Carrier 69NT20-531-300 manual Controller Alarms

Page 31

1.Bulb mode code Cd35 is set to “Nor.”

2.Dehumidification code Cd33 is set to “Off.”

3.The user changes the set point to one that is in the frozen range.

When bulb mode is disabled by any of the above, the evaporator fan operation for dehumidification reverts to “alt” and the DTS termination setting resets to the value determined by controller configuration variable CnF41.

3.3.10 Temperature Control -- Frozen Mode

With configuration variable CnF26 (Heat Lockout Temperature) set to -10_C the frozen mode of operation is active with set points at or below -10_C (+14_F). With the variable set to -5_C, the frozen mode is active at or below -5_C (+23_F).

When in the frozen mode the controller maintains the return air temperature at set point, the RETURN indicator light will be illuminated on the display module and the default reading on the display window will be the return air probe reading.

When the return air temperature enters the in-range temperature tolerance as selected at function code Cd30, the in-range light will energize.

3.3.11 Frozen Mode -- Conventional

Frozen range cargos are not sensitive to minor temperature changes. The method of temperature control employed in this range takes advantage of this fact to greatly improve the energy efficiency of the unit. Temperature control in the frozen range is accomplished by cycling the compressor on and off as the load demand requires.

When cooling from a temperature that is more than 2.5_C (4.5_F) above set point, the system will be in the frozen pull down mode. It will transition to economized operation with a target SMV position of 100% open. However, pressure and current limit functions may restrict the valve, if either exceeds the preset value.

Once set point is reached, the unit will transition to the frozen steady state mode. (Economized operation with maximum allowed suction modulating valve opening.)

When temperature drops to set point minus 0.2_C and the compressor has run for at least five minutes, the unit will transition to the frozen idle mode. The compressor is turned off and the evaporator fans continue to run to circulate air throughout the container. If temperature rises above set point +0.2_C, the unit will transition back to the frozen steady state mode.

If the temperature drops 10_C below set point, the unit will transition to the frozen “heating” mode. In the frozen heating mode the evaporator fans are brought to high speed. The unit will transition back to the frozen steady state mode when the temperature rises back to the transition point.

3.3.12 Frozen Mode - Economy

In order to activate economy frozen mode operation, a frozen set point temperature must be selected. The economy mode is active when function code Cd34 is set

to “ON”. When economy mode frozen is active, the system will perform normal frozen mode operations except that the entire refrigeration system, excluding the controller, will be turned off when the control temperature is less than or equal to the set point - 2_C. After an off-cycle period of 60 minutes, the unit will turn on high speed evaporator fans for three minutes, and then check the control temperature. If the control temperature is greater than or equal to the set point + 0.2_C., the unit will restart the refrigeration system and continue to cool until the previously mentioned off-cycle temperature criteria are met. If the control temperature is less than the set point + 0.2_C, the unit will turn off the evaporator fans and restart another 60 minute off-cycle.

3.4 CONTROLLER ALARMS

Alarm display is an independent controller software function. If an operating parameter is outside of expected range or a components does not return the correct signals back to the controller an alarm is generated. A listing of the alarms is provided in Table 3-6.

The alarm philosophy balances the protection of the refrigeration unit and that of the refrigerated cargo. The action taken when an error is detected always considers the survival of the cargo. Rechecks are made to confirm that an error actually exists.

Some alarms requiring compressor shutdown have time delays before and after to try to keep the compressor on line. An example is alarm code “LO”, (low main voltage), when a voltage drop of over 25% occurs, an indication is given on the display, but the unit will continue to run.

When an Alarm Occurs:

a. The red alarm light will illuminate for alarm code numbers 13, 17, 20, 21, 22, 23, 24, 25, 26, and 27.

b. If a detectable problem is found to exist, its alarm code will be alternately displayed with the set point on the left display.

c.The user should scroll through the alarm list to deter- mine what alarms exist or have existed. Alarms must be diagnosed and corrected before the Alarm List can be cleared.

To Display Alarm Codes :

a. While in the Default Display mode, press the ALARM LIST key. This accesses the Alarm List Dis- play Mode, which displays any alarms archived in the Alarm Queue.

b. The alarm queue stores up to 16 alarms in the se- quence in which they occurred. The user may scroll through the list by depressing an ARROW key.

c. The left display will show “AL##,” where ## is the alarm number sequentially in the queue.

d. The right display will show the actual alarm code. “AA##” will display for an active alarm, where “##” is the alarm code. Or “IA##” will display for an inac- tive alarm. See Table 3-6.

