Carrier 69NT20-531-300 manual Evaporator FAN Motor Capacitors

Page 76

the refrigeration unit into the container. The fan motor bearings are factory lubricated and do not require additional grease.

6.17.1Replacing The Evaporator Fan Assembly

WARNING

Always turn OFF the unit circuit breakers (CB-1 & CB-2) and disconnect main power supply before working on moving parts.

a. Remove upper access panel (see Figure 2-2) by removing mounting bolts and T.I.R. locking device. Reach inside of unit and remove the Ty-Rap securing the wire harness loop. Then unplug the connector by twisting to unlock and pulling to separate. NOTE: It may be easier to unplug the connector with the motor assembly partially pulled out (after step b).

6.18 EVAPORATOR FAN MOTOR CAPACITORS

The evaporator fan motors are of the permanent-split capacitor type. The motor is equipped with one capacitor used in the high speed circuit and another capacitor used for the low speed circuit.

6.18.1 When To Check For A Defective Capacitor

a.Fan motor will not change speed. For example: in the conventional perishable mode, the motors should run in high speed. In the economy perishable mode they should switch speeds and in the frozen mode, the mo- tors should run in low speed.

NOTE

The evaporator fan motors will always start in high speed.

b. Remove the four mounting bolts that secure the mo- tor-fan assembly to the unit.

c. Slide the fan assembly out from the unit and place it on a sturdy work surface.

d. Remove the motor and fan from the assembly. e. Replace the motor.

f. Lubricate the fan motor shaft with a graphite-oil solution (Never-Seez) and apply thread sealer (Loc- tite H, brown in color) to the two fan set screws. Install fan on the motor shaft, so that the coupling sur- face will be even with the end of the motor shaft.

g. Install the fan assembly in reverse order of removal. Apply power momentarily to check for proper fan rotation (refer to paragraph 2.3). If the fan spins back- wards, than motor wiring or motor is defective.

Replace access panel making sure that panel does not leak. Lock-wire the T.I.R. locking device(s).

4

3

 

 

5

2

 

 

 

6

 

 

 

1

 

 

 

8

 

 

 

9

7

1.

Bracket

6.

Cap Screw, Hxhd

2.

Flat washer, 3/8

 

5/16-18 x 1.25

3.

Bolt, 3/8-16 x 1.00

7.

Fan

4.

Locknut, 5/16-18

8.

Shim

5.

Flat washer, 5/16

9.

Evaporator Motor

 

Figure 6-16. Evaporator Fan Assembly

T-309

 

6-12

b.Motor running in wrong direction (after checking for correct wiring application).

c.Motor will not start, and IP-EM’s are not open.

6.18.2 Removing The Capacitor

WARNING

Make sure power to the unit is OFF and power plug disconnected before removing capacitor(s).

The capacitors are located on the motor and above the evaporator fan deck they may be removed by two methods:

1If container is empty, open upper rear panel of the unit. The capacitor may be serviced after disconnect- ing power plug.

2If container is full, turn the unit power OFF and dis- connect power plug. Remove the evaporator fan motor access panel. (See see Figure 2-1). For removal of the evaporator fan assembly, refer to sec- tion 6.17.

WARNING

With power OFF discharge the capacitor be- fore disconnecting the circuit wiring.

6.18.3 Checking The Capacitor

If the capacitor is suspected of malfunction, you may choose to simply replace it. Direct replacement requires a capacitor of the same value. Two methods for checking capacitor function are:

1. Volt-ohmmeter set on RX 10,000 ohms.

Connect ohmmeter leads across the capacitor terminals and observe the meter needle. If the capacitor is good, the needle will make a rapid swing toward zero resistance and then gradually swing back toward a very high resistance reading.

If the capacitor has failed open, the ohmmeter needle will not move when the meter probes touch the terminals. If the capacitor is shorted, the needle will swing to zero resistance position and stay there.

2. Capacitor analyzer:

The function of the analyzer is to read the microfarad value of a capacitor and to detect insulation breakdown

