Goodman Mfg GDS8, GHS8, GMS8 instruction manual GAS Manifold Pressure Measurement and Adjustment

Page 24

GAS MANIFOLD PRESSURE MEASUREMENT AND ADJUSTMENT

CAUTION

TO PREVENT UNRELIABLE OPERATION OR EQUIPMENT DAMAGE, THE GAS MANIFOLD PRESSURE MUST BE AS SPECIFIED ON THE UNIT RATING PLATE. ONLY MINOR ADJUSTMENTS SHOULD BE MADE BY ADJUSTING THE GAS VALVE PRESSURE REGULATOR.

WHITE-RODGERS 36F22 GAS VALVE

Only small variations in gas pressure should be made by adjusting the gas valve pressure regulator. The manifold pressure must be measured with the burners operating. To measure and adjust the manifold pressure, use the following procedure.

1.Turn OFF gas to furnace at the manual gas shutoff valve external to the furnace.

2.Connect a calibrated water manometer (or appropriate gas pressure gauge) at the gas valve outlet pressure tap (refer to gas valve figure in previous section).

3.Turn ON the gas supply and operate the furnace.

4.Measure gas manifold pressure with burners firing. Adjust manifold pressure according to the Manifold Gas Pressure table:

Manifold Gas Pressure

Ga s

 

Range

Nominal

 

 

 

 

Natural

3.2

- 3.8" w.c.

3.5" w.c.

Propane

9.7

- 10.3" w.c.

10.0" w.c.

6.Remove regulator screw cover. Turn regulator screw either clockwise to increase pressure or counterclockwise to decrease. Always adjust regulator to provide the correct pressure according to the original equipment manufacturer specifications listed on the appliance rating plate.

7.Replace regulator screw cover and finger-tighten securely.

8.Turn OFF all electrical power to the system.

9.Remove manometer and hose from outlet pressure tap.

10.Tighten outlet pressure tap clockwise 7 in-lbs minimum to seal port.

11.Turn ON system power and set thermostat to call for heat.

12.Using a leak detection solution or non-chlorine soap suds, check for leaks at hose connection. Bubbles forming indicate a leak. SHUT OFF GAS AND FIX ALL LEAKS IMMEDIATELY!

Measure gas manifold pressure with burners firing. Adjust manifold pressure per the Manifold Gas Pressure table.

Manifold Gas Pressure

Gas

 

Range

Nominal

 

 

 

 

Natural

3.2

- 3.8" w.c.

3.5" w.c.

Propane

9.7

- 10.3" w.c.

10.0" w.c.

The final manifold pressure must not vary more than ± 0.3 w.c. from specified manifold pressure.

Any necessary major changes in gas flow rate should be made by changing the size of the burner orifice.

GAS INPUT RATE MEASUREMENT (NATURAL GAS ONLY)

The final manifold pressure must not vary more than ± 0.3 “ w.c. The gas input rate to the furnace must never be greater than that

from the above specified pressures. Any necessary major changes

specified on the unit rating plate. To measure natural gas input

in gas flow rate should be made by changing the size of the burner

using the gas meter, use the following procedure.

orifice.

 

1.

Turn OFF the gas supply to all other gas-burning

5.

To adjust the gas valve pressure regulator, remove the

 

appliances except the furnace.

 

regulator cap.

 

 

 

 

2.

While the furnace is operating, time and record one

6.

Turn the adjustment screw clockwise to increase the

 

complete revolution of the smallest gas meter dial.

 

pressure, or counterclockwise to decrease the pressure.

 

 

3. Calculate the number of seconds per cubic foot (sec/ ft3) of

7.

Securely replace the regulator cap.

 

gas being delivered to the furnace. If the dial is a one cubic

8.

Turn OFF gas to furnace at the manual shutoff valve and

 

 

foot dial, divide the number of seconds recorded in step 2

 

disconnect manometer.

 

 

 

by one. If the dial is a two cubic foot dial, divide the number

9.

Reinstall gas valve outlet pressure tap plug before turning

 

 

of seconds recorded in step 2 by two.

 

on gas to furnace.

 

4. Calculate the furnace input in BTUs per hour (BTU/ hr).

WHITE-RODGERS 36G22 GAS VALVE

 

Input equals the sum of the installation’s gas heating value

This valve is shipped from the factory with the regulator preset

 

and a conversion factor (hours to seconds) divided by the

 

number of seconds per cubic foot. The measured input

(see control label).

 

 

 

 

must not be greater than the input indicated on the unit

Consult the appliance rating plate to ensure burner manifold

 

 

rating plate.

pressure is as specified.

If another outlet pressure is required,

 

EXAMPLE:

follow these steps.

 

 

Installation’s gas heating (HTG) value: 1,000 BTU/ft3

1.

Turn OFF all electrical power to the system.

 

(Obtained from gas supplier)

2.

Using a 3/32 inch hex wrench, loosen outlet pressure tap

 

Installation’s seconds per cubic foot: 34 sec/ ft3

 

screw one turn. Do not remove screw.

 

Conversion Factor (hours to seconds): 3600 sec/hr

3.

Connect a calibrated water manometer and 5/16 inch hose

 

Input = (Htg. value x 3600) ÷ seconds per cubic foot

 

to the gas valve outlet pressure tap. Hose should overlap

 

Input = (1,000 BTU/ft3 x 3600 sec/hr) ÷ 34 sec/ ft3

 

tap by 3/8 inch.

 

 

Input = 106,000 BTU/hr

4.

Turn ON system power and set thermostat to a call for

 

 

This measured input must not be greater than the input

 

heat.

 

 

 

 

 

indicated on the unit rating plate.

