hussman SCSS-SL Joint Trim, Waste Outlet and P-TRAP, Corner Wedges, Installing Condensate Drain

Page 6

IGSSB-SCSS / SCSS-SL-0108

Installation (cont’d.)

CORNER WEDGES

Corner wedges are attached via front and rear camlocks. Use a 7mm Allen wrench to turn the locks. Do not over- tighten! Join the top by using a joint bracket (included in joint kit) with 3/8" bolts.

JOINT TRIM

After cases have been leveled and joined, and refrigera- tion, electrical, and wasted piping work completed, install the splashguards. Fasten along the top edge, or center, with #10 X 3/3" sheet metal screws.

DO NOT SEAL JOINT TRIM TO FLOOR!

Plumbing

WASTE OUTLET AND P-TRAP

The waste outlet is located off the center of the case on one side allowing drip piping to be run lengthwise under the fixture.

A 3/4" P-trap and threaded adapter are supplied with each fixture.The P-trap must be installed to prevent air leakage and insect entrance into the fixture.

NOTE: PVC-DWV solvent cement is recommended. Follow Hussmann’s instructions.

INSTALLING CONDENSATE DRAIN

Poorly or improperly installed condensate drains can se- riously interfere with the operation of this refrigerator, and result in costly maintenance and product losses. Please follow the recommendations listed below when installing condensate drains to insure a proper installation:

1.Never use pipe for condensate drains smaller than the nominal diameter of the pipe or P-trap supplied with the case.

2.When connecting condensate drains, the P-trap must be used as part of the condensate drain to prevent air leakage or insect entrance. Store plumb- ing system floor drains should be at least 14" off the center of the case to allow use of the P-trap pipe section. Never use two water seals in series in any one line. Double P-traps in series will cause a lock and prevent draining.

3.Always provide as much down hill slope (“fall”) as possible; 1/8" per foot is the preferred minimum. PVC pipe, when used, must be supported to main- tain the 1/8" pitch and to prevent warping.

4.Avoid long runs of condensate drains. Long runs make it impossible to provide the “fall” necessary for good drainage.

5.Provide a suitable air break between the flood rim of the floor drain and outlet of condensate drain. 1" is ideal.

6.Prevent condensate drains from freezing:

a.Do not install condensate drains in contact with non-insulated suction lines. Suction lines should be insulated with a nonabsorbent insulation material such as Armstrong’s Armaflex.

b.Where condensate drains are located in dead air spaces (between refrigerators or between a refrigerator and a wall), provide means to prevent freezing.The water seal should be insulated to prevent condensation.

Waste Outlet

 

 

Nipple

Inside Case

 

 

 

(All Models)

 

 

Coupling

 

 

90°

 

 

Remote

 

 

 

Air Gap

 

Refrigeration

 

 

Only!

 

 

 

6

Image 6
Contents Service Bakery REVModel Descriptions ApplicationShortages Hussmann Chino Product ControlSCSS-SL Leveling Do not USE PermagumWaste Outlet and P-TRAP Installing Condensate DrainJoint Trim Corner WedgesLinesthrough Merchandisersthatare Condensing Unit Installation Requirements Stat LocationPiping Wiring Color Code Ashrae Color CodeRear CLOSE-OFF Panel EKC 201 Controllers Quick guideController application setting parameters Eration Case CleaningStocking Important StepsEvaporator pan must be monitored for NON-GLARE GlassPlexiglass & Acrylic Care Tips & Troubleshooting Before calling for service, check the followingReplacing Fluorescent Lamps Electrical Schematics Controls lines W8100002mnl Controls lines Appendix B. Application Recommendations Refrigerated Appendix A. Temperature Guidelines RefrigeratedType Typical Entering Refrigerator AIR Temperature Appendix C. Field Recommendations RefrigeratedAppendix D. Recommendations to User Refrigerated Appendices, Cont’dAppendices, Cont’d IGSSB-SCSS / SCSS-SL-0108 Limited Warranty Model Serial Number