noid valve changing from economized operation to unloaded operation. (As shown in Figure
d.The controller monitors the supply air. Once the sup- ply air falls below set point the controller periodically records the supply air temperature, set point and time. A calculation is then performed to determine temper- ature drift from set point over time.
e.If the calculation determines cooling is no longer re- quired, contacts TD and TN are opened to
f.The evaporator fan motors continue to run to circulate air throughout the container. The
g.If the supply air temperature increases to 0.2_C (0.4_F) above set point and the three minute off time has elapsed, relays TD, TU and TN are energized to restart the compressor and condenser fan motors in unloaded operation. The cool light is also illumi- nated.
ENERGIZED |
| |
CONTROL TRANSFORMER | ||
FOR FULL DIAGRAM AND | ||
| ||
LEGEND, SEE SECTION 7 |
|
POWER TO
CONTROLLER
T6 | PB |
| PA |
TD | T6 | PA | PB |
SIGNAL TO |
|
|
|
CONTROLLER | TU | USV |
|
TS |
|
| ESV |
NOTE: HIGH SPEED EVAPORATOR FAN SHOWN. FOR LOW SPEED CONTACT TE IS
Figure 4-5 Perishable Mode Heating
4.9.3Sequence Of Operation -- Perishable Mode Heating
a.If the air temperature decreases 0.5_C (0.9_F) below set point, the system enters the heating mode. (See Figure
b.When the temperature rises to 0.2_C (0.4_F) above set point, contact TH opens to
rator fans continue to run to circulate air throughout the container.
c. A safety heater termination thermostat (HTT), at- tached to an evaporator coil support, will open the heating circuit if overheating occurs.
4.9.4Sequence Of operation
a. With supply air temperature above set point and de- creasing, the unit will transition to economized cool- ing with the condenser fan motor (CF), compressor motor (CH), economizer solenoid valve (ESV), low speed evaporator fan motors (ES) energized and the COOL light illuminated. (See Figure
b.When the air temperature decreases to a predeter- mined tolerance above set point, the
illuminated. |
|
|
| |
ENERGIZED |
|
|
| |
CONTROL TRANSFORMER | ||||
FOR FULL DIAGRAM AND | ||||
|
|
| ||
LEGEND, SEE SECTION 7 |
|
|
| |
POWER TO |
|
|
| |
CONTROLLER |
|
|
| |
T6 | PB |
| PA | |
TD | T6 | PA | PB | |
SIGNAL TO |
|
|
| |
CONTROLLER | TU | USV |
| |
TS |
|
| ESV |
Figure 4-6 Frozen Mode
c. When the return air temperature decreases to 0.2_C (0.4_F) below set point, contacts TD, TS and TN are opened to
d. The evaporator fan motors continue to run in low speed to circulate air throughout the container. The
e.When return air temperature is 10_C (18_F) or more below set point, the evaporator fans are brought to high speed.
f.When the return air temperature increases to 0.2_C (0.4_F) above set point and the three minute off time has elapsed, relays TD, TS and TN are energizes to restart the compressor and condenser fan motors. The cool light is illuminated.
4.9.5 Sequence Of Operation
The defrost cycle may consist of up to three distinct operations. The first is