Goodman Mfg GHS8 General Furnace Layout, GAS Piping Connections General, Upflow Installations

Page 19

This unit is configured for natural gas. The appropriate manufacturer’s propane gas conversion kit, must be applied for propane gas installations. Refer to the “Propane Gas and/or High Altitude Installations” section for details.

Contact your distributor for a tabular listing of appropriate manufacturer’s kits for propane gas and/or high altitude installations. The indicated kits must be used to insure safe and proper furnace operation. All conversions must be performed by a qualified installer, or service agency.

GAS PIPING CONNECTIONS

GENERAL

CAUTION

TO AVOID POSSIBLE UNSATISFACTORY OPERATION OR EQUIPMENT DAMAGE DUE TO UNDERFIRING OF EQUIPMENT, USE THE PROPER SIZE OF NATURAL/PROPANE GAS PIPING NEEDED WHEN RUNNING PIPE FROM THE METER/TANK TO THE FURNACE.

When sizing a trunk line, be sure to include all appliances which will operate simultaneously when sizing a trunk line.

The gas piping supplying the furnace must be properly sized based on the gas flow required, specific gravity of the gas, and length of the run. The gas line installation must comply with local codes, or in their absence, with the latest edition of the National Fuel Gas Code, NFPA 54/ANSI Z223.1.

Natural Gas Capacity of Pipe

In Cubic Feet of Gas Per Hour (CFH)

Length of

 

Nominal Black Pipe Size

 

Pipe in Feet

1/2"

3/4"

1"

1 1/4"

1 1/2"

 

10

132

278

520

1050

1600

 

20

92

190

350

730

1100

 

30

73

152

285

590

980

 

40

63

130

245

500

760

 

50

56

115

215

440

670

 

60

50

105

195

400

610

 

70

46

96

180

370

560

 

80

43

90

170

350

530

 

90

40

84

160

320

490

100

38

79

150

305

460

(Pressure 0.5 psig or less and pressure drop of 0.3" W.C.; Based on

 

0.60 Specific Gravity Gas)

 

 

 

 

 

CFH =

BTUH Furnace Input

 

 

 

 

 

 

 

 

 

 

 

 

 

Heating Value of Gas (BTU/Cubic Foot)

 

 

 

 

 

Use two pipe wrenches when making connection to the gas valve to keep it from turning. The orientation of the gas valve on the manifold must be maintained as shipped from the factory.

Install a manual shutoff valve between the gas meter and unit within six feet of the unit. If a union is installed, the union must be downstream of the manual shutoff valve, between the shutoff valve and the furnace.

Tighten all joints securely.

Connect the furnace to the building piping by one of the following methods:

Rigid metallic pipe and fittings.

Semi-rigid metallic tubing and metallic fittings.

Aluminum alloy tubing must not be used in exterior locations.

Use listed gas appliance connectors in accordance with

their instructions. Connectors must be fully in the same room as the furnace.

Protect connectors and semi-rigid tubing against

physical and thermal damage when installed. Ensure aluminum-alloy tubing and connectors are coated to protect against external corrosion when in contact with masonry, plaster, or insulation, or subjected to repeated wetting by liquids such as water (except rain water), detergents, or sewage.

Location of Manual Valve

(Installed Ahead of Ground

Joint Pipe Union)

Height Required

By Local Code

Ground Joint Pipe Union

To Be Installed Ahead Of

Gas Valve

Drip Leg

 

 

 

 

 

 

 

 

``

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Reducing Coupling 1/2" x 1/8" with 1/8" Pipe Plug To Measure Line Gas Pressure

To connect the furnace to the building’s gas piping, the installer must supply a ground joint union, drip leg, manual shutoff valve, and line and fittings to connect to gas valve. In some cases, the installer may also need to supply a transition piece from 1/2" pipe to a larger pipe size.

The following stipulations apply when connecting gas piping.

Use black iron or steel pipe and fittings for the building piping.

Use pipe joint compound on male threads only. Pipe joint compound must be resistant to the action of the fuel used.

Use ground joint unions.

Install a drip leg to trap dirt and moisture before it can enter the gas valve. The drip leg must be a minimum of three inches long.

Install a 1/8" NPT pipe plug fitting, accessible for test gage connection, immediately upstream of the gas supply connection to the furnace.

General Furnace Layout

UPFLOW INSTALLATIONS

When the gas piping enters through the right side of the furnace, the installer must supply the following fittings (starting from the gas valve):

90 degree elbows (2).

Close nipple.

Straight pipe to reach the exterior of the furnace .

A ground joint union, drip leg, and manual shutoff valve must also be supplied by the installer. In some cases, the installer may also need to supply a transition piece from 1/2" to another pipe size.

When the gas piping enters through the left side of the furnace, the installer must supply the following fittings (starting from the gas valve):

Straight pipe to reach the exterior of the furnace.

A ground joint union, drip leg, and manual shutoff valve must also be supplied by the installer. In some cases, the installer may also need to supply a transition piece from 1/ 2 inch to another pipe size.

