Goodman Mfg GMS8, GDS8 Propane Gas Installation Typ, Counterflow Installations, GAS Piping Checks

Page 20

COUNTERFLOW INSTALLATIONS

When the gas piping enters through the left side of the furnace, the installer must supply a straight pipe to reach the exterior of the furnace.

A ground joint union, drip leg, and manual shutoff valve must also be supplied by the installer. In some cases, the installer may also need to supply a transition piece from 1/2" to another pipe size. When the gas piping enters through the right side of the furnace, the installer must supply the following fittings (starting at the gas valve):

90 degree elbow.

Close nipple.

90 degree elbow.

Straight pipe to reach exterior of furnace.

GAS PIPING CHECKS

Before placing unit in operation, leak test the unit and gas connections.

WARNING

TO AVOID THE POSSIBILITY OF EXPLOSION OR FIRE, NEVER USE A MATCH OR OPEN FLAME TO TEST FOR LEAKS.

Check for leaks using an approved chloride-free soap and water solution, an electronic combustible gas detector, or other approved testing methods.

CAUTION

TO PREVENT PROPERTY DAMAGE OR PERSONAL INJURY DUE TO FIRE, THE FOLLOWING INSTRUCTIONS MUST BE PERFORMED REGARDING GAS CONNECTIONS, PRESSURE TESTING, LOCATION OF SHUTOFF VALVE AND INSTALLATION OF GAS PIPING.

NOTE: Never exceed specified pressures for testing. Higher pressure may damage the gas valve and cause subsequent overfiring, resulting in heat exchanger failure.

Disconnect this unit and shutoff valve from the gas supply piping system before pressure testing the supply piping system with pressures in excess of 1/2 psig (3.48 kPa).

This unit must be isolated from the gas supply system by closing its manual shutoff valve before pressure testing of gas supply piping system with test pressures equal to or less than 1/2 psig (3.48 kPa).

PROPANE GAS TANKS AND PIPING

WARNING

IF THE GAS FURNACE IS INSTALLED IN A BASEMENT, AN EXCAVATED AREA OR A CONFINED SPACE, IT IS STRONGLY RECOMMENDED TO CONTACT A PROPANE SUPPLIER TO INSTALL A GAS DETECTING WARNING DEVICE IN CASE OF A GAS LEAK.

SINCE PROPANE GAS IS HEAVIER THAN AIR, ANY LEAKING GAS CAN SETTLE IN ANY LOW AREAS OR CONFINED SPACES.

PROPANE GAS ODORANT MAY FADE, MAKING THE GAS UNDETECTABLE EXCEPT WITH A WARNING DEVICE.

A gas detecting warning system is the only reliable way to detect a propane gas leak. Rust can reduce the level of odorant in propane gas. Do not rely on your sense of smell. Contact a local propane

gas supplier about installing a gas detecting warning system. If the presence of gas is suspected, follow the instructions on Page 4 of this manual.

All propane gas equipment must conform to the safety standards of the National Board of Fire Underwriters, NBFU Manual 58.

For satisfactory operation, propane gas pressure must be 11 inch WC at the furnace manifold with all gas appliances in operation. Maintaining proper gas pressure depends on three main factors:

1.Vaporization rate, depending on temperature of the liquid, and “wetted surface” area of the container or containers.

2.Proper pressure regulation. (Two-stage regulation is recommended for both cost and efficiency).

3.Pressure drop in lines between regulators, and between second stage regulator and the appliance. Pipe size will depend on length of pipe run and total load of all appliances.

Complete information regarding tank sizing for vaporization, recommended regulator settings, and pipe sizing is available from most regulator manufacturers and propane gas suppliers.

Since propane gas will quickly dissolve white lead and most standard commercial compounds, special pipe dope must be used. Shellac-based compounds resistant to the actions of liquefied petroleum gases such as Gasolac®, Stalactic®, Clyde’s® or John Crane® are satisfactory.

Refer to the following illustration for typical propane gas installations and piping.

First Stage

5 to 15 PSIG

 

 

 

(20 PSIG Max.)

 

 

 

Regulator

Continuous

 

 

 

 

 

11" W.C.

200 PSIG

 

 

Second Stage

 

Maximum

 

 

Regulator

 

 

 

 

 

 

 

 

 

 

 

 

 

Propane Gas Installation (Typ.)

PROPANE GAS PIPING CHARTS

Sizing Between First and Second Stage Regulator*

Maximum Propane Capacities listed are based on 2 psig pressure drop at 10 psig setting. Capacities in 1,000 BTU/hour.

Pipe or

 

Tubing Size, O.D. Type L

 

Nominal Pipe Size

Tubing

 

 

 

 

 

 

 

Schedule 40

Length,

 

 

 

 

 

3/8"

1/2"

5/8"

3/4"

7/8"

1/2"

3/4"

