Goodman Mfg GHS8, GDS8 Suspended Furnace, Clearances and Accessibility, Horizontal Installation

Page 7

Refer to subbase instructions for installation details. Follow the instructions with the subbase for proper installation. Do not install the furnace directly on carpeting, tile, or other combustible material other than wood flooring. (Note: The subbase will not be required if an air conditioning coil is installed between the supply air opening on the furnace and the floor.)

Vent Pipe Clearance to Combustibles- 6" using Single Wall Connector or 1" using B-1 vent.

Top - 1"

Back - 0"

Side

Clearance - 1"

Front Clearance - 3"

Adequate combustion/ combustion air must be supplied to the closet.

Furnace must be completely sealed to floor or base. Combustion/ ventilation air supply pipes must terminate 12" from top of closet and 12" from floor of closet. DO NOT remove solid base plate for side return.

Return air ducts must be completely sealed to the furnace and terminate outside the enclosure surfaces.

CLEARANCES AND ACCESSIBILITY

Unobstructed front clearance of 24" for servicing is recommended.

 

VE NT

SID ES

FR O N T

B ACK

TO P

B1-V ENT

SING LE

(PLEN UM )

 

 

 

1"

 

6"

1"

3"

0"

1"

 

 

 

 

 

 

 

Top clearance for horizontal configuration - 1"

HORIZONTAL INSTALLATION

Line contact to framing is permitted when installed in the horizontal configuration. Line contact is defined as the portion of the cabinet that is formed by the intersection of the top and side.

ACCESSIBILITY CLEARANCE,WHERE GREATER, SHOULD TAKE PRECEDENCE OVER MINIMUM FIRE PROTECTION CLEARANCE. A gas-fired furnace for installation in a residential garage must be installed so that the ignition source and burners are located not less than eighteen inches (18") above the floor and is protected or located to prevent physical damage by vehicles. A gas furnace must not be installed directly on carpeting, tile, or other combustible materials other than wood flooring.

FURNACE SUSPENSION

If suspending the furnace from rafters or joist, use 3/8" threaded rod and 2”x2”x3/8” angle iron as shown below. The length of rod will depend on the application and the clearances necessary.

 

PROVIDE 8" MINMUM CLEARANCE BETWEEN

 

CENTER ROD AND FURNACE CABINET

 

TO ALLOW FOR CIRCULATOR BLOWER REMOVAL

3/8" DIAMETER

ASSURE FURNACE IS LEVEL FROM

END TO END AND HAS A SLIGHT

THREADED ROD

FORWARD TILT WITH THE FRONT

(6 PLACES)

OF THE FURNACE 0"-3/4"

 

HOLD DOWN

BELOW THE BACK OF THE FURNACE

NUTS

 

SUPPORT

NUTS

2" X 2" X 3/8"

ANGLE IRON

(3 PLACES)

POSITION AS CLOSE AS POSSIBLE TO BLOWER DECK TO ALLOW FOR CIRCULATOR BLOWER REMVOAL

TILT OUTWARD TO ALLOW FOR DOOR AND CIRCULATOR BLOWER REMOVAL

Suspended Furnace

EXISTING FURNACE REMOVAL

NOTE: When an existing furnace is removed from a venting system serving other appliances, the venting system may be too large to properly vent the remaining attached appliances.

The following vent testing procedure is reproduced from the

American National Standard/National Standard of Canada for Gas-Fired Central Furnaces ANSI Z21.47-1998, CSA-2.3-M98 Section 1.23.1. The following steps shall be followed with each appliance connected to the venting system placed in operation, while any other appliances connected to the venting system are not in operation:

a. Seal any unused openings in the venting system;

b. Inspect the venting system for proper size and horizontal pitch, as required by the National Fuel Gas Code, ANSI Z223.1 or the CAN/CSA B149 Installation Codes and these instructions. Determine that there is no blockage or restriction, leakage, corrosion and other deficiencies which could cause an unsafe condition;

c. In so far as practical, close all building doors and windows and all doors between the space in which the appliance(s) connected to the venting system are located and other spaces of the building. Turn on clothes dryers and any appliance not connected to the venting system. Turn on any exhaust fans, such as range hoods and bathroom exhausts, so they shall operate at maximum speed. Do not operate a summer exhaust fan. Close fireplace dampers;

d. Follow the lighting instructions. Place the appliance being inspected in operation. Adjust thermostat so appliance shall operate continuously;

e. Test for draft hood equipped appliance spillage at the draft hood relief opening after 5 minutes of main burner operation. Use the flame of a match or candle;

f.After it has been determined that each appliance connected to the venting system properly vents when tested as outlined above, return doors, windows, exhaust fans, fireplace dampers and any other gas burning appliance to their previous conditions of use;

g.If improper venting is observed during any of the above tests, the common venting system must be corrected.

