m. Time of day:

1)Display module, in conjunction with the microprocessor, must also be capable of displaying the output (results) of a ser- vice test. Service test shall verify opera- tion of every switch, thermistor, and compressor before chiller is started.

2)Diagnostics shall include the ability to review a list of the 30 most recent alarms with clear language descriptions of the alarm event. Display of alarm codes without the ability for clear lan- guage descriptions shall be prohibited.

3)An alarm history buffer shall allow the user to store no less than 30 alarm events with clear language descriptions, time and date stamp event entry.

4)The chiller controller shall include multi- ple connection ports for communicating with the local equipment network, the Carrier Comfort Network (CCN) sys- tem and the ability to access all chiller control functions from any point on the chiller.

5)The control system shall allow software upgrade without the need for new hard- ware modules.

J.Operating Characteristics:

Unit shall be capable of starting up with 95 F (35 C) entering fluid temperature to the evaporator.

K.Electrical Requirements:

1.Unit primary electrical power supply shall enter the unit at a single location.

2.Unit shall operate on 3-phase power at the volt- age shown in the equipment schedule.

3.Control voltage shall be 115-v (60 Hz), single- phase, separate power supply.

L.Special Features:

Certain standard features are not applicable when the features designated by * are specified. For assis- tance in amending the specifications, contact your local Carrier Sales office.

*1. Wye-Delta Starter:

Unit shall have a factory-installed, wye-delta starter to minimize electrical inrush current.

2.Vibration Isolation:

Unit shall be supplied with rubber-in-shear vibration isolators for field installation.

3.Control Power Transformer:

Unit shall be supplied with a factory-installed controls transformer that will supply control cir- cuit power from the main unit power supply.

4.Temperature Reset Sensor:

Unit shall reset leaving chilled fluid temperature based on outdoor ambient temperature or space temperature when this sensor is installed.

* 5. Minimum Load Control:

Unit shall be equipped with factory-installed, microprocessor-controlled, minimum load con- trol that shall permit unit operation down to 10% of full capacity.

6.One-Pass Evaporator:

Factory-installed option shall reduce pressure drop for high flow applications.

7.Three-Pass Evaporator:

Factory-installed option shall enhance perfor- mance for low flow applications.

8.Energy Management Module:

A factory or field installed module shall provide the following energy management capabilities: 4 to 20 mA signals for leaving fluid temperature reset, cooling set point reset or demand limit control; 2-point demand limit control (from 0 to 100%) activated by a remote contact closure; and discrete input for "Ice Done" indication for ice storage system interface.

9.BACnet™ Translator Control:

Unit shall be supplied with field-installed inter- face between the chiller and a BACnet Local Area Network (LAN, i.e., MS/TP EIA-485).

10.LON Translator Control:

Unit shall be supplied with field-installed inter- face between the chiller and a Local Operating Network (LON, i.e., LonWorks® FT-10A ANSI/EIA-709.1).

11.Navigator™ Hand Held Portable Display:

a.Portable hand held display module with a minimum of 4 lines and 20 characters per line, or clear English, Spanish, Portuguese or French language.

b.Display menus shall provide clear language descriptions of all menu items, operating modes, configuration points and alarm diag- nostics. Reference to factory codes shall not be accepted.

c.RJ-14 connection plug shall allow display module to be connected to factory-installed receptacle.

d.Industrial grade coiled extension cord shall allow the display module to be moved around the chiller.

e.Magnets shall hold the display module to any sheet metal panel to allow hands-free operation.

f.Display module shall have NEMA 4x housing.

g.Display shall have back light and contrast adjustment for easy viewing in bright sun- light or night conditions.

h.Raised surface buttons with positive tactile response.

31

Image 31
Contents Small footprint Features/BenefitsTable of contents Heat exchangers Optional suction service valvesRefrigerant isolation valves Marine container shipmentOptional Navigator Display Touch Pilot DisplaySmooth Rotary Compressor TWIN-SCREW DesignA30-4744 Model number nomenclatureCapacity ratings 30XW325-400 Unit Physical Data English Physical data30XW325-400 Unit Physical Data SI A30-4685 Options and accessoriesFactory-installed options A30-4684.epsField-installed accessories Field-supplied and field-installed insulationA30-4686 FIELD-SUPPLIED and FIELD-INSTALLED Insulation30XW Unit and Waterbox Dimensions Dimensions30XW Unit Dimensions Standard 30XW Unit DimensionsA30-4748 A304755 A30-4747A30-4752 A30-4725A30-4751 A30-4749Performance data Selection procedureEvaporator and Condenser Flow Rates 30XW325-400 Evaporator NIH Flange 30XW325-400 Evaporator Marine Waterbox30XW325-400 Evaporator NIH Victaulic A30-469430XW325-400 Condenser Marine Waterbox 30XW325-400 Condenser NIH Flange A30-469630XW325-400 Condenser NIH Victaulic Microprocessor ControlsControl sequence Safeties 30XW Unit Control Wiring Schematic Typical control wiring schematicsA30-4697 Application data Condenser minimum flow rate Water loop volumeVariable evaporator flow rates Evaporator fouling factorElectric utility interests Typical Piping and Wiring for 30XW Evaporator and Condenser WiringA30-4700 Electrical data Standard Single Input Power ConfigurationNO. Power ICF REC Fuse Control Circuit Unit Optional Dual Input Power ConfigurationSupply RLA Compressor Electrical Data30HX Unit Voltage Compressor Compressor a Compressor B Size RLA LRA WDHvac Guide Specifications Guide specificationsGuide specifications Page Carrier Corporation Syracuse, New York