5.

Using a leak detection solution or non-chlorine soap suds,

 

5. Turn ON gas and relight appliances turned off in step 1.

 

check for leaks at hose connection. Bubbles forming

 

 

Ensure all the appliances are functioning properly and that

 

indicate a leak. SHUT OFF GAS AND FIX ALL LEAKS

 

 

 

all pilot burners are operating.

 

IMMEDIATELY!

 

 

 

 

 

 

IO-242C

24

05/05

Image 24
Contents Installation & Operating Table of Contents XII. Start-up Procedure and Adjustment XIV. Safety Circuit DescriptionXV. Troubleshooting XVI. MaintenanceII. Safety To the InstallerHomeowner Notice To the OwnerIII. Product Application American National Standards InstituteNational Fire Protection Association CSA InternationalIV. Location Requirements and Considerations National Fire Protection Association, IncGeneral Clearances and Accessibility Horizontal InstallationSuspended Furnace Existing Furnace RemovalZ223.1 Section General Thermostat InfluencesEquipment Located in Unconfined Spaces Space, Unconfined Equipment Located in Confined SpacesSpecially Engineered Installations VI. Category I Venting Vertical VentingLouvers and Grilles Model Minimum VentChecklist Summary VII. Exterior Masonry Chimneys Category I Furnaces onlyUpflow Rotated Induced Draft Blower Typical Multiple Flue Clay Tile ChimneyTermination 10 Feet Or Less From Ridge, Wall or Parapet Termination More Than 10 Feet From Ridge, Wall or ParapetCheck 1 Proper Chimney Termination Check 4 Debris in Cleanout Check 7 Complete the InstallationCheck 3 Chimney Crown Condition Check 5 Liner ConditionVIII. Electrical Connections FIX 2 -CHANGE Venting ArrangementsFIX 3 Rebuild the Crown FIX 4 ReliningWiring Harness Integrated Ignition ControlVolt Line Connections Fossil Fuiel ApplicationsTypical Field Wiring 24 VAC Control Circuit Volt Thermostat WiringSetting the Heat Anticipator Heating Heating/Cooling Room ThermostatIX. GAS Supply and Piping TwinningHigh Altitude Derate Pressure Switch Changes Furnace input Kbtu/hr 904BNA does not require a switch changeFiring Rate Propane GAS ConversionUpflow Installations General Furnace LayoutGAS Piping Connections General Propane Gas Installation Typ Counterflow InstallationsPropane GAS Piping Charts GAS Piping ChecksCirculating AIR and Filters XI. Sequence of Operation Integrated Ignition ControlDuctwork Air XII. START-UP Procedure and Adjustment White-Rodgers Model 36F22White-Rodgers Model 36G22 White-Rodgers Model 36G22 Measuring Inlet Gas Pressure Alternate MethodGAS Supply Pressure Measurement WHITE-RODGERS 36F22 GAS ValveGAS Manifold Pressure Measurement and Adjustment GAS Input Rate Measurement Natural GAS onlyTemperature Rise Measurement Adjustment SwitchesXIII. Operational Checks XIV. Safety Circuit Description XV. TroubleshootingBurner Flame XVI. Maintenance Flame Sensor Qualified Servicer only Igniter Qualified Servicer onlyUpright Filter Removal Induced Draft and Circulator Blower MotorsTroubleshooting Chart Continuously Wiring Diagram for GMS8/GDS8/GHS8 Are Subject to Change Without Notice
Related manuals
Manual 16 pages 38.83 Kb

GMS8, GHS8, GDS8 specifications

Goodman Manufacturing, a well-reputed name in the HVAC industry, offers a comprehensive range of heating and cooling solutions. Among their notable products are the GDS8, GHS8, and GMS8 series, each designed to meet diverse customer needs while providing exceptional performance and energy efficiency.

The Goodman GDS8 gas furnace is known for its remarkable efficiency and reliability. Boasting an AFUE (Annual Fuel Utilization Efficiency) rating of up to 80%, the GDS8 converts a significant portion of fuel into usable heat, ensuring lower energy bills for homeowners. This model features a multi-speed blower motor that optimizes airflow, enhancing temperature consistency throughout the home, and reducing noise levels during operation. The GDS8 comes equipped with a durable heat exchanger crafted from high-quality steel, ensuring longevity and optimal heat transfer.

On the other hand, the GHS8 series represents Goodman’s commitment to high-efficiency heating. With an AFUE rating of up to 96%, the GHS8 is engineered for maximum performance. Its two-stage heating system allows for better temperature control, enabling the furnace to operate quietly and efficiently. Another standout feature is the ComfortBridge technology, which enhances the system’s ability to communicate and adapt to the home’s specific heating needs. This feature optimizes energy usage and increases comfort levels in any environment.

The Goodman GMS8 model is an exceptional choice for homeowners looking for a reliable gas furnace with a focus on energy efficiency. Similar to its counterparts, the GMS8 also delivers an AFUE of up to 96.5%. This unit features an advanced modulating gas valve that adjusts heating output based on the temperature requirements, creating a consistent and comfortable indoor climate. The GMS8 is also equipped with a high-efficiency ECM blower motor, which reduces energy consumption while improving airflow.

All three models feature Goodman’s quality construction, including a heavy-gauge cabinet that minimizes noise and enhances durability. They also are backed by Goodman’s limited lifetime warranty on the heat exchanger and a 10-year limited warranty on parts, providing customers with peace of mind regarding their investment. These furnaces are designed with efficiency and comfort in mind, making the GDS8, GHS8, and GMS8 ideal choices for homeowners looking to enhance their indoor environment while keeping energy costs in check.