Carrier 30XW325-400 manual Capacity ratings

Page 6

Capacity ratings

 

CAPACITY

INPUT

EVAPORATOR

EVAPORATOR

CONDENSER

CONDENSER

FULL LOAD

 

30XW

FLOW

PRESSURE DROP

FLOW

PRESSURE DROP

IPLV

 

 

UNIT SIZE

Tons

Output

POWER

gpm

L/s

Ft of

kPa

gpm

L/s

Ft of

kPa

EFFICIENCY

(kW/Ton)

 

(kW)

(kW)

Water

Water

(kW/Ton)

 

 

 

 

 

 

 

 

 

 

 

 

325

322

1132.5

204.8

773

48.8

15.6

46.5

967

61.0

10.9

32.5

0.636

0.468

350

343

1206.3

215.7

824

52.0

17.5

52.2

1029

64.9

12.3

36.7

0.629

0.471

400

385

1354.0

242.8

924

58.3

21.5

64.1

1155

72.9

15.2

45.3

0.631

0.474

LEGEND

AHRI — Air Conditioning, Heating and Refrigeration Institute

IPLV — Integrated Part Load Value

NOTES:

1.Certified in accordance with AHRI Standard 550/590 at standard rating conditions.

2.Standard rating conditions are as follows:

Evaporator Conditions:

Leaving Water Temperature: 44 F (6.7 C)

Flow:2.4 gpm per ton (0.043 L/s per kW) Condenser Conditions:

Entering Water Temperature:85 F (29.4 C)

Flow:

3.0 gpm per ton (0.054 L/s per kW)

Fouling Factor (Evaporator):

0.00010 hr x sq ft x F per Btuh (0.000018 m2 x K per W) Fouling Factor (Condenser):

0.00025 hr x sq ft x F per Btuh (0.000044 m2 x K per W)

3.IPLV is a single number part-load efficiency value calculated from the system full-load efficiency values and corrected for a typical building air-conditioning application.

4.Contact Carrier for custom ratings.

5.Data shown for standard chiller with 2 pass, nozzle-in-head (NIH) waterboxes.

6

Image 6
Contents Features/Benefits Small footprintTable of contents Marine container shipment Optional suction service valvesRefrigerant isolation valves Heat exchangersTWIN-SCREW Design Touch Pilot DisplaySmooth Rotary Compressor Optional Navigator DisplayModel number nomenclature A30-4744Capacity ratings Physical data 30XW325-400 Unit Physical Data English30XW325-400 Unit Physical Data SI A30-4684.eps Options and accessoriesFactory-installed options A30-4685Field-supplied and field-installed insulation Field-installed accessoriesFIELD-SUPPLIED and FIELD-INSTALLED Insulation A30-4686Standard 30XW Unit Dimensions Dimensions30XW Unit Dimensions 30XW Unit and Waterbox DimensionsA30-4747 A304755 A30-4748A30-4749 A30-4725A30-4751 A30-4752Selection procedure Performance dataEvaporator and Condenser Flow Rates 30XW325-400 Evaporator Marine Waterbox 30XW325-400 Evaporator NIH FlangeA30-4694 30XW325-400 Evaporator NIH Victaulic30XW325-400 Condenser Marine Waterbox A30-4696 30XW325-400 Condenser NIH Flange30XW325-400 Condenser NIH Victaulic Controls MicroprocessorControl sequence Safeties Typical control wiring schematics 30XW Unit Control Wiring SchematicA30-4697 Application data Evaporator fouling factor Water loop volumeVariable evaporator flow rates Condenser minimum flow rateElectric utility interests Wiring Typical Piping and Wiring for 30XW Evaporator and CondenserA30-4700 Standard Single Input Power Configuration Electrical dataOptional Dual Input Power Configuration NO. Power ICF REC Fuse Control Circuit UnitSupply RLA LRA WD Compressor Electrical Data30HX Unit Voltage Compressor Compressor a Compressor B Size RLAGuide specifications Hvac Guide SpecificationsGuide specifications Page Carrier Corporation Syracuse, New York