IO-242C

19

05/05

 

 

Image 19
Contents Installation & Operating Table of Contents XVI. Maintenance XII. Start-up Procedure and AdjustmentXIV. Safety Circuit Description XV. TroubleshootingTo the Owner II. SafetyTo the Installer Homeowner NoticeCSA International III. Product ApplicationAmerican National Standards Institute National Fire Protection AssociationNational Fire Protection Association, Inc IV. Location Requirements and ConsiderationsGeneral Existing Furnace Removal Clearances and AccessibilityHorizontal Installation Suspended FurnaceThermostat Influences Z223.1 Section GeneralEquipment Located in Unconfined Spaces Equipment Located in Confined Spaces Space, UnconfinedModel Minimum Vent Specially Engineered InstallationsVI. Category I Venting Vertical Venting Louvers and GrillesTypical Multiple Flue Clay Tile Chimney Checklist SummaryVII. Exterior Masonry Chimneys Category I Furnaces only Upflow Rotated Induced Draft BlowerTermination More Than 10 Feet From Ridge, Wall or Parapet Termination 10 Feet Or Less From Ridge, Wall or ParapetCheck 1 Proper Chimney Termination Check 5 Liner Condition Check 4 Debris in CleanoutCheck 7 Complete the Installation Check 3 Chimney Crown ConditionFIX 4 Relining VIII. Electrical ConnectionsFIX 2 -CHANGE Venting Arrangements FIX 3 Rebuild the CrownFossil Fuiel Applications Wiring HarnessIntegrated Ignition Control Volt Line ConnectionsHeating Heating/Cooling Room Thermostat Typical Field Wiring 24 VAC Control CircuitVolt Thermostat Wiring Setting the Heat AnticipatorTwinning IX. GAS Supply and PipingHigh Altitude Derate Propane GAS Conversion Pressure Switch Changes Furnace input Kbtu/hr904BNA does not require a switch change Firing RateGeneral Furnace Layout Upflow InstallationsGAS Piping Connections General GAS Piping Checks Propane Gas Installation TypCounterflow Installations Propane GAS Piping ChartsXI. Sequence of Operation Integrated Ignition Control Circulating AIR and FiltersDuctwork Air White-Rodgers Model 36F22 XII. START-UP Procedure and AdjustmentWhite-Rodgers Model 36G22 WHITE-RODGERS 36F22 GAS Valve White-Rodgers Model 36G22Measuring Inlet Gas Pressure Alternate Method GAS Supply Pressure MeasurementGAS Input Rate Measurement Natural GAS only GAS Manifold Pressure Measurement and AdjustmentAdjustment Switches Temperature Rise MeasurementXIII. Operational Checks XV. Troubleshooting XIV. Safety Circuit DescriptionBurner Flame XVI. Maintenance Induced Draft and Circulator Blower Motors Flame Sensor Qualified Servicer onlyIgniter Qualified Servicer only Upright Filter RemovalTroubleshooting Chart Continuously Wiring Diagram for GMS8/GDS8/GHS8 Are Subject to Change Without Notice
Related manuals
Manual 16 pages 38.83 Kb

GMS8, GHS8, GDS8 specifications

Goodman Manufacturing, a well-reputed name in the HVAC industry, offers a comprehensive range of heating and cooling solutions. Among their notable products are the GDS8, GHS8, and GMS8 series, each designed to meet diverse customer needs while providing exceptional performance and energy efficiency.

The Goodman GDS8 gas furnace is known for its remarkable efficiency and reliability. Boasting an AFUE (Annual Fuel Utilization Efficiency) rating of up to 80%, the GDS8 converts a significant portion of fuel into usable heat, ensuring lower energy bills for homeowners. This model features a multi-speed blower motor that optimizes airflow, enhancing temperature consistency throughout the home, and reducing noise levels during operation. The GDS8 comes equipped with a durable heat exchanger crafted from high-quality steel, ensuring longevity and optimal heat transfer.

On the other hand, the GHS8 series represents Goodman’s commitment to high-efficiency heating. With an AFUE rating of up to 96%, the GHS8 is engineered for maximum performance. Its two-stage heating system allows for better temperature control, enabling the furnace to operate quietly and efficiently. Another standout feature is the ComfortBridge technology, which enhances the system’s ability to communicate and adapt to the home’s specific heating needs. This feature optimizes energy usage and increases comfort levels in any environment.

The Goodman GMS8 model is an exceptional choice for homeowners looking for a reliable gas furnace with a focus on energy efficiency. Similar to its counterparts, the GMS8 also delivers an AFUE of up to 96.5%. This unit features an advanced modulating gas valve that adjusts heating output based on the temperature requirements, creating a consistent and comfortable indoor climate. The GMS8 is also equipped with a high-efficiency ECM blower motor, which reduces energy consumption while improving airflow.

All three models feature Goodman’s quality construction, including a heavy-gauge cabinet that minimizes noise and enhances durability. They also are backed by Goodman’s limited lifetime warranty on the heat exchanger and a 10-year limited warranty on parts, providing customers with peace of mind regarding their investment. These furnaces are designed with efficiency and comfort in mind, making the GDS8, GHS8, and GMS8 ideal choices for homeowners looking to enhance their indoor environment while keeping energy costs in check.