Table 3-9 DataCORDER Pre-Trip Result Records

 

 

 

Test

TITLE

DATA

No.

 

 

1-0

Heater On

Pass/Fail/Skip Result, Change in current for Phase A, B and C

 

 

 

1-1

Heater Off

Pass/Fail/Skip Result, Change in currents for Phase A, B and C

2-0

Condenser Fan On

Pass/Fail/Skip Result, Water pressure switch (WPS) - Open/Closed,

Change in currents for Phase A, B and C

 

 

2-1

Condenser Fan Off

Pass/Fail/Skip Result, Change in currents for Phase A, B and C

3-0

Low Speed Evaporator Fan

Pass/Fail/Skip Result, Change in currents for Phase A, B and C

On

 

 

3-1

Low Speed Evaporator Fan

Pass/Fail/Skip Result, Change in currents for Phase A, B and C

On

 

 

4-0

High Speed Evaporator Fan

Pass/Fail/Skip Result, Change in currents for Phase A, B and C

On

 

 

4-1

High Speed Evaporator Fan

Pass/Fail/Skip Result, Change in currents for Phase A, B and C

On

 

 

5-0

Supply/Return Probe Test

Pass/Fail/Skip Result, STS, RTS, SRS and RRS

5-1

Secondary Supply Probe Test

Pass/Fail/Skip

 

 

 

5-2

Secondary Return Probe Test

Pass/Fail/Skip

6-0

Discharge Thermistor Test

Pass/Fail/Skip

 

 

 

6-1

Suction Thermistor Test

Pass/Fail/Skip

6-2

Discharge Pressure Sensor

Pass/Fail/Skip

Test

 

 

6-3

Suction Pressure Sensor Test

Pass/Fail/Skip

6-4

Compressor Current Draw

Pass/Fail/Skip

Test

 

 

6-5

Suction Modulation valve Test

Pass/Fail/Skip

 

 

 

6-6

Economizer Valve Test

Pass/Fail/Skip

 

 

 

6-7

Unloader Valve Test

Pass/Fail/Skip

 

 

 

7-0

High Pressure Switch Closed

Pass/Fail/Skip Result, AMBS, DPT or CPT (if equipped)

Input values that component opens

 

 

7-1

High Pressure Switch Open

Pass/Fail/Skip Result, STS, DPT or CPT (if equipped)

Input values that component closes

 

 

8-0

Perishable Mode Heat Test

Pass/Fail/Skip Result, STS, time it takes to heat to 16_C (60_F)

 

 

 

8-1

Perishable Mode Pull Down

Pass/Fail/Skip Result, STS, time it takes to pull down to 0_C (32_F)

Test

 

 

8-2

Perishable Mode Maintain

Pass/Fail/Skip Result, Averaged DataCORDER supply temperature

Test

(SRS) over last recording interval.

 

9-0

Defrost Test

Pass/Fail/Skip Result, DTS reading at end of test, line voltage, line

frequency, time in defrost.

 

 

10-0

Frozen Mode Heat Test

Pass/Fail/Skip Result, STS, time unit is in heat.

 

 

 

10-1

Frozen Mode Pull Down Test

Pass/Fail/Skip Result, STS, time to pull down unit to -17.8_C (0_F).

 

 

 

10-2

Frozen Mode Maintain Test

Pass/Fail/Skip Result, Averaged DataCORDER return temperature

(RRS) over last recording interval.

 

 

T-309

3-26

Image 51
Contents Service Model Safety Summary 309 Safety-2 Safety-3 309 Table of Contents Table of Contents Check Controller Function Codes Connect Remote MonitoringPrecheck Procedure Checking The Stepper valve Valve ReplacementEvaporator Coil Replacement Evaporator Heater Replacement Replacing The Evaporator Fan AssemblyElectrical Wiring Schematic Refrigeration Circuit Schematic Economized Operation Refrigeration Circuit Schematic Standard OperationList of Tables DataCORDER Configuration VariablesUnit is fitted with a scroll compressor Section IntroductionManual, T-300 Section Description Evaporator Section Compressor Section Condenser Section Communications interface module For further information Module which allow communication with a masterOil level range, with the compressor off Model RSH105 Weight Dry 46.5 kg 103 lbTemperature Approved Oil Mobil ST32 Oil Charge 2957 ml 100 ouncesElectrical Data Safety and Protective Devices Refrigeration Circuit 2.5.1 Standard Operation Standard Operation with Receiver Refrigeration Circuit Schematic -- Economized Operation Section Microprocessor Temperature Control SystemKEY Function Controller Software Modes of Operation Perishable Mode -- Economy Controller Alarms Unit PRE-TRIP Diagnostics DCF02=6 Thermistor inputssupply & returnDCF02=2 DCF02=5 Usda thermistor inputsRaw Data Report for ABC1234567 Standard Configuration Download ReportLogging Interval dCF03 DataCORDER may be powered up in any one of four waysDataView DataCORDER Alarms SnAP CnF11 Defrost Off Selection NoOFFStd, Full CnF33 Snap Freeze OptionDisplay Only Functions Plicable with frozen set points Defrost temperature sensor reading is displayedPossibly delaying a needed defrost cycle Sensor ReadingController Function Codes Sheet 3 Controller Alarm Indications Sheet 1 Controller Alarm Indications Sheet 2 Controller Alarm Indications Sheet 3 Memory failure Error DescriptionOnds Draw test is done after 15 secondsP1-1 Draw test is done after 10 secondsCrease, the test fails Supply is comparedTest fails P6-2 Requirements Control temperature must be at least 15.6C 60F Pressure switch is open or the condenser fan switch is open Timer is started Denser fan is started and a 60 second timer is startedRequirements Control temperature must be at least 7.2C 45F Set point, the test proceeds to testBy starting P10-0 over Inapplicable Functions Display Title Data 10 DataCORDER Alarm Indications 69NT Fresh AIR Makeup OperationTo start a pre-trip test, do the following Will be displayedWill be displayed Pull Down Falling Rising Controller Operation -- Perishable ModeController Operation -- Frozen Mode Frozen Mode Defrost Section Troubleshooting Unit will not heat or has insuffi Bent motor shaft Will not initiate defrostSuperheat Unit reads abnormal currents Current sensor wiring Check Valve Frontseated Backseated Section ServiceCompressor in a deep vacuum, internal dam- age will result Refrigerant Leak Checking Remove all refrigerant using a refrigerant recovery system Refrigerant Charge Compressor Upper Mounting Compressor OIL Level Condenser FAN and Motor Assembly Two expansion valves are used, the evaporator Wrapped with Insulating compound. SeeRemoving the Expansion Valve Check superheat refer to step Cleaned regularly. The preferred cleaning fluid is freshIf applicable, braze the equalizer connection to Equalizer line14. Unloader Solenoid Valve Start unit and check operationEvaporator FAN Motor Capacitors Valve Override Controls Precheck Procedure TP1 Mounting Stud Type Cut one replacement sensor wire opposite color Cut wires 5 cm 2 inches from shoulder of defecCut one wire of existing cable 40 mm 1-1/2 inch Shorter than the other wireMaintenance of Painted Surfaces 23 Door Hinge Repair Crack, Chip & Hole Repair Kit 24. Insert Location In-lbs Ft-lbs 13.99 18.86 In-lbs #10 Ft-lbs 12.72 17.1414.6 49.4 37.08 12.3 41.6 31.25 32.8 24.64 22.7 17.00 11.9 Section Electrical Wiring Schematic Schematic Diagram Wiring Diagram Sheet 1 Wiring Diagram Sheet 2 Index 309 Index-2