Goodman Mfg GMS8, GDS8, GHS8 IX. GAS Supply and Piping, Twinning, High Altitude Derate

Page 17

24 VAC HUM

1.24 VAC Hum - A ¼” piggy back quick connect terminal on the pressure switch provides 24 VAC humidifier control. This terminal will be powered any time the pressure switch is closed. To connect 24 VAC hum, connect 24vac line of humidifier to piggyback on the pressure switch. The com side of the humidfier to C on the terminal strip on the control board (or to com side to 24VAC transformer). Do not connect 115V humidifier to these terminals.

TWINNING

A twin terminal located on the thermostat terminal strip can be used to twin two furnaces. This twin terminal synchronizes the circulation blowers of the two furnaces. Furnaces must be same model and heat / cool speeds the same. In addition, both furnaces must be powered by separate circuits originating from the same power leg in the main electrical box (hot and neutral must be in phase). Furnaces can be twinned to provide either single or 2-stage heat. If used as 2-stage heat the temperature rise from the register to return will be reduced during low fire operation.

To twin furnaces, ensure models are the same. Connect twin terminals on both furnaces and ensure heat and cool speeds are the same on both furnaces. For single stage operation, wire thermostat as normal to one of the furnaces. Conncect W from furnace 1 to one of the coil terminals on an isolation relay. Connect the other coil terminal to C of furnace 1. Connect R of furnace 2 to the common terminal of the isolation relay. Connect normally open (NO) to W of furnace 2.

For 2-stage operation connect twin of both furnaces. Connect one furnace to 2-stage thermostat as normal, connecting W1 on thermostat to W on this furnace. Connect W2 from thermostat to the coil terminal on isolation relay. Connect the other coil terminal to C of furnace 1. Connect common of the isolation relay to R on furnace 2 and normally open (NO) to W of furnace 2. With 2- stage configuration, furnace 1 will provide low stage heat (circulator blower of furnace 2 will run at heat speed). During a call for High heat both furnaces will operate.

NOTE: Check operation of twin by turning thermostat to “fan on” or placing a jumper wire from R to G (furnace connected to thermostat). If twinning wire is working properly, both blowers will turn on at the same speed. If twinning does not work properly, check proper 24-volt polarity and ensure both furnaces are powered from the same power leg. If the 24-volt polarity is incorrect, switch common and 24-volt leads on furnace that is not working. Check operation.

Furnace 1

Furnace 2

TWIN Y W R G C

TWIN Y W R G C

 

NO

 

C

Isolation Relay

Thermostat

Furnace 1

Furnace 2

TWIN Y W R

G C

TWIN Y W R G C

 

 

NO

 

 

C

R

W

Isolation Relay

Y

G

W2

 

2-Stage Thermostat

IX. GAS SUPPLY AND PIPING

GENERAL

The furnace rating plate includes the approved furnace gas input rating and gas types. The furnace must be equipped to operate on the type of gas applied. This includes any conversion kits required for alternate fuels and/or high altitude.

CAUTION

TO PREVENT UNRELIABLE OPERATION OR EQUIPMENT DAMAGE, THE INLET GAS SUPPLY PRESSURE MUST BE AS SPECIFIED ON THE UNIT RATING PLATE WITH ALL OTHER HOUSEHOLD GAS FIRED APPLIANCES OPERATING.

Inlet gas supply pressures must be maintained within the ranges specified in the following table. The supply pressure must be constant and available with all other household gas fired appliances operating. The minimum gas supply pressure must be maintained to prevent unreliable ignition. The maximum must not be exceeded to prevent unit overfiring.

Inlet Gas Supply Pressure

Natural Gas

Minimum: 5.0" w.c.

Maximum:10.0" w.c.

Propane Gas

Minimum: 11.0" w.c.

Maximum:13.0" w.c.

NOTE: Adjusting the minimum supply pressure below the limits in the above table could lead to unreliable ignition. Gas input to the burners must not exceed the rated input shown on the rating plate. Overfiring of the furnace can result in premature heat exchanger failure. Gas pressures in excess of 13 inches water column can also cause permanent damage to the gas valve.

At all altitudes, the manifold pressure must be within 0.3 inches w.c. of that listed in the Product Data Book applicable to your model for the fuel used. At all altitudes and with either fuel, the air temperature rise must be within the range listed on the furnace nameplate. Should this appliance be converted to LP, refer to the instructions included in the factory authorized LP conversion kit LPT* .

HIGH ALTITUDE DERATE

IMPORTANT NOTE: The furnace will naturally derate itself with altitude. Do not attempt to increase the firing rate by changing orifices or increasing the manifold pressure. This can cause poor combustion and equipment failure.