T-309

3-6

Image 31
Contents Service Model Safety Summary 309 Safety-2 Safety-3 309 Table of Contents Table of Contents Check Controller Function Codes Connect Remote MonitoringPrecheck Procedure Checking The Stepper valve Valve ReplacementEvaporator Coil Replacement Evaporator Heater Replacement Replacing The Evaporator Fan AssemblyElectrical Wiring Schematic Refrigeration Circuit Schematic Economized Operation Refrigeration Circuit Schematic Standard OperationList of Tables DataCORDER Configuration VariablesUnit is fitted with a scroll compressor Section IntroductionManual, T-300 Section Description Evaporator Section Compressor Section Condenser Section Communications interface module For further information Module which allow communication with a masterOil level range, with the compressor off Model RSH105 Weight Dry 46.5 kg 103 lbTemperature Approved Oil Mobil ST32 Oil Charge 2957 ml 100 ouncesElectrical Data Safety and Protective Devices Refrigeration Circuit 2.5.1 Standard Operation Standard Operation with Receiver Refrigeration Circuit Schematic -- Economized Operation Section Microprocessor Temperature Control SystemKEY Function Controller Software Modes of Operation Perishable Mode -- Economy Controller Alarms Unit PRE-TRIP Diagnostics DCF02=6 Thermistor inputssupply & returnDCF02=2 DCF02=5 Usda thermistor inputsRaw Data Report for ABC1234567 Standard Configuration Download ReportLogging Interval dCF03 DataCORDER may be powered up in any one of four waysDataView DataCORDER Alarms SnAP CnF11 Defrost Off Selection NoOFFStd, Full CnF33 Snap Freeze OptionDisplay Only Functions Plicable with frozen set points Defrost temperature sensor reading is displayedPossibly delaying a needed defrost cycle Sensor ReadingController Function Codes Sheet 3 Controller Alarm Indications Sheet 1 Controller Alarm Indications Sheet 2 Controller Alarm Indications Sheet 3 Memory failure Error DescriptionOnds Draw test is done after 15 secondsP1-1 Draw test is done after 10 secondsCrease, the test fails Supply is comparedTest fails P6-2Requirements Control temperature must be at least 15.6C 60F Pressure switch is open or the condenser fan switch is openTimer is started Denser fan is started and a 60 second timer is startedSet point, the test proceeds to test Requirements Control temperature must be at least 7.2C 45FBy starting P10-0 over Inapplicable Functions Display Title Data 10 DataCORDER Alarm Indications 69NT Fresh AIR Makeup OperationTo start a pre-trip test, do the following Will be displayedWill be displayed Pull Down Falling Rising Controller Operation -- Perishable ModeController Operation -- Frozen Mode Frozen Mode Defrost Section Troubleshooting Unit will not heat or has insuffi Bent motor shaft Will not initiate defrostSuperheat Unit reads abnormal currents Current sensor wiring Check Valve Frontseated Backseated Section ServiceCompressor in a deep vacuum, internal dam- age will result Refrigerant Leak Checking Remove all refrigerant using a refrigerant recovery system Refrigerant Charge Compressor Upper Mounting Compressor OIL Level Condenser FAN and Motor Assembly Wrapped with Insulating compound. See Two expansion valves are used, the evaporatorRemoving the Expansion Valve Check superheat refer to step Cleaned regularly. The preferred cleaning fluid is freshIf applicable, braze the equalizer connection to Equalizer line14. Unloader Solenoid Valve Start unit and check operationEvaporator FAN Motor Capacitors Valve Override Controls Precheck Procedure TP1 Mounting Stud Type Cut one replacement sensor wire opposite color Cut wires 5 cm 2 inches from shoulder of defecCut one wire of existing cable 40 mm 1-1/2 inch Shorter than the other wireMaintenance of Painted Surfaces 23 Door Hinge Repair Crack, Chip & Hole Repair Kit 24. Insert Location In-lbs Ft-lbs 13.99 18.86 In-lbs #10 Ft-lbs 12.72 17.1414.6 49.4 37.08 12.3 41.6 31.25 32.8 24.64 22.7 17.00 11.9 Section Electrical Wiring Schematic Schematic Diagram Wiring Diagram Sheet 1 Wiring Diagram Sheet 2 Index 309 Index-2

69NT20-531-300 specifications

The Carrier 69NT20-531-300 is a cutting-edge rooftop unit designed to meet the demanding requirements of commercial heating and cooling applications. This model embodies Carrier’s commitment to energy efficiency, reliability, and advanced technological features that enhance indoor comfort while minimizing operational costs.

One of the standout features of the Carrier 69NT20-531-300 is its high energy efficiency. It is equipped with advanced compressor technology that optimizes performance while reducing energy consumption. This ensures that businesses can maintain a comfortable indoor climate without incurring exorbitant utility bills. With a high Seasonal Energy Efficiency Ratio (SEER) and Energy Efficiency Ratio (EER), users can expect not only enhanced comfort but also significant cost savings over time.

The cooling capabilities of the 69NT20-531-300 are complemented by its robust heating options. This unit utilizes a gas heat exchanger, ensuring quick and even heating throughout the space. The combination of cooling and heating capabilities in one compact unit makes it a versatile choice for various applications, including retail spaces, offices, and warehouses.

In addition to its impressive performance specifications, the Carrier 69NT20-531-300 incorporates innovative technologies that further enhance its functionality. The unit comes with advanced controls, allowing for precise temperature regulation and zoning capabilities. This ensures that different areas of a building can maintain their desired temperatures based on usage, improving overall energy efficiency.

Durability is another hallmark of the Carrier 69NT20-531-300. The unit is constructed with high-quality materials and features a weather-proof cabinet that protects it from the elements, ensuring long-term reliability even in harsh conditions. Furthermore, its modular design simplifies maintenance, making it easy for technicians to access critical components.

The 69NT20-531-300 is also designed with low noise operation in mind. It employs sound-dampening technology to ensure that operations are quiet, making it an ideal choice for locations where noise reduction is a priority, such as schools or healthcare facilities.

Overall, the Carrier 69NT20-531-300 stands out as a premier choice for businesses looking for an efficient, reliable, and feature-rich rooftop HVAC unit. Its blend of energy efficiency, advanced technology, and durability positions it as a leader in commercial heating and cooling solutions, making it a valuable investment for any commercial property.