Image 76
Contents Service Model Safety Summary 309 Safety-2 Safety-3 309 Table of Contents Table of Contents Connect Remote Monitoring Check Controller Function CodesValve Replacement Evaporator Coil Replacement Evaporator Heater ReplacementReplacing The Evaporator Fan Assembly Precheck Procedure Checking The Stepper valveElectrical Wiring Schematic Refrigeration Circuit Schematic Standard Operation Refrigeration Circuit Schematic Economized OperationDataCORDER Configuration Variables List of TablesSection Introduction Unit is fitted with a scroll compressorManual, T-300 Section Description Evaporator Section Compressor Section Condenser Section Module which allow communication with a master Communications interface module For further informationModel RSH105 Weight Dry 46.5 kg 103 lb TemperatureApproved Oil Mobil ST32 Oil Charge 2957 ml 100 ounces Oil level range, with the compressor offElectrical Data Safety and Protective Devices Refrigeration Circuit 2.5.1 Standard Operation Standard Operation with Receiver Refrigeration Circuit Schematic -- Economized Operation Temperature Control System Section MicroprocessorKEY Function Controller Software Modes of Operation Perishable Mode -- Economy Controller Alarms Unit PRE-TRIP Diagnostics Thermistor inputssupply & return DCF02=2DCF02=5 Usda thermistor inputs DCF02=6Standard Configuration Download Report Raw Data Report for ABC1234567DataCORDER may be powered up in any one of four ways Logging Interval dCF03DataView DataCORDER Alarms CnF11 Defrost Off Selection NoOFF Std, FullCnF33 Snap Freeze Option SnAPDisplay Only Functions Defrost temperature sensor reading is displayed Possibly delaying a needed defrost cycleSensor Reading Plicable with frozen set pointsController Function Codes Sheet 3 Controller Alarm Indications Sheet 1 Controller Alarm Indications Sheet 2 Controller Alarm Indications Sheet 3 Error Description Memory failureDraw test is done after 15 seconds P1-1Draw test is done after 10 seconds OndsSupply is compared Test failsP6-2 Crease, the test failsPressure switch is open or the condenser fan switch is open Timer is startedDenser fan is started and a 60 second timer is started Requirements Control temperature must be at least 15.6C 60FSet point, the test proceeds to test Requirements Control temperature must be at least 7.2C 45FBy starting P10-0 over Inapplicable Functions Display Title Data 10 DataCORDER Alarm Indications Operation 69NT Fresh AIR MakeupWill be displayed To start a pre-trip test, do the followingWill be displayed Controller Operation -- Perishable Mode Pull Down Falling RisingController Operation -- Frozen Mode Frozen Mode Defrost Section Troubleshooting Unit will not heat or has insuffi Will not initiate defrost Bent motor shaftSuperheat Unit reads abnormal currents Current sensor wiring Check Section Service Valve Frontseated BackseatedCompressor in a deep vacuum, internal dam- age will result Refrigerant Leak Checking Remove all refrigerant using a refrigerant recovery system Refrigerant Charge Compressor Upper Mounting Compressor OIL Level Condenser FAN and Motor Assembly Wrapped with Insulating compound. See Two expansion valves are used, the evaporatorRemoving the Expansion Valve Cleaned regularly. The preferred cleaning fluid is fresh If applicable, braze the equalizer connection toEqualizer line Check superheat refer to stepStart unit and check operation 14. Unloader Solenoid ValveEvaporator FAN Motor Capacitors Valve Override Controls Precheck Procedure TP1 Mounting Stud Type Cut wires 5 cm 2 inches from shoulder of defec Cut one wire of existing cable 40 mm 1-1/2 inchShorter than the other wire Cut one replacement sensor wire opposite colorMaintenance of Painted Surfaces 23 Door Hinge Repair Crack, Chip & Hole Repair Kit 24. Insert Location In-lbs #10 Ft-lbs 12.72 17.14 In-lbs Ft-lbs 13.99 18.8614.6 49.4 37.08 12.3 41.6 31.25 32.8 24.64 22.7 17.00 11.9 Section Electrical Wiring Schematic Schematic Diagram Wiring Diagram Sheet 1 Wiring Diagram Sheet 2 Index 309 Index-2

69NT20-531-300 specifications

The Carrier 69NT20-531-300 is a cutting-edge rooftop unit designed to meet the demanding requirements of commercial heating and cooling applications. This model embodies Carrier’s commitment to energy efficiency, reliability, and advanced technological features that enhance indoor comfort while minimizing operational costs.

One of the standout features of the Carrier 69NT20-531-300 is its high energy efficiency. It is equipped with advanced compressor technology that optimizes performance while reducing energy consumption. This ensures that businesses can maintain a comfortable indoor climate without incurring exorbitant utility bills. With a high Seasonal Energy Efficiency Ratio (SEER) and Energy Efficiency Ratio (EER), users can expect not only enhanced comfort but also significant cost savings over time.

The cooling capabilities of the 69NT20-531-300 are complemented by its robust heating options. This unit utilizes a gas heat exchanger, ensuring quick and even heating throughout the space. The combination of cooling and heating capabilities in one compact unit makes it a versatile choice for various applications, including retail spaces, offices, and warehouses.

In addition to its impressive performance specifications, the Carrier 69NT20-531-300 incorporates innovative technologies that further enhance its functionality. The unit comes with advanced controls, allowing for precise temperature regulation and zoning capabilities. This ensures that different areas of a building can maintain their desired temperatures based on usage, improving overall energy efficiency.

Durability is another hallmark of the Carrier 69NT20-531-300. The unit is constructed with high-quality materials and features a weather-proof cabinet that protects it from the elements, ensuring long-term reliability even in harsh conditions. Furthermore, its modular design simplifies maintenance, making it easy for technicians to access critical components.

The 69NT20-531-300 is also designed with low noise operation in mind. It employs sound-dampening technology to ensure that operations are quiet, making it an ideal choice for locations where noise reduction is a priority, such as schools or healthcare facilities.

Overall, the Carrier 69NT20-531-300 stands out as a premier choice for businesses looking for an efficient, reliable, and feature-rich rooftop HVAC unit. Its blend of energy efficiency, advanced technology, and durability positions it as a leader in commercial heating and cooling solutions, making it a valuable investment for any commercial property.