GE PVB94, PVB98, PVB37, PVB67 Use 3-1/4 x 10 duct. It can transition to 6 round, Flexible ducting

Page 10

Installation Preparation

DUCT FITTINGS

Use 3-1/4" x 10" duct. It can transition to 6" round.

Use this chart to compute maximum permissible lengths for duct runs to outdoors.

NOTE: Do not exceed maximum permissible equivalent lengths!

Downdraft Vent: 150' maximum equivalent length

Flexible ducting:

If flexible metal ducting is used, all the equivalent feet values in the table should be doubled. The flexible metal duct should be straight and smooth and extended as much as possible.

DO NOT use flexible plastic ducting.

NOTE: Any home ventilation system, such as a cooktop with a downdraft exhaust mechanism, may interrupt the proper flow of combustion air and exhaust required by fireplaces, gas furnaces, gas water heaters and other naturally vented systems. To minimize the chance of interruption of such naturally vented systems, follow the heating equipment manufacturer’s guidelines and safety standards such as those published by NFPA and ASHRAE.

 

 

 

 

Total

 

 

Equivalent

Quantity

Equivalent

Duct Piece

Dimensions

Length*

Used

Length

 

 

1 ft.

 

 

 

6" round,

(per foot

 

 

 

straight

length)

 

 

 

 

1 ft.

 

 

 

3-1⁄4" x 10"

(per foot

 

 

 

straight

length)

 

 

 

6"

 

 

 

 

90° elbow

12 ft.

 

 

 

6"

 

 

 

 

45° elbow

7 ft.

 

 

 

3-1⁄4" x 10"

 

 

 

 

90° elbow

14 ft.

 

 

 

3-1⁄4" x 10"

 

 

 

 

45° elbow

8 ft.

 

 

 

3-1⁄4" x 10"

 

 

 

 

90° flat elbow

33 ft.

 

 

 

6" round

 

 

 

 

to 3-1⁄4" x 10"

 

 

 

 

transition

2 ft.

 

 

 

3-1⁄4" x 10"

 

 

 

 

round to 6"

 

 

 

 

transition

2 ft.

 

 

 

6" round to

 

 

 

 

3-1⁄4" x 10"

 

 

 

 

transition

 

 

 

 

90° elbow

4 ft.

 

 

 

3-1⁄4" x 10" to 6"

 

 

 

 

round transition

 

 

 

 

90° elbow

4 ft.

 

 

 

6" round

 

 

 

 

wall cap

 

 

 

 

with damper

24 ft.

 

 

 

3-1⁄4" x 10"

 

 

 

 

wall cap

 

 

 

 

with damper

24 ft.

 

 

 

6" round

 

 

 

 

roof cap

33 ft.

 

 

*Actual length of straight duct plus duct fitting

Total Duct Run

 

 

equivalent. Equivalent length of duct pieces is based

 

 

on actual tests conducted by GE Evaluation Engineering

 

 

and reflect requirements for good venting performance

 

 

with any downdraft cooktop.

 

 

10

Image 10
Contents Installation Instructions Read these instructions completely and carefully Safety InformationCompletion Time 1 to 3 hours This appliance must be properly groundedAccessories ContentsProduct Dimensions Design InformationAdvance Planning Ductwork ClearancesElectrical and Gas Locations Cutouts and Clearances Installation PreparationCOOKTOP/DOWNDRAFT Tools and Materials Required ClearancesParts Supplied Remove PackagingElectric Cooktops Power SupplyGas Cooktops Please read carefullyVenting Options Side-to-Side AdjustmentsReinstall blower and mounting plate with original screws Discharge DirectionUse 3-1/4 x 10 duct. It can transition to 6 round Flexible ductingInstall Ductwork Installation InstructionsInstall Downdraft Vent Bracket location for left-side blower dischargeConnect Wire Lead to Control Box Connect Control Switch to Remote HarnessDrill a 1/2-dia. hole into the desired location Plug power cord into properly grounded receptacle Connect PowerCleaning To lower the vent, press the ON/OFF padPage Page 31-10728 10728-31 Notas Notas Instalación de Instrucciones Energía LA ConecteModelos algunos en Control DE Interruptor EL Instale Conductos LOS Instale Longitudes las calcular Instalación la para PreparaciónPermitidas máximas Para tabla esta UtiliceLaterales Ajustes Ventilación DE OpcionesDescarga de Dirección Derecha o izquierda la hacia descarga una cambiar ParaTierra a Energía DE SuministroUn cambiar consumidor del obligación y Espacios Marque y mida comenzar, de Antes Nota 2 MínimoConductos Diseño de InformaciónElectricidad y gas de suministro del Ubicación EspaciosEncimera de mostrador del Requisitos Creativas SolucionesBase gabinete de Requisitos Instalación la comenzar de AntesInstalación de Instrucciones Conductos3344.561.800.1 Seguridad de InformaciónAl llame 1845.444.800.1Instalación de Instrucciones