When this furnace is installed at high altitude, the appropriate High Altitude orifice kit must be applied. The furnace is supplied with orifices sized for natural gas at altitudes up to 4,500 feet

IO-242C

17

05/05

 

 

Image 17
Contents Installation & Operating Table of Contents XIV. Safety Circuit Description XII. Start-up Procedure and AdjustmentXV. Troubleshooting XVI. MaintenanceTo the Installer II. SafetyHomeowner Notice To the OwnerAmerican National Standards Institute III. Product ApplicationNational Fire Protection Association CSA InternationalGeneral IV. Location Requirements and ConsiderationsNational Fire Protection Association, Inc Horizontal Installation Clearances and AccessibilitySuspended Furnace Existing Furnace RemovalEquipment Located in Unconfined Spaces Z223.1 Section GeneralThermostat Influences Equipment Located in Confined Spaces Space, UnconfinedVI. Category I Venting Vertical Venting Specially Engineered InstallationsLouvers and Grilles Model Minimum VentVII. Exterior Masonry Chimneys Category I Furnaces only Checklist SummaryUpflow Rotated Induced Draft Blower Typical Multiple Flue Clay Tile ChimneyCheck 1 Proper Chimney Termination Termination 10 Feet Or Less From Ridge, Wall or ParapetTermination More Than 10 Feet From Ridge, Wall or Parapet Check 7 Complete the Installation Check 4 Debris in CleanoutCheck 3 Chimney Crown Condition Check 5 Liner ConditionFIX 2 -CHANGE Venting Arrangements VIII. Electrical ConnectionsFIX 3 Rebuild the Crown FIX 4 ReliningIntegrated Ignition Control Wiring HarnessVolt Line Connections Fossil Fuiel ApplicationsVolt Thermostat Wiring Typical Field Wiring 24 VAC Control CircuitSetting the Heat Anticipator Heating Heating/Cooling Room ThermostatHigh Altitude Derate IX. GAS Supply and PipingTwinning 904BNA does not require a switch change Pressure Switch Changes Furnace input Kbtu/hrFiring Rate Propane GAS ConversionGAS Piping Connections General Upflow InstallationsGeneral Furnace Layout Counterflow Installations Propane Gas Installation TypPropane GAS Piping Charts GAS Piping ChecksDuctwork Air Circulating AIR and FiltersXI. Sequence of Operation Integrated Ignition Control White-Rodgers Model 36G22 XII. START-UP Procedure and AdjustmentWhite-Rodgers Model 36F22 Measuring Inlet Gas Pressure Alternate Method White-Rodgers Model 36G22GAS Supply Pressure Measurement WHITE-RODGERS 36F22 GAS ValveGAS Input Rate Measurement Natural GAS only GAS Manifold Pressure Measurement and AdjustmentXIII. Operational Checks Temperature Rise MeasurementAdjustment Switches Burner Flame XIV. Safety Circuit DescriptionXV. Troubleshooting XVI. Maintenance Igniter Qualified Servicer only Flame Sensor Qualified Servicer onlyUpright Filter Removal Induced Draft and Circulator Blower MotorsTroubleshooting Chart Continuously Wiring Diagram for GMS8/GDS8/GHS8 Are Subject to Change Without Notice
Related manuals
Manual 16 pages 38.83 Kb

GMS8, GHS8, GDS8 specifications

Goodman Manufacturing, a well-reputed name in the HVAC industry, offers a comprehensive range of heating and cooling solutions. Among their notable products are the GDS8, GHS8, and GMS8 series, each designed to meet diverse customer needs while providing exceptional performance and energy efficiency.

The Goodman GDS8 gas furnace is known for its remarkable efficiency and reliability. Boasting an AFUE (Annual Fuel Utilization Efficiency) rating of up to 80%, the GDS8 converts a significant portion of fuel into usable heat, ensuring lower energy bills for homeowners. This model features a multi-speed blower motor that optimizes airflow, enhancing temperature consistency throughout the home, and reducing noise levels during operation. The GDS8 comes equipped with a durable heat exchanger crafted from high-quality steel, ensuring longevity and optimal heat transfer.

On the other hand, the GHS8 series represents Goodman’s commitment to high-efficiency heating. With an AFUE rating of up to 96%, the GHS8 is engineered for maximum performance. Its two-stage heating system allows for better temperature control, enabling the furnace to operate quietly and efficiently. Another standout feature is the ComfortBridge technology, which enhances the system’s ability to communicate and adapt to the home’s specific heating needs. This feature optimizes energy usage and increases comfort levels in any environment.

The Goodman GMS8 model is an exceptional choice for homeowners looking for a reliable gas furnace with a focus on energy efficiency. Similar to its counterparts, the GMS8 also delivers an AFUE of up to 96.5%. This unit features an advanced modulating gas valve that adjusts heating output based on the temperature requirements, creating a consistent and comfortable indoor climate. The GMS8 is also equipped with a high-efficiency ECM blower motor, which reduces energy consumption while improving airflow.

All three models feature Goodman’s quality construction, including a heavy-gauge cabinet that minimizes noise and enhances durability. They also are backed by Goodman’s limited lifetime warranty on the heat exchanger and a 10-year limited warranty on parts, providing customers with peace of mind regarding their investment. These furnaces are designed with efficiency and comfort in mind, making the GDS8, GHS8, and GMS8 ideal choices for homeowners looking to enhance their indoor environment while keeping energy costs in check.