Balancing the Kitchen Exhaust System

A.To determine the proper dining room air balance:

1.Refer to engineering drawings to determine total exhaust CFM from dining areas. (Exhaust fans, heating and air conditioning units, restrooms, etc.)

2.Determine the total CFM of make-up air supplied to dining area.

3.Subtract #1 from #2 above. If the result is a negative number, a negative pressure is present in the dining area. In this case, kitchen exhaust odors could be drawn from the kitchen to the dining area. Therefore, exhaust or supply air should be adjusted to provide a slight positive pressure in the dining area.

B.To determine proper kitchen air balance:

1.Refer to engineering drawings to determine total exhaust from the kitchen area. (Exhaust hoods, dishwasher hoods, etc.)

2.Determine total CFM of make-up air supplied to kitchen area. (Make-up air hoods, heating and air conditioning units, etc.)

3.Subtract #1 from #2 above. The result should be a negative number. If the result is a positive number, a positive pressure is present in the kitchen area. Kitchen odors could be forced into the dining area. Also, a positively balanced kitchen area can adversely affect the performance of the exhaust hood.

Caution: According to NFPA 96, Ch. 8-3 Replacement Air: Replacement air quantity shall be adequate to prevent negative pressures in the commercial cooking area(s) from exceeding 4.98 kPa (0.02 in. water column).

Testing Hood Air Volume

Baffle Filter Style Hoods

A. Exhaust:

With all the filters in place, determine the total hood exhaust volume with a rotating vane anemometer as follows:

1.All cooking equipment should be on.

2.Measure the velocities

Velocity measurements should be taken at five locations per filter. These must be over a filter slot as in Fig. 21.

x

 

x

H/4

 

 

 

x

 

H

 

 

 

x

 

x

H/2

 

H/4

 

 

 

Fig. 21

 

 

 

16 Proximity Hood

®

Image 16
Contents Installation, Operation and Maintenance Manual Table of Contents Hood Weights Receiving and HandlingHood Installation Overview InstallationRear Filler Panel Installation Instructions Hood Hanging Height End Filler Panel Installation InstructionsContinuous Capture Plenum Hoods Supply Ductwork ExhaustElectrical Connections External Supply Plenum Installation Installation InstructionsInstalling the Back Supply Plenum Hanging the Back Supply PlenumHanging the Hood with Back Supply Plenum Hood Mounting InstructionsFull Enclosure Panels Plate Shelf with Duct Enclosure Panels Passover Shelf with Duct Enclosure Panels Backsplash Panel Installation Instructions Flat Backsplash PanelDuct Collar Installation Fire System InstallationExhaust Air Balancing Baffles Eabb Checking for BalanceTesting Hood Air Volume Baffle Filter Style Hoods Exhaust Balancing the Kitchen Exhaust SystemRotating Vane Anemometer Supply If Applicable Example for Perforated Face Supply185 + 187.0 fpm High Velocity Cartridge Filters Exhaust Example282 fpm 423.0 cfm Volume with a rotating vane anemometer as follows 1042 4012 m3/hr Amerex Wiring Plan View PRMAnsul Wiring Plan View EquipmentOverall Wiring Plan View HoodWiring for Switch Panels Weekly Maintenance Maintenance Daily MaintenancePeriodic Maintenance Proximity Hood Grease Grabber Filter Cleaning Frequent MaintenanceFilter Washing Frequency Guide Equipment Required CyclesTroubleshooting Problem Cold air can be felt by the cook at the hood Replacement Parts Maintenance Log Warranty

PN 458294 specifications

Greenheck Fan PN 458294 is a prominent product in the HVAC industry, designed to deliver high performance, efficiency, and reliability in various applications. This unit is widely recognized for its ability to optimize airflow while minimizing energy consumption, a feature that is becoming increasingly vital in current energy-conscious markets.

One of the key features of the Greenheck Fan PN 458294 is its robust construction. Built with durable materials, this fan is engineered to withstand harsh environmental conditions, making it suitable for both indoor and outdoor installations. The corrosion-resistant finish further enhances its resilience, ensuring a longer lifespan and reduced maintenance costs.

The fan is equipped with advanced aerodynamic designs that improve its airflow performance. This design focus not only maximizes the fan's efficiency but also provides quieter operation, which is a crucial factor in sensitive environments such as offices, schools, and hospitals. The noise reduction technology integrated into the unit helps maintain a comfortable atmosphere while keeping operational disturbances to a minimum.

In terms of technology, the Greenheck Fan PN 458294 features state-of-the-art motor technology that offers variable speed control. This capability allows users to adjust the fan's operation according to specific needs, enhancing energy efficiency while ensuring optimal airflow. The internally mounted motor and belt drive system contribute to reduced vibration and increased stability, further lowering wear and tear over time.

This fan also incorporates innovative control options, allowing for easy integration into existing building management systems. This smart technology enables users to monitor and adjust performance remotely, ensuring maximum efficiency and adaptability to changing operational demands.

Another noteworthy characteristic of the Greenheck Fan PN 458294 is its versatility. It can be utilized in a variety of applications, including industrial ventilation, commercial exhaust, and air supply systems. The wide range of available configurations and accessory options makes it an ideal choice for meeting diverse project requirements.

In conclusion, the Greenheck Fan PN 458294 stands out in the HVAC market due to its combination of robust construction, advanced aerodynamic design, innovative motor technology, and versatile application capabilities. As energy efficiency continues to be a priority in building design, this fan offers a reliable solution for maintaining optimal airflow while minimizing environmental impact.