2.A ICEMAKER INOPERATIVE

YES

IS

“RUN”

“RUN/STOP”

“STOP”

HOPPER

 

FULL?

 

SWITCH

 

 

 

 

?

 

 

NO

 

 

 

 

NORMAL SHUTOFF ON

YES

IS BIN

NO

 

BIN THERMOSTAT.

THERMOSTAT

 

 

 

OPEN

 

1.CHECK THERMOSTAT ADJUSTMENT.

2.REPLACE BIN THERMOSTAT.

PUT SWITCH IN

“RUN” POSITION.

 

IS

 

 

 

IS LOW

 

 

IS HIGH

YES

WATER

YES

 

PRESSURE

NO

PRESSURE

 

SWITCH

 

SWITCH

 

LEVEL NORMAL

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

IN EVAP.?

 

 

 

OPEN?

 

 

OPEN?

 

 

 

 

 

 

20/80 PSI

 

 

448 PSI

 

 

NO

 

 

 

 

NO

 

 

 

YES

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CHECK FOR LOOSE CONNECTION

 

 

 

 

 

 

 

 

 

 

OR BROKEN WIRE.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1.CHECK THAT WATER SUPPLY IS OPEN.

2.CHECK WATER SUPPLY FILTER.

3.CHECK FOR PLUGGED WATER INLET VALVE.

4.CHECK FOR PROPER TIMING ON TIMERS, IN- CREASE IF LOW WATER LEVEL OBSERVED.

5.CHECK IF DRAINS ARE PLUGGED, KINKED,

OR ARE NOT PROPERLY PITCHED TO AN OPEN TRAP.

1.CHECK FOR REFRIGERANT UNDER- CHARGE.

2.CHECK TXV VALVE.

AIR COOLED UNITS

1.CHECK FOR RESTRICTED AIR FLOW TO AIR CONDENSER.

2.CHECK FOR HOT AIR RECIRCULATING TO AIR CONDENSER. ELIMINATE BY BAFFLING.

3.CHECK FOR DIRTY AIR COOLED CONDENSER.

4.CHECK CONDENSER FAN MOTOR.

5.CHECK FOR REFRIGERANT OVER-CHARGE.

WATER COOLED UNITS

1.CHECK EATER SUPPLY TO CONDENSER.

2.CHECK FOR FAULTY WATER REGULATOR VALVE.

3.CHECK FOR REFRIGERANT OVER-CHARGE.

4.CHECK FOR FOULED CONDENSER.

25

90846

Image 29
Contents From kent M O R a N D U MSpiral ICEMAKER-DISPENSER Table of Contents Table of Contents cont’d Important Installation Notice Safety PrecautionsUnpacking DescriptionPlumbing InstallationLocation Beverage System InstallationMounting Template Model SID650--80 15 7/8 29/32 29 1/4 18 3/416 1/4 28 3/4 14 7/8 15 3/4 17 5/8 29 1/4 34 3/8 34 7/8 16 5/811 1/8 13/16Models Post MIX Beverage Syustem Schematic BC Models Post MIX Beverage System Schematic Icemaker Start UPIcemaker Operating Instructions Cam Time Switch ActionOperating Instructions Wiring Schematic 115 / 1 / 60 HZ Wiring Diagram Refrigeration Schematic Cleaning Instructions MaintenanceDispenser Section For Units with Beverage SystemBeverage System Thermostat Altitude Adjustments MAINTENANCE/ADJUSTMENT ProcedureICE Thickness Adjustment Clearing Evaporator FREEZE-UPHarvest Timer Adjustment Cleaning / Replacing the FilterCleaning the Condenser AIR-COOLED Unit Manual Filling Detail of CAM Wheel # T1 Troubleshooting Guide 90846 90846 RUN? GO to Is ICE Production Icemaker Inoperative YES RUN RUN/STOP Check Voltage Problems No ICE on Evaporator Harvest YES ±10%? CON’T Check Refrigeration System 90846 Dispenser Problem YES Does Agitator ROTATE? 90846 Refrigeration Components Parts ListElectrical Controls Miscellaneous Components Description Refrigeration Components cont’dEvaporator Components Warranty IMI Cornelius INC