Feet

10

730

1,700

3,200

5,300

8,300

3,200

7,500

20

500

1,100

2,200

3,700

5,800

2,200

4,200

30

400

920

2,000

2,900

4,700

1,800

4,000

40

370

850

1,700

2,700

4,100

1,600

3,700

50

330

770

1,500

2,400

3,700

1,500

3,400

60

300

700

1,300

2,200

3,300

1,300

310

80

260

610

1,200

1,900

2,900

1,200

2,600

100

220

540

1,000

1,700

2,600

1,000

2,300

125

200

490

900

1,400

2,300

900

2,100

150

190

430

830

1,300

2,100

830

1,900

175

170

400

780

1,200

1,900

770

1,700

200

160

380

730

1,100

1,800

720

1,500

IO-242C

20

05/05

Image 20
Contents Installation & Operating Table of Contents XII. Start-up Procedure and Adjustment XIV. Safety Circuit DescriptionXV. Troubleshooting XVI. MaintenanceII. Safety To the InstallerHomeowner Notice To the OwnerIII. Product Application American National Standards InstituteNational Fire Protection Association CSA InternationalGeneral IV. Location Requirements and ConsiderationsNational Fire Protection Association, Inc Clearances and Accessibility Horizontal InstallationSuspended Furnace Existing Furnace RemovalEquipment Located in Unconfined Spaces Z223.1 Section GeneralThermostat Influences Space, Unconfined Equipment Located in Confined SpacesSpecially Engineered Installations VI. Category I Venting Vertical VentingLouvers and Grilles Model Minimum VentChecklist Summary VII. Exterior Masonry Chimneys Category I Furnaces onlyUpflow Rotated Induced Draft Blower Typical Multiple Flue Clay Tile ChimneyCheck 1 Proper Chimney Termination Termination 10 Feet Or Less From Ridge, Wall or ParapetTermination More Than 10 Feet From Ridge, Wall or Parapet Check 4 Debris in Cleanout Check 7 Complete the InstallationCheck 3 Chimney Crown Condition Check 5 Liner ConditionVIII. Electrical Connections FIX 2 -CHANGE Venting ArrangementsFIX 3 Rebuild the Crown FIX 4 ReliningWiring Harness Integrated Ignition ControlVolt Line Connections Fossil Fuiel ApplicationsTypical Field Wiring 24 VAC Control Circuit Volt Thermostat WiringSetting the Heat Anticipator Heating Heating/Cooling Room ThermostatHigh Altitude Derate IX. GAS Supply and PipingTwinning Pressure Switch Changes Furnace input Kbtu/hr 904BNA does not require a switch changeFiring Rate Propane GAS ConversionGAS Piping Connections General Upflow InstallationsGeneral Furnace Layout Propane Gas Installation Typ Counterflow InstallationsPropane GAS Piping Charts GAS Piping ChecksDuctwork Air Circulating AIR and FiltersXI. Sequence of Operation Integrated Ignition Control White-Rodgers Model 36G22 XII. START-UP Procedure and AdjustmentWhite-Rodgers Model 36F22 White-Rodgers Model 36G22 Measuring Inlet Gas Pressure Alternate MethodGAS Supply Pressure Measurement WHITE-RODGERS 36F22 GAS ValveGAS Manifold Pressure Measurement and Adjustment GAS Input Rate Measurement Natural GAS onlyXIII. Operational Checks Temperature Rise MeasurementAdjustment Switches Burner Flame XIV. Safety Circuit DescriptionXV. Troubleshooting XVI. Maintenance Flame Sensor Qualified Servicer only Igniter Qualified Servicer onlyUpright Filter Removal Induced Draft and Circulator Blower MotorsTroubleshooting Chart Continuously Wiring Diagram for GMS8/GDS8/GHS8 Are Subject to Change Without Notice
Related manuals
Manual 16 pages 38.83 Kb

GMS8, GHS8, GDS8 specifications

Goodman Manufacturing, a well-reputed name in the HVAC industry, offers a comprehensive range of heating and cooling solutions. Among their notable products are the GDS8, GHS8, and GMS8 series, each designed to meet diverse customer needs while providing exceptional performance and energy efficiency.

The Goodman GDS8 gas furnace is known for its remarkable efficiency and reliability. Boasting an AFUE (Annual Fuel Utilization Efficiency) rating of up to 80%, the GDS8 converts a significant portion of fuel into usable heat, ensuring lower energy bills for homeowners. This model features a multi-speed blower motor that optimizes airflow, enhancing temperature consistency throughout the home, and reducing noise levels during operation. The GDS8 comes equipped with a durable heat exchanger crafted from high-quality steel, ensuring longevity and optimal heat transfer.

On the other hand, the GHS8 series represents Goodman’s commitment to high-efficiency heating. With an AFUE rating of up to 96%, the GHS8 is engineered for maximum performance. Its two-stage heating system allows for better temperature control, enabling the furnace to operate quietly and efficiently. Another standout feature is the ComfortBridge technology, which enhances the system’s ability to communicate and adapt to the home’s specific heating needs. This feature optimizes energy usage and increases comfort levels in any environment.

The Goodman GMS8 model is an exceptional choice for homeowners looking for a reliable gas furnace with a focus on energy efficiency. Similar to its counterparts, the GMS8 also delivers an AFUE of up to 96.5%. This unit features an advanced modulating gas valve that adjusts heating output based on the temperature requirements, creating a consistent and comfortable indoor climate. The GMS8 is also equipped with a high-efficiency ECM blower motor, which reduces energy consumption while improving airflow.

All three models feature Goodman’s quality construction, including a heavy-gauge cabinet that minimizes noise and enhances durability. They also are backed by Goodman’s limited lifetime warranty on the heat exchanger and a 10-year limited warranty on parts, providing customers with peace of mind regarding their investment. These furnaces are designed with efficiency and comfort in mind, making the GDS8, GHS8, and GMS8 ideal choices for homeowners looking to enhance their indoor environment while keeping energy costs in check.