Air extraction

Push the ducting on to the cooker hood exhaust connector or on to the reducer (adaptor) and secure.

Note

If the exhaust ducting is to run through rooms, ceiling space etc. where there may be great variations in temperature between the different areas, the prob- lem of sweating or condensation will need to be addressed.

The exhaust ducting will need to be suitably insulated.

In addition to insulating the exhaust ducting it may also be necessary in some cases to install a suitable conden- sate trap to collect and evaporate any condensate which may occur.

When installing a condensate trap, ensure that it is located vertically and if possible directly above the exhaust connection.

Calculation of extraction ducting

A pipe diameter of 125 mm (5’’) should ensure trouble-free extraction up to a total pipe length of 33 m (108’’).

Determine the total pipe length as fol- lows:

Measure the total length of the ex- haust ducting to be used.

Add the appropriate length of addi- tional piping to this figure (see table), according to the number and type of bends:

Type

Angle

Radius of

Length of

of

of

bend

additional

bend

bend

 

 

piping

 

 

 

 

 

 

 

 

in inch

in mm

in foot

in

 

 

 

 

 

metres

 

 

 

 

 

 

Wall

 

 

 

 

 

vent

 

 

 

 

 

duct

 

 

 

 

 

with

 

 

 

3,3’

1.0

grill

 

 

 

 

 

and

 

 

 

 

 

flap

 

 

 

 

 

 

 

 

 

 

 

Smooth

90°

5

125

1

0.3

interior

90°

10

250

3/4

0.2

wall

45°

5

125

3/4

0.2

bends

45°

10

250

1/2

0.1

 

 

 

 

 

 

Elbow

90°

 

 

6 3/4

2.0

bend

45°

 

 

1 3/4

0.5

 

 

 

 

 

 

Bend

90°

 

 

2 1/2

0.7

in

 

 

 

 

 

rent

 

 

 

 

 

hose

 

 

 

 

 

 

 

 

 

 

 

Flexible

90°

5

125

1

0.35

piping

90°

10

250

1

0.3

 

90°

20

500

3/4

0.2

 

45°

5

125

3/4

0.2

 

45°

10

250

3/4

0.15

 

45°

20

500

1/2

0.1

 

 

 

 

 

 

23

Image 23
Contents Operating instructions Cooker hoods DA 262 DA 272 DA 292 DA 262 DA 272 i / DA 292 Description of the applianceAir extraction Slide switch for cooktop illumination nSlide switch for the fan m Slide switch for ,,Power selec- tionContents Disposal of your old machine Help to protect our environmentDisposal of packaging Save These Instructions and Review Them Periodically Page Disposal of discarded appliances After cooking OperationGrease filters Cleaning and careCleaning Inserting or changing the active charcoal filters Changing the light tube and/or starterAfter Sales Service For USA only Electrical connectionFor CDN only Technical data Installation 13/16˝ Appliance dimensions Wall unit dimensionsBuilding Depth alignment DA 262 Fitting the light tube coverFitting the cover caps Preparing the lightshield Removing the transit stripsOnly use the template for lightshields Dismantling Fitting the front facia panel / lightshieldConnection Air extractionConnection for extraction Bend Calculation of extraction ductingAir recirculation Page Page