Electrical data

STANDARD SINGLE INPUT POWER CONFIGURATION

30XW

UNIT VOLTAGE

 

NO. POWER

 

 

 

ICF

REC FUSE

CONTROL CIRCUIT

UNIT

 

Supplied

SUPPLY

MCA

MOCP

 

 

MCA and

V-Ph-Hz

 

 

 

SIZE

V-Ph-Hz

SIZE

 

 

 

CONDUCTORS

 

 

 

 

 

MOCP

Min

 

Max

 

 

WD

 

XL

 

 

 

 

 

 

 

 

200-3-60

187

 

220

9

920.3

1200

1347.0

 

1200

115-1-60

20

 

230-3-60

207

 

253

9

799.0

1000

1171.1

 

1000

115-1-60

20

325

380-3-60

342

 

418

6

487.6

700

710.7

 

1753.7

600

115-1-60

20

 

460-3-60

414

 

506

6

401.0

500

586.2

 

1448.2

450

115-1-60

20

 

575-3-60

518

 

633

3

317.3

450

467.0

 

1157.0

400

115-1-60

20

 

200-3-60

187

 

220

12

1168.2

1600

1848.2

 

1600

115-1-60

20

325

230-3-60

207

 

253

9

1018.4

1200

1608.6

 

1200

115-1-60

20

380-3-60

342

 

418

6

614.5

800

973.1

 

2452.1

700

115-1-60

20

HM

 

 

460-3-60

414

 

506

6

510.8

700

805.0

 

2027.0

600

115-1-60

20

 

 

 

 

575-3-60

518

 

633

6

406.8

500

642.8

 

1620.8

450

115-1-60

20

 

200-3-60

187

 

220

9

920.3

1200

1347.0

 

1200

115-1-60

20

 

230-3-60

207

 

253

9

799.0

1000

1171.1

 

1000

115-1-60

20

350

380-3-60

342

 

418

6

487.6

700

710.7

 

1753.7

600

115-1-60

20

 

460-3-60

414

 

506

6

401.0

500

586.2

 

1448.2

450

115-1-60

20

 

575-3-60

518

 

633

3

317.3

450

467.0

 

1157.0

400

115-1-60

20

 

200-3-60

187

 

220

12

1168.2

1600

1848.2

 

1600

115-1-60

20

350

230-3-60

207

 

253

9

1018.4

1200

1608.6

 

1200

115-1-60

20

380-3-60

342

 

418

6

614.5

800

973.1

 

2452.1

700

115-1-60

20

HM

 

 

460-3-60

414

 

506

6

510.8

700

805.0

 

2027.0

600

115-1-60

20

 

 

 

 

575-3-60

518

 

633

6

406.8

500

642.8

 

1610.8

450

115-1-60

20

 

200-3-60

187

 

220

9

1041.3

1200

1400.8

 

1200

115-1-60

20

 

230-3-60

207

 

253

9

902.9

1200

1217.3

 

1200

115-1-60

20

400

380-3-60

342

 

418

6

545.2

700

736.3

 

1779.3

700

115-1-60

20

 

460-3-60

414

 

506

6

452.9

600

609.3

 

1471.3

600

115-1-60

20

 

575-3-60

518

 

633

3

366.3

500

488.8

 

1178.6

450

115-1-60

20

 

200-3-60

187

 

220

12

1329.8

1600

1920.0

 

1600

115-1-60

20

400

230-3-60

207

 

253

12

1156.7

1600

1670.1

 

1600

115-1-60

20

380-3-60

342

 

418

6

700.9

1000

1011.5

 

2490.5

800

115-1-60

20

HM

 

 

460-3-60

414

 

506

6

579.8

800

835.7

 

2057.7

700

115-1-60

20

 

 

 

 

575-3-60

518

 

633

6

464.4

600

668.4

 

1646.4

600

115-1-60

20

 

 

LEGEND

ICF

Maximum Instantaneous Current Flow

HM

Heat Machine Units

LRA

Locked Rotor Amps

MCA

Minimum Circuit Ampacity (for wire sizing)

MOCP —

Maximum Overcurrent Protection

RLA

Rated Load Amps

WD

Wye-Delta Start

XL

Across-the-Line Start

NOTES:

1.Each main power source must be supplied from a field-supplied fused electrical service with a (factory-installed or field-installed) disconnect located in sight from the unit.

2.Control circuit power must be supplied from a separate source through a field-supplied disconnect. An optional control transformer may be used to provide control circuit power from the main unit power supply.

3.Maximum instantaneous current flow (ICF) during start-up is the point in the starting sequence where the sum of the LRA for the start-up compressor, plus the total RLA for all running compressors is at a maximum.

4.Maximum incoming wire size for each terminal block is 500 kcmil.

5.Maximum allowable phase imbalance is: voltage, 2%; amps, 5%.

6.Use copper conductors only.

7.The MOCP is calculated as follows:

MOCP = (2.25) (largest RLA) + the sum of the other RLAs. Size the fuse one size down from the result. The RLAs are listed on the nameplate.

The recommended fuse size in amps (RFA) is calculated as follows: RFA = (1.50) (largest RLA) + the sum of the other RLAs. Size the fuse one size up from the result. The RLAs are listed on the nameplate.

26

Image 26
Contents Features/Benefits Small footprintTable of contents Marine container shipment Optional suction service valvesRefrigerant isolation valves Heat exchangersTWIN-SCREW Design Touch Pilot DisplaySmooth Rotary Compressor Optional Navigator DisplayModel number nomenclature A30-4744Capacity ratings Physical data 30XW325-400 Unit Physical Data English30XW325-400 Unit Physical Data SI A30-4684.eps Options and accessoriesFactory-installed options A30-4685Field-supplied and field-installed insulation Field-installed accessoriesFIELD-SUPPLIED and FIELD-INSTALLED Insulation A30-4686Standard 30XW Unit Dimensions Dimensions30XW Unit Dimensions 30XW Unit and Waterbox DimensionsA30-4747 A304755 A30-4748A30-4749 A30-4725A30-4751 A30-4752Evaporator and Condenser Flow Rates Selection procedurePerformance data 30XW325-400 Evaporator Marine Waterbox 30XW325-400 Evaporator NIH Flange30XW325-400 Condenser Marine Waterbox A30-469430XW325-400 Evaporator NIH Victaulic 30XW325-400 Condenser NIH Victaulic A30-469630XW325-400 Condenser NIH Flange Control sequence ControlsMicroprocessor Safeties A30-4697 Typical control wiring schematics30XW Unit Control Wiring Schematic Application data Evaporator fouling factor Water loop volumeVariable evaporator flow rates Condenser minimum flow rateElectric utility interests A30-4700 WiringTypical Piping and Wiring for 30XW Evaporator and Condenser Standard Single Input Power Configuration Electrical dataSupply Optional Dual Input Power ConfigurationNO. Power ICF REC Fuse Control Circuit Unit RLA LRA WD Compressor Electrical Data30HX Unit Voltage Compressor Compressor a Compressor B Size RLAGuide specifications Hvac Guide SpecificationsGuide specifications Page Carrier Corporation Syracuse, New York