IO-242C

7

05/05

 

 

Image 7
Contents Installation & Operating Table of Contents XVI. Maintenance XII. Start-up Procedure and AdjustmentXIV. Safety Circuit Description XV. TroubleshootingTo the Owner II. SafetyTo the Installer Homeowner NoticeCSA International III. Product ApplicationAmerican National Standards Institute National Fire Protection AssociationNational Fire Protection Association, Inc IV. Location Requirements and ConsiderationsGeneral Existing Furnace Removal Clearances and AccessibilityHorizontal Installation Suspended FurnaceThermostat Influences Z223.1 Section GeneralEquipment Located in Unconfined Spaces Equipment Located in Confined Spaces Space, UnconfinedModel Minimum Vent Specially Engineered InstallationsVI. Category I Venting Vertical Venting Louvers and GrillesTypical Multiple Flue Clay Tile Chimney Checklist SummaryVII. Exterior Masonry Chimneys Category I Furnaces only Upflow Rotated Induced Draft BlowerTermination More Than 10 Feet From Ridge, Wall or Parapet Termination 10 Feet Or Less From Ridge, Wall or ParapetCheck 1 Proper Chimney Termination Check 5 Liner Condition Check 4 Debris in CleanoutCheck 7 Complete the Installation Check 3 Chimney Crown ConditionFIX 4 Relining VIII. Electrical ConnectionsFIX 2 -CHANGE Venting Arrangements FIX 3 Rebuild the CrownFossil Fuiel Applications Wiring HarnessIntegrated Ignition Control Volt Line ConnectionsHeating Heating/Cooling Room Thermostat Typical Field Wiring 24 VAC Control CircuitVolt Thermostat Wiring Setting the Heat AnticipatorTwinning IX. GAS Supply and PipingHigh Altitude Derate Propane GAS Conversion Pressure Switch Changes Furnace input Kbtu/hr904BNA does not require a switch change Firing RateGeneral Furnace Layout Upflow InstallationsGAS Piping Connections General GAS Piping Checks Propane Gas Installation TypCounterflow Installations Propane GAS Piping ChartsXI. Sequence of Operation Integrated Ignition Control Circulating AIR and FiltersDuctwork Air White-Rodgers Model 36F22 XII. START-UP Procedure and AdjustmentWhite-Rodgers Model 36G22 WHITE-RODGERS 36F22 GAS Valve White-Rodgers Model 36G22Measuring Inlet Gas Pressure Alternate Method GAS Supply Pressure MeasurementGAS Input Rate Measurement Natural GAS only GAS Manifold Pressure Measurement and AdjustmentAdjustment Switches Temperature Rise MeasurementXIII. Operational Checks XV. Troubleshooting XIV. Safety Circuit DescriptionBurner Flame XVI. Maintenance Induced Draft and Circulator Blower Motors Flame Sensor Qualified Servicer onlyIgniter Qualified Servicer only Upright Filter RemovalTroubleshooting Chart Continuously Wiring Diagram for GMS8/GDS8/GHS8 Are Subject to Change Without Notice
Related manuals
Manual 16 pages 38.83 Kb

GMS8, GHS8, GDS8 specifications

Goodman Manufacturing, a well-reputed name in the HVAC industry, offers a comprehensive range of heating and cooling solutions. Among their notable products are the GDS8, GHS8, and GMS8 series, each designed to meet diverse customer needs while providing exceptional performance and energy efficiency.

The Goodman GDS8 gas furnace is known for its remarkable efficiency and reliability. Boasting an AFUE (Annual Fuel Utilization Efficiency) rating of up to 80%, the GDS8 converts a significant portion of fuel into usable heat, ensuring lower energy bills for homeowners. This model features a multi-speed blower motor that optimizes airflow, enhancing temperature consistency throughout the home, and reducing noise levels during operation. The GDS8 comes equipped with a durable heat exchanger crafted from high-quality steel, ensuring longevity and optimal heat transfer.

On the other hand, the GHS8 series represents Goodman’s commitment to high-efficiency heating. With an AFUE rating of up to 96%, the GHS8 is engineered for maximum performance. Its two-stage heating system allows for better temperature control, enabling the furnace to operate quietly and efficiently. Another standout feature is the ComfortBridge technology, which enhances the system’s ability to communicate and adapt to the home’s specific heating needs. This feature optimizes energy usage and increases comfort levels in any environment.

The Goodman GMS8 model is an exceptional choice for homeowners looking for a reliable gas furnace with a focus on energy efficiency. Similar to its counterparts, the GMS8 also delivers an AFUE of up to 96.5%. This unit features an advanced modulating gas valve that adjusts heating output based on the temperature requirements, creating a consistent and comfortable indoor climate. The GMS8 is also equipped with a high-efficiency ECM blower motor, which reduces energy consumption while improving airflow.

All three models feature Goodman’s quality construction, including a heavy-gauge cabinet that minimizes noise and enhances durability. They also are backed by Goodman’s limited lifetime warranty on the heat exchanger and a 10-year limited warranty on parts, providing customers with peace of mind regarding their investment. These furnaces are designed with efficiency and comfort in mind, making the GDS8, GHS8, and GMS8 ideal choices for homeowners looking to enhance their indoor environment while keeping energy costs in check.