifications électriquesExemple de circuit dévacuation Composant Conduit de diamètre de 15,2 cm Coude à Pi 0,8 mInstallation de la bande de mousse Instructions D’INSTALLATIONPréparation de la table de cuisson Avant d’établir la connexion électriquePour faire pivoter le moteur du ventilateur Rotation du ventilateur FacultativePour faire pivoter le ventilateur Raccordement électrique Installation de la table de cuissonOptions de raccordement électrique Câblage de la maison Point deSi vous avez besoin dassistance ou de service Achever linstallationPage 2009 10/09 All rights reserved