Air extraction
Danger of toxic fumes. Please heed the ,,Warning and Safety Instructions“ to avoid the dangers of toxic fumes.
The cooker hood should be in- stalled according to local building regulations. Seek approval from the building inspector where necessary.
Connection for extraction
–The extraction ducting should be as short and straight as possible.
–To ensure efficient air extraction the diameter of the exhaust ducting should not be less than 125 mm (5").
The use of flat ducting also reduces the air extraction efficiency.
–The use of exhaust ducting with a diameter less than 125 mm (5") and flat ducting increases the noise level of the cooker hood.
–Only use wide radius bends. Tight bends reduce the air throughput of the cooker hood.
–Only use smooth or flexible pipes made from
–Where ducting is horizontal, it must be laid to slope away at 1 cm per metre (1/8" per foot) , to ensure no condensation drains into the ap- pliance.
–If the exhaust air is to be ducted out- side, the installation of a Miele tele- scopic wall vent is recommended.
–If the exhaust air is to be ducted into a vent flue, the ducting must be di- rected in the flow direction of the flue.
Connection
Only use narrower diameter pipe- work where it is unavoidable, for example where existing pipework has to be used.
The narrower the diameter the lower the performance and the noisier the operation.
If a connection to 100 mm (4") diameter piping is to be made, fit the reducer supplied (adaptor) on to the exhaust connection of the cooker hood.
22